Tender For Supply, Installation, Testing And Commissioning Of Fire Fighting System At Canteen Block Gcet, Chak Bhalwal Jammu.
Tender Value
5.57 Lakhs
Estimated cost
Bid Submission
07 Nov 2026
8 days left
EMD
11200
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jammu → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Supply, Installation, Testing And Commissioning Of Fire Fighting System At Canteen Block Gcet, Chak Bhalwal Jammu.
BOQ
| Sl. No. | Item Description |
| 1 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required: (DSR-27.7) 40 mm dia. |
| 2 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required: (DSR-27.7) 25 mm dia. |
| 3 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585. 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipment on wall. Connections from riser with 25 mm dia stop SS/Gun metal metal valve & M.S. Pipe and socket. 30 m (DSR-27.17.1) |
| 4 | Providing and fixing gunmetal/SS single acting air release valve with screwed inlet 25 mm dia. (MR) |
| 5 | Dial type pressure gauge with isolation cock and copper pipe at hydrant station. Dial diameter 100 mm calibration 0-15 kg/ sq.cm (MR) |
| 6 | 25 mm dia ball valve (MR) |
| 7 | Providing and fitting of 1 hp pressure pump to be installed at the roof with allied connections with water tank and outlet to be connected with MS pipe. Complete job include all allied electrical and plumbing accessories required for the job. |
| 8 | Providing and fitting of Polyethylene water storage tank of 1000 ltr capacity each ISI: 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet and outlet pipes including overflow pipes with fittings and foundation including all allied connections etc. Complete job includes cost of labour, material, transportation and other taxes. (MR) |
| 9 | Supplying & lying of 1.5 sqmm or of suitable capacity PVC insulated copper conductor armored cable with proper conduiting/clamping from the source as per the site condition. (MR) |
| 10 | Providing and fixing ABC powder type fire extinguishers 6kg (IS: 15683:2018) consisting of welded M.S. cylindrical body ABC powder type extinguisher finished externally with red enamel paint and fixed to ceiling with brackets complete with internal charge. (MR) |
| 11 | Providing & fixing CO2 type fire extinguishers 6kg cap. (IS: 15683:2018) Complete with wheel valve arrangement, high-pressure wire Braided hose pipe as req. (MR) |
| 12 | Providing and fixing ABC powder type fire extinguishers 5 Kg capacity (IS: 15683:2018) consisting of welded M.S. cylindrical body automatic modular ABC powder type extinguisher actuated through a sprinkler head mounted on The extinguisher body finished externally with red enamel paint and fixed to ceiling with brackets complete with internal charge. (MR) |
| 13 | Supply of manual call point 02 nos. & necessary fixing arrangements with key complete as required. MCP should have IP52 or better protection rating Shall be EN54 -Vds/UL-FM Certification. Job also includes Supplying, laying, testing and commissioning of Low Smoke Zero Halogen Silicon Insulated Fire Survival Cable of suitable size along with supply of Addressable Sounder 02 nos. with sound pressure 90 dB(A), Sounder should have IP40 or better protection rating. Shall be EN54 -Vds/UL-FM Certification. (MR) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 28, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 07, 2026
17:00 IST