Defence Statutory Bodies & Commissions/Committees Closing in 20 days TDR #58294213

Tender For Repair/Maint To Lt Network System At Ccosw, 9 R&O, 1 Ew And Other Locations Under Ge (U) Udh Ur.

Issued by Statutory Bodies & Commissions/Committees · Reasi, Jammu and Kashmir
Tender Value
47 Lakhs
Estimated cost
Bid Submission
20 Nov 2026
20 days left
EMD
94000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Reasi → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Repair/Maint To Lt Network System At Ccosw, 9 R&O, 1 Ew And Other Locations Under Ge (U) Udh Ur.

BOQ

Name of Work:- Repair/Maint to LT network system at CCOSW, 9 R&O, 1 EW and other locations under GE (U) Udh ur.
Sl. No. Item Description
1Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair/Maint to LT network system at CCOSW, 9 R&O, 1 EW and other locations under GE (U) Udhampur. Contract No: GE/U-126/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words
2Earthing complete with GI earth electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 meter below normal ground level with top edge of earth plate at a depth not less than 1.5 meter below normal ground surrounded from all sides by 15 CM thick and packed layer of charcoal dust and common salt filling in alternate layers cleaned connected to and including GI earth strip 32X6 mm size up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected light grade 20 mm bore for watering and including funnel wire mesh, RCC pit cover 50 mm thick and PCC chamber pit with PCC 1:3:6 type C-2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 meter) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 all as specified and directed by Engr-in-Charge.
3Supply and fix earth pit chamber board of 3.15mm thick mild steel sheet of size 45cmX30cm fixed with12mm thick MS rod two nos up to 90 cm height by nuts/bolts including spray painting with two coats of synthetic enamel black paint complete MS sheet both side including writing letters 6cm height i.e Eart pit No, Location, Earthing test Value and date complete all as directed by Engr-in-Charge.
4Material and labour for repairs of earthing chamber of size 450x450x300mm depth outside & 250x250x250 mm depth of PCC (1:4:8) type D-2 & including provn of PCC cover including painting of two coat as directed complete all as directed by Engr - in - Charge .
5Material and labour for Painting of earth pit chamber with two coat of acrylic emulsion paint including making the earth pit and colour of paint as directed by Engr - in - Charge .
6S & F GI earth continuity conductor or main earthing lead of size 32X6 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as specified and directed by Engr-in-Charge.
7S & F copper earth continuity conductor or main earthing lead of size 25x3 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as specified and directed by Engr-in-Charge.
8Supplying and laying in replacement of GI tubing light grade 40mm bore for protection of strip fixing to pole/wall or in such similar position complete all as specified and directed by Engr-in-Charge.
9Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming :- (a) C/O switch 400Amps 4 pole 50 KA-01 No.(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 set
10Outgoing ;- (a) MCCB 200 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-05 No.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables.(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover.(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately.
11Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming :- (a) ACB 800 AMP 4 pole 50 KA-01 No.(b) C/O Switch 1000 Amps 4P-01(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1200 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 set
12Outgoing ;- (a) MCCB 200 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-05 No.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables.(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover.(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately.
13Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming :- (a) C/O switch 400Amps 4 pole 50 KA-02 No.(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 set
14Outgoing ;- (a) MCCB 200 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-03 No.(b) (a) MCCB 100 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-02 No.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables.(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover.(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately.
15Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming :- (a) C/O switch 630Amps 4 pole 50 KA-02 No.(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 800 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 set
16Outgoing ;- (a) MCCB 400 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-05No.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables.(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover.(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately.
17Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming :- (a) C/O switch 400Amps 4 pole 50 KA-02 No.(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 800 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 set
18Outgoing ;- (a) MCCB 200 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-07 Nos.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables.(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover.(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately.
19Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming :- (a) MCCB 630Amps 4 pole 50 KA-01 No.(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 800 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 set
20Outgoing ;- (a) 3 outgoing 500 Amps Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising with corrosion resistance SMC insulators.Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.(iii) Outgoing MCCBs shall be fed with solid busbar connectors.(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables.(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover.(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately.
21Supply and fix in replacement on load change over switch 415 V, 4 pole, 250 A open execution as per existing make and model suitable equivalent make as per list of make at PScomplete all as specified and directed by Engr-in-Charge.
22Supply and fix in replacement on load changeover switch 415 V, 4 pole, 320A open execution as per existing make and model suitable equivalent make as per list of make at PScomplete all as specified and directed by Engr-in-Charge.
23Supply and fix in replacement on load changeover switch 415 V, 4 pole, 400A open execution as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
24Supply and fix in replacement on load changeover switch 415 V, 4 pole, 630A open execution as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
25Supply and fix in replacement MCCB, 415 volts, 4 pole 16 KA, 63A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
26Supply and fix in replacement MCCB, 415 volts, 4 pole 16 KA, 100 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
27Supply and fix in replacement MCCB, 415 volts, 4 pole 16 KA, 125A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
28Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 160A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
29Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 200A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
30Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 250A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
31Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 320A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
32Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 400A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
33Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 630A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
34Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 125A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
35Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 160A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
36Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 200A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
37Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 250A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engr-in-Charge.
38M&L for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed and making the disturbed surface after relaying the cable and making joints suitable for aluminium conductor of size 16 to 25 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.Note : Taking down the fault cable, excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this sch.
39All as per item no-31 above but 35 to 70 Sqmm 3.5 core
40All as per item no-31 above but 95 to 150 Sqmm 3.5 core
41All as per item no- 31 above but 185 to 240 Sqmm 3.5 core
42All as per item no- 31 above but 300 to 400 Sqmm 3.5 core
43M&L for disconnecting LT supply and taking out defective LT draw out EDO type ACB 440 V suitable for 800 Amps to 1250Amps and servicing by OEM .i.e Auth dealer cleaning the fixed and moving all parts, removing dust particles by using high speed blower applying grease/jelly to moving mechanism and moving parts, tightening nut bolts of all the components of ACB and complete testing and putting on full load all as specified and directed by Engr-in-Charge.
44S&F in replacement of isolating JAW contacts suitable for 800 Amps to 1250Amps LT draw out EDO type ACB complete all as specified and directed by Engr-in-Charge.
45S&F in replacement of polyester resin cast CT 800 / 5A suitable for 800 Amps to 1250Amps LT draw out EDO type ACB as per existing make and model complete all as specified and directed by Engr-in-Charge.
46S&F in replacement of ARC Chutes for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engr-in-Charge.
47S&F in replacement of Pole Unit for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engr-in-Charge.
48S&F in replacement of Draw out terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engr-in-Charge.
49S&F in replacement of Lower terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engr-in-Charge.
50S&F in replacement of Upper terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engr-in-Charge.
51S&F in replacement of Charging motor for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engr-in-Charge.
52S&F in replacement of shunt trip and closing coil for Air circuit brekers EDO type suitable for 800 Amps to 1250Ampscomplete all as specified and directed by Engr-in-Charge.
53S&F in replacement of manual Charging handle for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engr-in-Charge.
54S&F in replacement of under voltage trip device compact with UVT coil for Air circuit brekers EDO type suitable for 800Amp/ 630Amp as per existing make and model complete all as specified and directed by Engr-in-Charge.
55S&F in replacement of Safety shutter assembly for Air circuit brekers EDO type suitable for 800Amp/630Amp as per existing make and model complete all as specified and directed by Engr-in-Charge.
56S&F in replacement of Earth fault relay with NCT for Air circuit brekers EDO type suitable for 800/630 Amp as per existing make and model complete all as specified and directed by Engr-in-Charge.
57Supplying and laying in replacement of GI tubing medium grade for cable protection in trenches/duct/fixing to pole/wall or in such similar position of following size all as specified and directed by Engr-in-Charge. :-
58100 mm dia
5980 mm dia
6050 mm dia
6140 mm dia
62Taking up old unserviceable LT UG cables from trench/poles/wall etc of following size all as specified and directed by Engr-in-Charge. :-
6316 Sqmm 4 core
6425 Sqmm 3.5 core
6535 Sqmm 3.5 core
6670 Sqmm 3.5 core
6795 Sqmm 3.5 core
68120 Sqmm 3.5 core
69185 Sqmm 3.5 core
70240 Sqmm 3.5 core
71300 Sqmm 3.5 core
72400 Sqmm 3.5 core
73Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of following sizes all as specified and directed by Engr-in-Charge :-
7416 Sqmm 4 core
7525 Sqmm 3.5 core
7635 Sqmm 3.5 core
7770 Sqmm 3.5 core
7895 Sqmm 3.5 core
79120 Sqmm 3.5 core
80185 Sqmm 3.5 core
81240 Sqmm 3.5 core
82300 Sqmm 3.5 core
83400 Sqmm 3.5 core
84Excavation in soft / loose soil not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable all as specified and directed by Engr-in-Charge.
85Excavation in hard / dense soil Including road cutting etc not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable all as specified and directed by Engr-in-Charge.
86Returning filling using excavated soil including spreading leveling, watering and well ramming in layers n exc 25 cms all as specified and directed by Engr-in-Charge.
87Removal of surplus excavated material n.exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtrs above the starting point all as specified and directed by Engr-in-Charge.
88Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed by Engr-in-Charge.
89All as per item No-81 above but outer dia of 63 mm and inner dia 50 mm.
90All as per item No-81 above but outer dia of 77 mm and inner dia 63 mm.
91All as per item No-81 above but outer dia of 90 mm and inner dia 76 mm .
92All as per item No-81 above here in before but outer dia of 120 mm and inner dia 103.5 mm.
93Supply and installation of heat shrinkable/PVC cable sleeves with color-coded as per phase identification (Red, Yellow, Blue, Black, Green), suitable for LT Aluminium/aluminum cables of sizes ranging from 16 mm² to 300 mm², with thickness not less than 1.2 mm and temperature rating ≥ 90°C. The scope includes cutting, cleaning of cables, and proper application of sleeves with hot air gun or flame torch to ensure tight adhesion without air pockets. Work shall conform to IS: 7098/IS: 13592 and standard electrical practices all as specified and directed by Engr-in-Charge.
94M&L for aluminium thimble cable (Lugs) suitable for Cable of following sizes complete all as specified and directed by Engr-in-Charge.
95All as per item no-87 above but size 95 Sqmm to 120 Sqmm
96All as per item no-87 above but size 150 Sqmm to 240 Sqmm
97All as per item no-87 above but size 300 Sqmm to 400 Sqmm
98Repair/Maint LT Panel board / Feeder pillar boxes , removing the carbon deposited inside the panel, cleaning the panel with cotton waste, applying two coat of synthetic enamel paint , checking the faults inside the panel board complete all as specified and directed by Engr-in-Charge. Note : (a) Proper shut down shall be taken prior the commencement of work . (b) Fabrication of LT Panels for broken hinges shall be rectified. (c) LT Panel shall be painted with two coats of synthetic enamel paint over a coat of red oxide primer.(d) Marking on LT panels shall be done as per sources of power supply (1100 volts) and outgoing area by 10cm glow sign/paint all as directions of Engr-in-Charge.
99Note :- The Contractor are advised to visit the site before quoting the rate. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58294213
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 47 Lakhs
LAST DATE 20-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maint To Lt Network System At Ccosw, 9 R&O, 1 Ew And Other Locations Under Ge (U) Udh Ur.
Basic Detail
Tender No GE/U-126/2026-27
Bidding Type Tender
Location
City Reasi
State Jammu and Kashmir
Key Dates
Publish Date 30 Oct 2026
Submission Date 20 Nov 2026
Open Date 23 Nov 2026
Finance
Tender Value 47 Lakhs
Tender Fee 500
EMD 94000
Exemption Not Available
Document List
a8d6c4ac-1fc7-44f3-bdef-d653e2a9cdc2.html
BOQ_893362.xls
TENDER126.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 30, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 20, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 20 days
Nov 23, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 23 days

Tender Documents

Download All (ZIP) ↓
html

a8d6c4ac-1fc7-44f3-bdef-d653e2a9cdc2.html

xls

BOQ_893362.xls

pdf

TENDER126.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender