Tender For Special Repair To Lt Oh Line To Lt Ug Cable And Connected Works At Various Loc Of 80 Inf Bde And 201 Fd Wksp & Provn Of 16 X Geysers (25 Ltrs) At 80 Inf Bde C At Naushera Under Age E/M Of Ge 862 Ews
Tender Overview
Project Description
Tender for Special Repair To Lt Oh Line To Lt Ug Cable And Connected Works At Various Loc Of 80 Inf Bde And 201 Fd Wksp & Provn Of 16 X Geysers (25 Ltrs) At 80 Inf Bde C At Naushera Under Age E/M Of Ge 862 Ews
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 05-Nov-2026 | Corrigendum1 | BOQ | 20-Nov-2026 |
| 2 | 20-Nov-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 27-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling of overhead ACSR conductor of any size including removing of PG Clamps jumpering etc and kept in safe custody for reuse serviceable ACSR in the work & removing unserviceable conductor from site, complete all as specified and directed. |
| 2 | Supply, laying and testing of XLPE insulated cable, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core, complete all as specified and directed. |
| 3 | Supply, laying and testing of XLPE insulated cable, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core, complete all as specified and directed. |
| 4 | Supply, laying and testing of XLPE insulated cable, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core. (PH To Bus Bar box for street light and Main Panel to Cdr House Panel), complete all as specified and directed. |
| 5 | Supply, laying and testing of XLPE insulated cable, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core. (Panel No 2 to Dy Rsesi Bus Bar, Panel No 1 to Guest room Bus Bar), complete all as specified and directed. |
| 6 | Supply, laying and testing of XLPE insulated cable, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sq mm 4 core (Guard Room Panel 2 and Guard Room Cdr House), complete all as specified and directed. |
| 7 | Supply, laying and testing of XLPE insulated cable, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sq mm 2 core. (Guest Room-04 Nos), complete all as specified and directed. |
| 8 | Supply, laying and testing of XLPE insulated cable, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sq mm 4 core, complete all as specified and directed. |
| 9 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth not exceeding 10sqm for laying of cable and foundation of poles stays and getting out in soft / loose soil, complete all as specified and directed. |
| 10 | Returning filling in trenches including spreading leveling watering and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed. |
| 11 | Removing of excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified & directed. |
| 12 | M&L for providing cable protection for UG cable in trenches by using Riddled Earth including filling, spreading and punning down to desired thickness, complete all as specified and directed. |
| 13 | Supply and laying brick covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat, size 230mm x 115mm x 75mm, complete all as specified and directed. |
| 14 | Supply & Laying in GI tubing light grade of 80mm bore with necessary fittings as in cable protection in trenches/fixed on wall / floor including necessary clamps bolts and nuts, complete all as specified and directed. |
| 15 | Supply & Laying in GI tubing light grade of 40mm bore with necessary fittings as in cable protection in trenches/fixed on wall / floor including necessary clamps bolts and nuts, complete all as specified and directed. |
| 16 | Supply, installation, testing and commissinoning LT Feeder piller box outdoor type 1.0mx1.0mx0.6m suitable for working on 3 phase ,4 wire ,415 volts AC, 50Hz ,outdoor cubical type, and tested at CPRI, Outer shell shall be made out of 3mm thick CRCA sheet & MS angle iron frame duly powder coated of size 50 x 50 x 6mm frame, with front & back open, double door system lockable, inner shell shall be made out of 2.0 mm thick CRCA sheet and completely vermin & dust proof, entry holes for incoming & outgoing cables as approved by GE. Panel shall have bus bar chamber and switch gear compartment, hinged door with rubber gasket, earthing terminals, and consisting of following:- (Main LT Panel) |
| 17 | Incomer MCCB(a) MCCB 250 Amp,4 pole, 50 HZ,415 V having rupturing capacity 35 KA-01 Nos as incoming (thermal magnetic) release and adjustable on load.Outgoing MCCB(a) MCCB 200 Amp,4 pole, 50 HZ,415 V having rupturing capacity 35 KA-02 Nos as outgoing (thermal magnetic) release and adjustable on load.(b) MCCB 100 Amp,4 pole, 50 HZ,415 V having rupturing capacity 25 KA-01 Nos as outgoing (thermal magnetic) release and adjustable on load.(c) MCCB 4 pole 40 amps - 02 Nos.(d) Digital voltmeter (0-500) & Digital Ammeter (0-100) Amps with suitable CTs.(e) LED phase indication lamps RYB- 01 set.(f) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 volts grade and Cupper Bus Bar including Painting etc.(g) Copper bus bar ,TPN 400 Amp rating -04 NosNotes: (i) Rates are deemed to be inclusive of PCC platform of suitable size of 45 cm height and 04 Nos legs of angle iron 50 mm x 50 mm x 6mm & 60 cm height for fixing the panel.(ii) MCCB & MCB shall be fixed in suitable sheet metal enclosure made up of 3.15mm thick CRCA sheet. (iii) Danger notice plate (02) Nos LT size 20 cmx 15 cm shall be fixed on the panel. (iv) Panel shall be from CPRI approved make. (v) Make of panel and drawing shall be approved from GE before placing order for procurement. |
| 18 | Supply, installation, testing and commissinoning LT Feeder piller box outdoor type 1.0mx1.0mx0.6m suitable for working on 3 phase ,4 wire ,415 volts AC, 50Hz ,outdoor cubical type, and tested at CPRI, Outer shell shall be made out of 3.15mm thick CRCA sheet & MS angle iron frame duly powder coated of size 50 x 50 x 6mm frame, with front & back open, double door system lockable, inner shell shall be made out of 2.0 mm thick CRCA sheet and completely vermin & dust proof, entry holes for incoming & outgoing cables as approved by GE. Panel shall have bus bar chamber and switch gear compartment, hinged door with rubber gasket, earthing terminals, and consisting of following:- (Street Light Panel) |
| 19 | Incomer MCCB(a) MCCB 160 Amp,4 pole, 50 HZ,415 V having rupturing capacity 35 KA-01 Nos as incoming (thermal magnetic) release and adjustable on load.Outgoing MCCB(a) MCCB 100 Amp,4 pole, 50 HZ,415 V having rupturing capacity 25 KA-01 Nos as outgoing (thermal magnetic) release and adjustable on load.(b) MCCB 63 Amp,4 pole, 50 HZ,415 V having rupturing capacity 25 KA-04 Nos as outgoing (thermal magnetic) release and adjustable on load.(c) MCB SPN 40 Amps -05 Nos.(d) Digital voltmeter (0-500) & Digital Ammeter (0-100) Amps with suitable CTs.(e) LED phase indication lamps RYB-01 Set.(f) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 volts grade and Cupper Bus Bar including Painting etc.(g) Copper bus bar ,TPN 400 Amp rating -04 NosNotes: (i) Rates are deemed to be inclusive of PCC platform of suitable size of 45 cm height and 04 Nos legs of angle iron 50 mm x 50 mm x 6mm & 60 cm height for fixing the panel.(ii) MCCB & MCB shall be fixed in suitable sheet metal enclosure made up of 3.15mm thick CRCA sheet. (iii) Danger notice plate (02) Nos LT size 20 cmx 15 cm shall be fixed on the panel. (iv) Panel shall be from CPRI approved make. (v) Make of panel and drawing shall be approved from GE before placing order for procurement. |
| 20 | Supply, installation, testing and commissinoning LT Feeder piller box outdoor type 1.0mx1.0mx0.6m suitable for working on 3 phase ,4 wire ,415 volts AC, 50Hz ,outdoor cubical type, and tested at CPRI, Outer shell shall be made out of 3.15mm thick CRCA sheet & MS angle iron frame duly powder coated of size 50 x 50 x 6mm frame, with front & back open, double door system lockable, inner shell shall be made out of 2.0 mm thick CRCA sheet and completely vermin & dust proof, entry holes for incoming & outgoing cables as approved by GE. Panel shall have bus bar chamber and switch gear compartment, hinged door with rubber gasket, earthing terminals, and consisting of following:- |
| 21 | Incomer MCCB(a) MCCB 160 Amp,4 pole, 50 HZ,415 V having rupturing capacity 35 KA-01 Nos as incoming (thermal magnetic) release and adjustable on load.Outgoing MCCB(b) MCCB 100 Amp,4 pole, 50 HZ,415 V having rupturing capacity 25 KA-01 Nos as outgoing (thermal magnetic) release and adjustable on load.(c) MCCB 63 Amp,4 pole, 50 HZ,415 V having rupturing capacity 25 KA-04 Nos as outgoing (thermal magnetic) release and adjustable on load.(d ) MCB SPN 40 Amps -05 Nos.(e) Digital voltmeter (0-500) & Digital Ammeter (0-100) Amps with suitable CTs.(f) LED phase indication lamps RYB-01 set(g) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 volts grade and Cupper Bus Bar including Painting etc.(h) Copper bus bar ,TPN 400 Amp rating -04 NosNotes: (i) Rates are deemed to be inclusive of PCC platform of suitable size of 45 cm height and 04 Nos legs of angle iron 50 mm x 50 mm x 6mm & 60 cm height for fixing the panel.(ii) MCCB & MCB shall be fixed in suitable sheet metal enclosure made up of 3.15mm thick CRCA sheet. (iii) Danger notice plate (02) Nos LT size 20 cmx 15 cm shall be fixed on the panel. (iv) Panel shall be from CPRI approved make. (v) Make of panel and drawing shall be approved from GE before placing order for procurement. |
| 22 | Supply, installation, testing and commissinoning LT Feeder piller box outdoor type 1.0mx1.0mx0.6m suitable for working on 3 phase ,4 wire ,415 volts AC, 50Hz ,outdoor cubical type, and tested at CPRI, Outer shell shall be made out of 3.15mm thick CRCA sheet & MS angle iron frame duly powder coated of size 50 x 50 x 6mm frame, with front & back open, double door system lockable, inner shell shall be made out of 2.0 mm thick CRCA sheet and completely vermin & dust proof, entry holes for incoming & outgoing cables as approved by GE. Panel shall have bus bar chamber and switch gear compartment, hinged door with rubber gasket, earthing terminals, and consisting of following:-( Sand Model Room) |
| 23 | Incomer MCCB(a) MCCB 200 Amp,4 pole, 50 HZ,415 V having rupturing capacity 35 KA-01 Nos as incoming (thermal magnetic) release and adjustable on load.Outgoing MCCB(a) MCCB 100 Amp,4 pole, 50 HZ,415 V having rupturing capacity 25 KA-02 Nos as outgoing (thermal magnetic) release and adjustable on load.(b) MCCB 63 Amp,4 pole, 50 HZ,415 V having rupturing capacity 25 KA-02 Nos as outgoing (thermal magnetic) release and adjustable on load.(c) MCB SPN 40/ 63 Amps-2 Nos.(d) Digital voltmeter (0-500) & Digital Ammeter (0-100) Amps with suitable CTs.(e) LED phase indication lamps RYB-01 set(f) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 volts grade and Cupper Bus Bar including Painting etc.(g) Copper bus bar,TPN 400 Amp rating -04 NosNotes: (i) Rates are deemed to be inclusive of PCC platform of suitable size of 45 cm height and 04 Nos legs of angle iron 50 mm x 50 mm x 6mm & 60 cm height for fixing the panel.(ii) MCCB & MCB shall be fixed in suitable sheet metal enclosure made up of 3.15mm thick CRCA sheet. (iii) Danger notice plate (02) Nos LT size 20 cmx 15 cm shall be fixed on the panel. (iv) Panel shall be from CPRI approved make. (v) Make of panel and drawing shall be approved from GE before placing order for procurement. |
| 24 | Supply, install,testing and commissioning of factory made bus bar chamber panel of size 600mm x900mmx350mm(CPRI approved outdoor type 3.15 mm qith four strips 200 Amps bus bar aluminium with MCCB 100 Amp -02 nos ,FP 16 KA adjustable type duly connected to aluminium strip at incoming side with suitable space for 2 incoming cable and outgoing of cable 2 cable bus bar fixed on insulators in zig zag position,clearance in each strip and clearance in both side should not be less than 125mm with sufficient working space,height of bus bar chamber not less than 1 mtr, mounted on MS angle 50 x50x6mm made of CRCA sheet 3mm thickoutdoor type powder coated after seven tank process both side opening shutter in two parts,cable opening from bottom side with indicators RYB hinges through out the length of shutter with half turn locking arrangements including grounting in PCC, including taking down old bus bar chamber, complete all as specified and directed. |
| 25 | M&L for FRP junction box of size 30 x 25 x 15cm, four strip aluminium bus bar of capacity 63 Amps mounted on epoxy insulators weather proof, MCB SP 6 Amps -01 No including provision for fixing to electric poles with 02 Nos MS clamps of flat 40 x 6mm suitable size complete with nuts & bolts making connection with cable & including thimbles at suitable size, complete all as specified and directed. |
| 26 | M&L for earthing complete with steel earth plate eletrode 60cmx60cmx6mm thick buried dirctly in ground vertically (earth pit not less than 2.25 mtr below ground level) with top edge of plat not less than 1.5 mtr below ground level connected to GI earth strip 25x4mm by means of bolts. nuts,check nuts and washers etc including GI light grade protection pipe 40mm dia up to 7.5m length, provision the earth lead to earth connection in ther main distribution box with lugs and GI nuts, bolts, earthing shall be done all as per shown electrical plate No 3 of SSR part 1 Including neccessary excavation in soft disintergrated rock and provision of 20mm dia GI medium pipe for watering with funnel, PCC earth chamber of 40mm thick precast RCC cover with suitable precast RCC frame and earth test point and testing in presence of Engr -in -Charge, complete all as specified and directed. |
| 27 | S&F three core copper flexible cable for connection of security lights of 1.5 sq mm from junction box to security lights, complete all as specified and directed. |
| 28 | S&F storage water heater (geyser) 5 star rated as per BEE norms electrically operated suitable for 230 volts, 50 hz, AC supply system complete with glass coated insulated heating element tank of capacity 25 litre, complete with all accessories such as safety valve, thermostat, NRV,connecting hose-02 nos hot and cold water, complete all as specified & directed. |
| 29 | M&L for submain wiring with single core PVC insulated but unsheathed FRLS cable of size 2 Run of 4 sq mm cable and one Run of 4 sq mm earth continuity conductor of similar type cable multistranded copper conductor 1100 volts grade IS:694 marked drawn in and inluding 25mm dia PVC casing caping pipe , medium grade, ISI marked complete with all acessories and fittings all laid in ceiling or surface ,walls and also include the specified runs of cables, complete all as specified & directed.Note :- 2 Run of main cable, one run of earth continuity conductor & one run of PVC casing capping shall be measured as one Run. |
| 30 | M&L for Modular switch 1 way 16 amps 6 pin flush type, 1 module ,230 volts, complete all as specified & directed. |
| 31 | M & L for Modular socket 6A/16A -2/3 pin combined 2 module , 230 volts, complete all as specified & directed. |
| 32 | M&L for galvanized steel water tubing medium grade with all fittings such as elbow, unions, nipples, tees, bends, short pieces, connectors, back-nuts, caps, plugs, diminishing pieces and sockets etc as per site requirement of 15 mm dia GI pipe line, complete all as specified & directed. |
| 33 | S&F PVC connection 15 mm dia (heavy duty) with two nos of brass adaptor and washer of size 450 mm to 600 mm long for hot/cold water suitable for geyser, complete all as specified & directed. |
| 34 | Supply, installing and fixing of Angle valve, with iron wheel head, complete with suitable for 15 mm bore pipe, screwed both side ends for GI pipe or unions and fixed in size 15 mm dia, complete all as specified & directed. |
| 35 | S&F brass bib tap standard galvanised steel for iron pipe 15mm, complete all as specified & directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 5 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender