Tender For Construction Of Court Complex And Other Infrastructure Facilities At Churu (Hq) (Ac Work)
Tender Value
1.32 Crore
Estimated cost
Bid Submission
12 Nov 2026
0 days left
EMD
2.64 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Churu → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Of Court Complex And Other Infrastructure Facilities At Churu (Hq) (Ac Work)
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling & heating, having 100% hermetically sealed inverter type twin rotary/Scroll Compressor(s) with and minimum two compressors , above 14 HP modules, microprocessor based Controller, Side / top discharge type condensing unit(s), with R-410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The EER/COP (W/W) at 100% load with AHRI conditions shall not be less than 3.8 etc. complete as required. |
| 2 | 14 HP to 26 HP |
| 3 | Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down valve in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor). |
| 4 | 2.0 TR (Cooling Capacity 7100 Watt) |
| 5 | 2.4 TR (Cooling Capacity 8700 Watt) |
| 6 | 3.0 TR (Cooling Capacity 11200 Watt) |
| 7 | 4.0 TR (Cooling Capacity 14000 Watt) |
| 8 | Supply, installation, testing and commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with and comfort washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50 Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down valve in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) |
| 9 | 1.3 TR (Cooling capacity 4500 watt) |
| 10 | 1.6 TR (Cooling capacity 5600 watt) |
| 11 | 2.0 TR (Cooling capacity 7000 watt) |
| 12 | Supply, installation, testing & commissioning of Group controller for monitoring the status and working condition of all indoor and outdoor units, The controller shall act as an advanced air conditioning management system to given complete control of VRV/VRF air conditioning equipment with Starting/stopping of air-conditioning as a zone or group of individual units. Temperature setting for each Indoor units of zone, Switching between temperature control modes, switching of the fan speed and direction of airflow, enabling/disabling of individual remote controller operation, Alarm code display in case of any problem. It shall be able to control up to 64 number of Indoor units. |
| 13 | Add Extra for extenders/adaptors compatible with central controller to enable the controller to work with 128 IDU's |
| 14 | Supplying and installation of high-pressure grade required size OEM make copper connection Y or T Joints / refnet for liquid and suction line , complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system complete as required. |
| 15 | Gas charging of VRF/VRV system with R410A refrigerant gas. Before gas charging system shall be flushed with high purity Nitrogen Gas to remove carbon content, dirt particles to make sure that there is no chance of mixing any impurity with Refrigerant Gas. Thereafter System shall be tested with Nitrogen Gas at 1.5 Times of working pressure of R410 Refrigerant Gas to ensure leakproof system. Whole system shall be Vacuumed up to 500-micron level which ensures the zero-moisture content level in piping to ensure better cooling efficiency and long life of the system. |
| 16 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM must ensure that the cable is tested for complaince, either through their in house laboratory accrediated by NABL or by any Govt. laboratory accrediated by NABL and the laboratory's scope of accrediation should cover the requirements and testing procedure as per IS:10810. |
| 17 | Armoured |
| 18 | 2 core x 1.5 Sq.mm |
| 19 | 4 core x 2.5 Sq.mm |
| 20 | Supply, installation, testing and commissioning of interconnecting copper refrigerant piping of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 with 7 mil Glass Cloth and 3 coats of anti UV paint (on area which is exposed to weather) including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. |
| 21 | 41.1 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 22 | 38 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 23 | 34.9 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 24 | 28.6 mm O.D., wall thinkness ≥ 1.2mm (insulation – 19 mm thick) |
| 25 | 25 mm O.D., wall thinkness ≥ 1.2mm (insulation – 19 mm thick) |
| 26 | 22.2 mm O.D., wall thinkness ≥ 1.0mm (insulation – 19 mm thick) |
| 27 | 19.1 mm O.D., wall thinkness ≥ 1.0mm (insulation – 13 mm thick) |
| 28 | 15.9 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 29 | 12.7 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 30 | 9.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 31 | 6.4 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 32 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. |
| 33 | 20 mm |
| 34 | 25 mm |
| 35 | 40 mm |
| 36 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 37 | 50 mm dia per running inch length |
| 38 | 100 mm dia per running inch length |
| 39 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. . |
| 40 | Add 18% GST Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 29, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 12, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
TodayNov 13, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 1 dayTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender