Tender For Provn Of Rmus And Vcbs At Domestic Area Under Ge (Af) Adm Area At Af Station Agra
Tender Value
43.79 Lakhs
Estimated cost
Bid Submission
21 Nov 2026
0 days left
EMD
87580
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Agra → Uttar Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Rmus And Vcbs At Domestic Area Under Ge (Af) Adm Area At Af Station Agra
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of 11 kV class, 12 kV rated, outdoor, SF₆ gas-insulated Ring Main Unit (RMU), 5-way, one-side extensible, manual-operated type, complete with one manual vacuum circuit breaker (VCB) incomer and four manual VCB outgoing feeders, suitable for ring-main distribution, including bus metering panel, all specified accessories, interconnections, protection, earthing, cable termination provisions and all works necessary for a complete and operational installation, as specified below and as directed by the Engineer-in-Charge. |
| 2 | A. RMU Main Assembly.i) RMU configuration: 5-way, outdoor, SF₆ gas-insulated, one-side extensible, manual-operated RMU, comprising 1 No. VCB incomer + 4 Nos. VCB outgoing feeders, with bus metering panel (Me) and arrangement (LLLLL+Me).ii) Rated voltage: 12 kV.iii) Power frequency withstand voltage: 28 kV.iv) Lightning impulse withstand voltage: 75 kV.v) Rated current: 630 A for ring-main feeder at 40°C.vi) VCB feeder rated current: 630 A.vii) Short-time withstand current: 21 kA for 1 second, or as per the approved manufacturer’s guaranteed technical particulars.viii) Rated short-circuit making current: 50 kA, subject to approved OEM technical data.ix) Internal arc classification: IAC AFLR, 21 kA for 1 second, with pressure relief directed downwards, as offered and subject to approved OEM technical particulars.x) Main busbar material: Copper (Cu).xi) Enclosure: Outdoor, minimum IP54 degree of protection.xii) Ambient temperature: Suitable for operation at 40°C.xiii) Current rating / derating: 630 A at 40°C, 600 A at 45°C and 565 A at 50°C, or as per approved OEM guaranteed technical particulars.xiv) Paint finish: Powder-coated, RAL 7032, coating thickness 100 microns ±25 microns.Complete with all required SF₆ gas compartments, operating mechanisms, busbars, interconnections, cable compartments, pressure-relief arrangements, nameplates, warning labels and manufacturer’s standard accessories. |
| 3 | B. Vacuum Circuit Breaker Feeders — 5 Nos.Each VCB feeder shall include:i) One manual-operated VCB with ON–OFF position indication.ii) VCB auxiliary switch arrangement 2NO + 2NC + 2CH.iii) Manual disconnector with three-position ON–OFF switching arrangement.iv) Manual-operated spring mechanism with OFF–EARTH position indication.v) Numerical relay for 3O/C + 1E/F, Siemens C&S / Ashida make or approved equivalent, without RS485 port, complete with required protection functions and accessories.vi)One low-energy series release.vii) Three Nos. current transformers, ratio 400–200–100/1 A, Class 5P10, Cl. 1.0, burden 2.5 VA, make Reco / NPT or approved equivalent.viii) Socket for capacitive voltage indicator (CVI), Leenan make or approved equivalent.Padlocking facility.ix) Provision for connecting up to 1R × 3C × 300 sqmm HT power cable, including suitable cable-entry arrangements.x) All necessary internal wiring, terminal blocks, control wiring, operating handles, labels and accessories for complete operation. |
| 4 | C. Bus Metering Panel The bus metering panel shall include:i) Three Nos. 11 kV / √3 / 110 V / √3 / 110/3 V, Class 1.0, 50 VA, 3P, 50 VA voltage transformers, or as per approved OEM technical particulars.ii) One surge arrester.iii) One set indicating lamps R, Y, B, thermostat, space heater, 2-pin plug and socket.iv) One digital multifunction meter (MFM), Class 0.5.v) Complete internal wiring, terminal blocks, metering connections, labels and accessories.D. Common Accessoriesi) One No. operating lever.ii) One set cable boot, including all required accessories.iii) All necessary operating, locking, interlocking, earthing and safety accessories.iv) Manufacturer’s standard tools, keys and accessories required for operation and maintenance.E. Installation and Erection Scope The item shall include, but not be limited to, the following works:i) Transportation of the RMU from the manufacturer’s works / approved storage location to the site, including unloading, shifting, handling and placing at the designated installation location. Please Enable Macros to View BoQ information |
| 5 | C. Bus Metering Panel The bus metering panel shall include:i) Three Nos. 11 kV / √3 / 110 V / √3 / 110/3 V, Class 1.0, 50 VA, 3P, 50 VA voltage transformers, or as per approved OEM technical particulars.ii) One surge arrester.iii) One set indicating lamps R, Y, B, thermostat, space heater, 2-pin plug and socket.iv) One digital multifunction meter (MFM), Class 0.5.v) Complete internal wiring, terminal blocks, metering connections, labels and accessories.D. Common Accessoriesi) One No. operating lever.ii) One set cable boot, including all required accessories.iii) All necessary operating, locking, interlocking, earthing and safety accessories.iv) Manufacturer’s standard tools, keys and accessories required for operation and maintenance.E. Installation and Erection Scope The item shall include, but not be limited to, the following works:i) Transportation of the RMU from the manufacturer’s works / approved storage location to the site, including unloading, shifting, handling and placing at the designated installation location. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 31, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 21, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedNov 28, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender