Tender For Repair And Replacement Of Tpn Dbs, Spn Dbs, Meter Box, Mccbs Mcbs And Submain Wiring And Other Connected Works At Various Location Under Age E&M-Iv Of Ge(S) Bathinda At Bathinda Mil Stn
Tender Value
49 Lakhs
Estimated cost
Bid Submission
20 Nov 2026
20 days left
EMD
98000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bathinda → Punjab
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair And Replacement Of Tpn Dbs, Spn Dbs, Meter Box, Mccbs Mcbs And Submain Wiring And Other Connected Works At Various Location Under Age E&M-Iv Of Ge(S) Bathinda At Bathinda Mil Stn
BOQ
| Sl. No. | Item Description |
| 1 | Taking down old complete and Material and labour sub main wiring with 2.50 Sq mm nominal cross sectional area, two single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 2.50 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into in existing surface/recessed PVC/steel conduit complete all as specified and directed. (Note :- 03 runs of 2.50 sqmm cable will be measured as one running length) |
| 2 | Taking down old complete and Material and labour sub main wiring with 04 Sq mm nominal cross sectional area, two single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 04 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into in existing surface/recessed PVC/steel conduit complete all as specified and directed. (Note :- 03 runs of 4.0 sqmm cable will be measured as one running length) |
| 3 | Taking down old complete and Material and labour sub main wiring with 06 Sq mm nominal cross sectional area, two single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 06 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into in existing surface/recessed PVC/steel conduit complete all as specified and directed. (Note :- 03 runs of 6.0 sqmm cable will be measured as one running length) |
| 4 | Taking down old complete and Material and labour sub main wiring with 04 Sq mm nominal cross sectional area, two single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 04 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 25 mm dia, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall and making good to the disturbed surfaces to matched and finised with existing surface are included in the ratecomplete all as specified and directed.Make of cable - Polycab/Havells/Grandlay cable Note:- (i) 2 run of 4.0 Sqmm main cable, one run of 4.0 Sqmm earth wire and one run length of PVC conduit of size 25mm shall be considered as one running length.(ii) The wiring shall be done in proper color coding using Red,Yellow, Blue for phases, Black for neutral and Green for earth. |
| 5 | Taking down old complete and Material and labour sub main wiring with 06 Sq mm nominal cross sectional area, two single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 06 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 25 mm dia, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall and making good to the disturbed surfaces to matched and finised with existing surface are included in the ratecomplete all as specified and directed.Make of cable - Polycab/Havells/Grandlay cable Note:- (i) 2 run of 6.0 Sqmm main cable, one run of 6.0 Sqmm earth wire and one run length of PVC conduit of size 25mm shall be considered as one running length.(ii) The wiring shall be done in proper color coding using Red,Yellow, Blue for phases, Black for neutral and Green for earth. |
| 6 | Taking down old complete and Material and labour Three phase sub main wiring with 10.0 Sq mm nominal cross sectional area, Four single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 06 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 25 mm dia, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall and making good to the disturbed surfaces to matched and finised with existing surface are included in the ratecomplete all as specified and directed.Make of cable - Polycab/Havells/Grandlay cable Note:- (i) 04 run of 10.0 Sqmm main cable, one run of 10.0 Sqmm earth wire and one run length of PVC conduit of size 25mm shall be considered as one running length.(ii) The wiring shall be done in proper color coding using Red,Yellow, Blue for phases, Black for neutral and Green for earth. |
| 7 | Taking down old complete and supply and fixing of sheet metal enclosure distribution board, double door, single pole and neutral, AC, 240 volt, 12 way, with 200 Amp rated copper bus bar and metal door with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. |
| 8 | Taking down old complete and supply and fixing of sheet metal enclosure distribution board, double door, single pole and neutral, AC, 240 volt, 08 way, with 200 Amp rated copper bus bar and metal door with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. |
| 9 | Taking down old complete and supply and fixing of sheet metal enclosure distribution board, double door, single pole and neutral, AC, 240 volt, 04 way, as TPN incommer only and metal door with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. |
| 10 | Taking down old complete and supply and fixing of sheet metal enclosure distribution board, double door, single pole and neutral, AC, 240 volt, 02 way, and metal door with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. |
| 11 | Supply and fixing in replacement of SPN enclosure with a two pin and earth plug and socket complete with and including MCB, SP, AC, 240 volt of 20 Amp, 'C' curve 10 KA breaking capacity and flush to wall including all cuttings & chases etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. |
| 12 | Supply and fixing in replacement (concealed flush to wall) factory made VTPN (Vertical type), 4 Way 415V, as per IEC 61439-3, DB (made out of CRCA sheet not less than 1.2mm thick, with copper bus bar rating 200 Amps, with two neutral bar, 2 earth bar and cable tie for cable management, and incl MCCB 125 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V,, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-54 protection class, including making good disturbed surfaces of walls as necessaty complete all as specified and directed..Note :- Only MCBs shall be measured and paid separately under appropriate item of BOQ. |
| 13 | Supply and fixing in replacement (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) TPN, 4 Way, 415V AC supply, As per IEC 61439-3, and provision for mounting Isolator/MCB/MCCB as incomer and for outgoing, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-54 protection class, including taking down unserviceable old DB any type including MCB etc and including making good disturbed surfaces of walls as necessaty complete all as specified and directed.Note :- MCBs shall be measured and paid separately under appropriate item of BOQ. |
| 14 | Taking down old complete and supply and fixing of SP MCB 6-32 Amp ,240Volt 10 KA ‘B’ series complete all as specified and directed. |
| 15 | Taking down old complete and supply and fixing of SPN MCB 40-63 Amp ,240Volt 10 KA ‘C’ series complete all as specified and directed. |
| 16 | Taking down old complete and supply and fixing of TPN MCB 100 Amp ,415 Volt 10 KA’ series complete all as specified and directed. |
| 17 | Taking down old complete and supply and fixing of TPN MCB 63 Amp ,415 Volt ‘C’ series complete all as specified and directed. |
| 18 | Taking down old complete and supply and fixing of MCCB 4 Pole, 125 Amps, 50 Hz, 25KA, 415 Volts,adjustable thermal and fixed magnetic type complete with powder coated SS enclosure MCCB box complete all necessary aluminium lugs and glands, etc complete all as spicified and directed. |
| 19 | Supply and fixing in replacement of SPN enclosure with a two pin and earth plug and socket complete with and including MCB, SP, AC, 240 volt of 20 Amp, 'C' curve 10 KA breaking capacity and flush to wall including all cuttings & chases etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. |
| 20 | Taking down old complete and M&L labour for earthing complete with galvanised mild steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level steel earth plate connected with GI wire 04 mm dia by means of lug, bolts, nuts, check nuts, washers of galvanised iron or steel GI protection pipe 15 mm bore light grade all as shown in elect plate No 3 on serial page No 497 of SSR part I - 2009 and connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150 mm thick around GI earth plate, GI pipe medium grade 20 mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover 40 mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 6 mm dia at the rate of 75 mm centre to centre both way with 12 mm dia lifting handle and pit / chamber in PCC 1:3:6 type C1, Angle iron 40 mm x 40 mm x 3 mm frame for pit cover including testing on completion complete all as specified and directed. Note : (i) Cost of GI earth strip and GI protection pipe upto 7.5 Mtr length shall be deemed to be included in the rate quoted for this item. |
| 21 | Isolate/de-energize the supply to the LT Panel Board/meter feeder panel of capacity ranging 125 Amps and voltage 415 Volts/230 Volts, opening the doors/covers of the cubicle enclosure for carrying out the servicing/maintenance/repairs of the Panel Board,modification and switch gear,MCCB, metering etc and re-fixing the same/New in place after repairs including testing and commissioning of the panel board comprising of the following:-a) Cleaning the inside switch gear chambers for removing dust, carbon and rusted surfaces including cleaning with blower b) Check the condition of the DMC/SMC support insulators including cleaning applying Dr beck red for better IR values and replacement of insulators/PVC copper cable size of 6.0 Sqmm if required. c) Tightening up of all bus bar connections, cable connections, replace bolt, nuts wherever required.(d) Repairs Panels /meters box doors with necessary hinged and welding work as per site requirement complete.(e) Re-painting alongwith preparation of old painted surface of panel by rust free, by scraping, cleaning, using wire brush, sand paper etc complete removal of old surface , After then Painting complete part of panel with two coat of synthetic enamel paint as per existing colour code over one coat of zinc chrome primer of approved make complete.Note :- MCB/MCCBs will be measured and paid separately and consumables items will be scope of the contractor |
| 22 | Supply and fixing in replacement of post top lantern LED type 25 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistance complete with driver and lamp complete all as specified and directed |
| 23 | Supplying, Laying ,and testing in of XLPE insulated armoured heavy duty electric cable of the size 10 Sqmm 2 core following size ,1100 Volts grade , with stranded aluminium conductor served with aninner sheathing of PVC tape armoured with GI wire and over all PVC sheathed in laid trenches/ passing through pipe/duct/road crossing/surface of wall/in hume pipe etc including fixing hardware,clamps,gland, thimble and making good the damaged surfaces etc complete all as specified and as directed. |
| 24 | Supplying, Laying ,and testing in of XLPE insulated armoured heavy duty electric cable of the size 16 Sqmm 2 core following size ,1100 Volts grade , with stranded aluminium conductor served with aninner sheathing of PVC tape armoured with GI wire and over all PVC sheathed in laid trenches/ passing through pipe/duct/road crossing/surface of wall/in hume pipe etc including fixing hardware,clamps,gland, thimble and making good the damaged surfaces etc complete all as specified and as directed. |
| 25 | Supplying, Laying ,and testing in of XLPE insulated armoured heavy duty electric cable of the size 25 Sqmm 4 core following size ,1100 Volts grade , with stranded aluminium conductor served with aninner sheathing of PVC tape armoured with GI wire and over all PVC sheathed in laid trenches/ passing through pipe/duct/road crossing/surface of wall/in hume pipe etc including fixing hardware,clamps,gland, thimble and making good the damaged surfaces etc complete all as specified and as directed. |
| 26 | Supply and laying double wall corrugated pipe (DWC) non metalic, Resistance to compression -type 450, resistance to impact -normal, resistance to bending - pliable , resistance to external influence- ingress protection IP67, resistance against corrosion - without protection, resistance to flame propagation-Non flame propagation, Nominal outside diameter 77 mm, minimum inside diameter 63mm confirming to IS 16205 (Part-24) -2017 for laying under ground cable including all connecetd accessories like socket, coupler, bends, tee etc complete all as specified and as directed. |
| 27 | Supply and laying double wall corrugated pipe (DWC) non metalic, Resistance to compression -type 450, resistance to impact -normal, resistance to bending - pliable , resistance to external influence- ingress protection IP67, resistance against corrosion - without protection, resistance to flame propagation-Non flame propagation, Nominal outside diameter 50mm, minimum inside diameter 37mm confirming to IS 16205 (Part-24) -2017 for laying under ground cable including all connecetd accessories like socket, coupler, bends, tee etc complete all as specified and as directed. |
| 28 | Excavation in trenches n exc 1.5m wide and n.exc 1.5 m in depth for laying of cable ,foundation etc. n exc 10 sqm on plan and nexc 1.5 m in depth and getting out in soft / loose soil all as specified and directed. |
| 29 | Returning,refilling in layers including spreading levelling, watering and well ramming in layers not exc 25 Cm ll as specified and directed. |
| 30 | Removal of surplus excavated soil not exc 50 mtrs and deposting where directed at level not exc 1.5 mtr above the starting point all as specified and directed. |
| 31 | Supply, installation, testing & commisioning of wall mounted indoor panel meter box protection class IP65, 415-433V made out of 2.0 mm thick RAL 7032/7035 coated CRCA steel, dust and vermin proof, single door complete prewired, with locking arrangements and hanging bracket suitable for hanging on wall with suitable arrangement as per site requirement complete including painting with powder coated paint over a coat of redoxide zinc crome primer complete incl necessary internal wiring with PVC insulated, unsheathed, FRLSH copper conductor cable size of 6.0 Sqmm for MCBs and electric meter and suitable opening for cable entry with suitable gland complete comprising of the following:-INCOMER :1 No. MCCB FP 100 A, 25 KA 415Volt,(Thermal Magnatic release)1 set of Phase indicating lamp for RYB1 No digital Ampere and volt meter 415 volts BUS BARS:150 A TPN bus bars of aluminium alloy with epoxy based insulation.OUT GOING:a) MCB SPN 63 Amp ,10 KA, C curve - 06 Nos.(for 06 Qtr)b) MCB SPN 16 Amp 10 KA, B curve -01 Nos . ( Comman Area)c) 07 x Nos Single Phase Digital Electronic Meter tamper proof LCD display , 230 Volt, 10-60 Amp , accuracy class -I, 50 Hz and conforming to IS 13779, IP-54 with parameters to show data ,time, current rating , load , PF, Voltage and KWH complete and provision of compartmental type for energy Meter with separate locking arragement , and front view with transparent acrylic sheet suitable for meter reading complete all as specified and direcetd. Note:-1. Taking down old TPN DB of any size. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 30, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 20, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysNov 23, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 23 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender