Tender For Special Repair / Replacement Of Vrf/Vrv Ac Plant Against Beyond Economical Repair At Kautilya (Dsp) Building Under Ge (I) R&D Rci, Hyderabad
Tender Overview
Project Description
Tender for Special Repair / Replacement Of Vrf/Vrv Ac Plant Against Beyond Economical Repair At Kautilya (Dsp) Building Under Ge (I) R&D Rci, Hyderabad
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 16-Nov-2026 | REVISED CRITICAL DATES | Date | 07-Dec-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | =B2& \\" BoQ\\" BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CHIEF ENGINEER (R&D) SECUNDERABAD Name of Work: SPECIAL REPAIR / REPLACEMENT OF VRF/VRV AC PLANT AGAINST BEYOND ECONOMICAL REPAIR AT KAUTILYA (DSP) BUILDING UNDER GE (I) R&D RCI, HYDERABAD Contract No: CERD/SEC/TOKEN/37 OF 2026-2027 Bidder Name : PRICE SCHEDULE( This BoQ template must not be modified / replaced by the bidder and the same should be uploaded after filling the relevant columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # SlNo. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency Rate in Figures to be entered by the Bidder Rs. Ps. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e. DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit, if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes Total Amount Total Amount in Words |
| 2 | Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead complete all as specified and directed. |
| 3 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25mm wide x 1.6mm thick with flanges of 27mm and 37mm, at 1200mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25 x 10 x 0.50mm of required length with nuts & bolts of required size and |
| 4 | other end of angle hanger fixed with intermediate G.I. channels 45 x 15 x 0.9mm running at the spacing of 1200mm centre to centre, to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26mm each having lips of 10.5mm, at 450mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64mm dia x 230mm long G.I. wire at every junction, including fixing perimeter channels 0.5mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall / partition with |
| 5 | the help of rawl plugs at 450mm centre, with 25mm long dry wall screws @ 230mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25mm at 230mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer’s specification and also including the cost of making openings for light fittings, |
| 6 | grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer-in-Charge including cost of painting with : 12.5mm thick tapered edge Glass Reinforced Gypsum (GRG) board conforming to IS: 2095-(Part 3):1996 (Boards with BIS certification marks). |
| 7 | Providing and fixing mineral fibre Silhouette false ceiling tiles at all heights of size 595 x 595mm of approved texture, design and pattern. The tiles should have Humidity esistance (RH) of 99%, Light Reflectance ≥ 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 Part - 6 & 7) in true horizont al level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33mm thick (galvanized @120 gsm) comprising of main T runners of 15 x 32mm of length 3000mm, cross T of size 15 x 32mm of length 1200mm and secondary intermediate cross T of |
| 8 | size 15 x 32mm of length 600mm to form grid module of size 600 x 600mm suspended from ceiling using galvanized mild steel item (galvanised @ 80gsm) 50mm long 8mm outer diameter M-6 dash fasteners, 6mm diameter fully threaded hanger rod up to 1000mm length and L-shape level adjuster of size 85 x 25 x 2mm, spaced at 1200mm centre to centre along main ‘T’. The system should rest on periphery walls / partitions with the help of GI perimeter wall angle of size 24 x 24 x 3000mm made of 0.40mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450mm centre to centre & 40mm |
| 9 | long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint for all heights. The work shall be carried out as per specifications, drawings and as per directions of the Engineer-in-Charge with 16mm thick beveled tegular mineral fibre false ceiling tile (NRC 0.55 to 0.60). |
| 10 | Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead complete all as specified and directed. |
| 11 | Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength in super structure above plinth level up to floor V level in : cement mortar 1:4 (1 cement : 4 coarse sand) complete all as specified and directed. |
| 12 | 15mm thick rendering in CM 1:4 on fair faces of brick work or concrete surfaces and finished the surface fair and even without using extra cement complete all as specified and directed. |
| 13 | 20mm thick rendering in CM 1:6 on fair faces of brick work or concrete surfaces and finished the surface fair and even without using extra cement complete all as specified and directed. |
| 14 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade new work (two or more coats) over and including water thinnable priming coat with cement primer complete all as specified and directed. |
| 15 | Finishing wall new work (two or more coats applied @ 1.43 litre / 10 Sqm over and including priming coat of exterior primer applied @ 0.90 litre / 10 Sqm with 100% premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489: 2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot tinted) with silicon additives complete all as specified and directed. |
| 16 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications : painting steel work with Deluxe Multi Surface Paint to give an even shade two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture complete all as specified and directed. |
| 17 | M&L for dismantling old VRF/VRV AC outdoor unit along with connected indoor units of any type including all connected items as in position and disconnecting the electric connections of the defective AC and transporting the same carefully to MES storeyard complete all as directed and specified by Engineer-in-Charge.Note: Hire charge for trailer, charges for loading / unloading and transportation are deemed to be included in quoted rate. |
| 18 | Supply, install, testing & comissioning of modular type Variable Refrigerant Flow / Variable Refrigerant Volume air cooled outdoor units of capacity 12 HP (12 x 30 = 360 HP suitable for cooling having 100% hermetically sealed inverter type twin rotary / scroll compressor(s), minimum two compressors (with individual seperate PCB) for below mentioned modules, microprocessor based controller, top discharge type condensing unit(s), with R-410-A refrigerant or equivalent, vibration isolators with |
| 19 | suitable foundation complete as required, to have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius. The unit shall be suitable to work on 400V + 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled |
| 20 | first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter |
| 21 | connections etc. as required (for capacity < 40 kWr ISEER 7.4, capacity > 40 and <70 ISEER 7.5, capacity > 70 ISEER 7.6 for Super ECSBC Building).Note: Initial charging of refrigerant gas for complete circuit is deemed to be included in quoted rate. |
| 22 | Supply, install, testing & comissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted mid high static ductable type / Cassette type indoor ceiling mounted unit equipped with washable synthetic media pre-filter, fan section with low noise fan / dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC |
| 23 | supply 230 V ± 10%, 50 Hz complete as required. The indoor units must shut down upon receiving a singal from the BMS System / Fire Signals. The system shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) High Static Ductable units (minimum 49 to 77 pascal external static pressure). for Cap of 1.6 HP. |
| 24 | All as per Sl item No. 13 above but of Cap 2 HP. |
| 25 | All as per Sl item No. 13 above but of Cap 2.6 HP. |
| 26 | All as per Sl item No. 13 above but of Cap 3.6 HP. |
| 27 | Supplying, installation, testing & commissioning of High Static Ductable units (minimum 78 pascal external static pressure) minimum capacity 6.6 TR VRF/VRV ceiling mounted high ductable type indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan / dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The indoor |
| 28 | units must shut down upon receiving a singal from the BMS System/Fire Signals. The cooling capacity of indoor unit will be at air inlet conditions of 27oC DB and 19oC WB temperature. (Make will be same as of Outdoor). |
| 29 | Supply, install, testing & comissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 30 | All as per Sl item No. 18 above but of size 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 31 | All as per Sl item No. 18 above but of size 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm hick insulation |
| 32 | All as per Sl item No. 18 above but of size 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 33 | All as per Sl item No. 18 above but of size15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 34 | All as per Sl item No. 18 above but of size 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 35 | All as per Sl item No. 18 above but of size 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 36 | All as per Sl item No. 18 above but of 25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 37 | All as per Sl item No. 18 above but of size 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
| 38 | All as per Sl item No. 18 above but of size 31.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation |
| 39 | All as per Sl item No. 18 above but of size 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation |
| 40 | All as per Sl item No. 18 above but of size 38.1 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation |
| 41 | All as per Sl item No. 18 above but of size 41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19mm thick insulation |
| 42 | S&F PVC insulated and PVC Round sheathed 3 core copper conductor flexible cable 1100 V grade 2.5 Sqmm |
| 43 | S&F PVC insulated and PVC Round sheathed 3 core copper conductor flexible cable 1100 V grade 4 Sqmm |
| 44 | M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint |
| 45 | Supplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation with IS : 655 and approved drawings and of Thickness 1.25 mmcomplete all as specifications by Engr-in-Charge. |
| 46 | Supplying and installingof size 150x50x1.6mm thick of perforated Hot Dipped Galvanised Iorn cable tray (Galvanisation thickness not less than 50 micron) withperforation not more than 17.5 % in convenient section, joined with connectors, suspended from the ceiling/fixed on wall with GI suspenders//Brackts including GI bolts & nuts, including necessary bends and T etc. as rquired |
| 47 | All as per Sl item No. 36 above but of size 300x50x1.6mm thick |
| 48 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 3½ core |
| 49 | Supply and fixing MCB TPN 63 Amp 415V 10KA 'B' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 15 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender