Tender For Repairs/Maint/Replacement Of Water Pumping Line, Sluice Valve, Non Return Valve, Water Level Indicator , Star Delta Starter And Certain Other Connected Works Under Ge Chennai
Tender Overview
Project Description
Tender for Repairs/Maint/Replacement Of Water Pumping Line, Sluice Valve, Non Return Valve, Water Level Indicator , Star Delta Starter And Certain Other Connected Works Under Ge Chennai
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 11-Nov-2026 | other_corrigendum | Other | 17-Nov-2026 |
| 2 | 17-Nov-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 24-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches n exc 1.5 mtr wide and n exc 1.5m in depth for laying of water supply pipe line etc n exc 10 Sqm on plan and getting out soft/loose soil.Note : -Excavation to be done through manual only due to site condition. |
| 2 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil. |
| 3 | Removing excavated material n exc 50 m and depositing where directed at a level n exc 1.5 m above the starting point |
| 4 | Finding of any type of water leakage of CI/DI/GI pipe line upto 100 mm dia and Repair leakage of water line in trench including replacement any type of CI/DI fitting and welding work at site and stopping leakage.Note- (i) Rates including excavation , welding work returning filling.(ii) CI/DI Fittings measured and paid seperately under relevent items. |
| 5 | Finding of any type of water leakage of CI/DI/GI pipe line upto 200 mm dia and Repair leakage of water line in trench including replacement any type of CI/DI fitting, lead joint as per site requirement and welding work at site and stopping leakage.Note- (i) Rates including excavation & returning filling,welding returning filling.(ii) CI/DI Fittings measured and paid seperately under relevant items. |
| 6 | Taking out old unserviceable sluice valve and supply, install, connecting and testing of sluice valve of size 80 mm dia bore, class PN- 1.6 double flanged with CI body, wheel and brass spindle and nuts etc., IS- 14846 marked including jointing materials i.e. rubber gaskets, nuts, bolts etc. including taking down old unserviceable sluice valve complete all as specified and directed by Engr-in-Charge |
| 7 | All as per item No. 6 above here-in-before but of size 100 mm dia bore. |
| 8 | All as per item No. 6 above here-in-before but of size 150 mm dia bore. |
| 9 | Taking out old unserviceable butterfly valve and supply, install connecting and testing of butterfly valve , heavy duty with CI body,liver operated, suitable length of liver, ISI marked including jointing materials i.e rubber gaskets, nuts bolts etc complete all as specified and directed of size 80 mm dia bore. |
| 10 | All as per item No. 9 above here-in-before but of size 100 dia mm bore. |
| 11 | Supply & fixing of Cast Iron NRV ISI Marked with necessary rubber packing, nuts bolts etc of size 150 mm dia bore including taking down old unserviceable NRV complete all as specified and directed. |
| 12 | All as per item No. 11 above here-in-before but of size 100 dia mm bore. |
| 13 | Supply and fixing CI ball type foot valve flanged end with necessary rubber packing nuts, bolts and washers of size 100 mm dia bore including taking down. complete all as specified ISI marked and directed by Engr-in-charge. |
| 14 | All as per item No. 13 above here-in-before but of size 150 dia mm bore. |
| 15 | M&L for DI fittings spigot socketed and flanged pipe such as bends (any type, radius and angle), tee pieces, 'Y' junction, cross collars, caps and plugs of any type or radius upto 300mm bore pipe. |
| 16 | Supply, laying , jointing and testing 25 mm bore galvanised steel water tubing medium grade including provision of all pipe fittings such as bends, tees, elbows, reducers, unions, plugs, sockets etc. laid in trenches, fixed to walls or laid in floors etc. complete all as specified and directed. |
| 17 | All as per item No. 16.00 above but 40mm bore tubing |
| 18 | All as per item No. 16.00 above but 50mm bore tubing |
| 19 | All as per item No. 16.00 above but 80mm bore tubing |
| 20 | All as per item No. 16 00 above but 100mm bore tubing |
| 21 | Supply and fixing in replacement of fully automatic star delta starter 3 phase 440 volts 50 HZ with over load relay range 17-25 A, contactors size 32 complete with all connections for capacity 25 HP complete all as directed.(Make: L&T / Seimens / Havells |
| 22 | Supply and fixing in replacement of automatic star delta starter 3 phase 440 volts 50 HZ with over load relay range 34-5-A, contactors size 50 complete with all connections for capacity 50 HP complete all as directed.(Make: L&T / Seimens / Havells |
| 23 | Supply and fixing in replacement of electric water level indicator electric operated with indications of level of water in over UG sump at a pump house bldg received from under ground sump complete with comprising of following. (a) Automatic multi level digital indicator of heavy duty board on principle of conductivity - 01 Nos.(b) PVC insulated copper conductor cable 0.5 sqmm 10 pair with 08 SWG GI wire and insulating hanger etc(approx 50 RM) exisitng electrical panel to water level indicator in 19/20 mm dia black rigid steel conduit fixed on under ground sump etc - 01 job |
| 24 | S & F PVC insulated multi stranded single core cable with copper conductor 1100 Volts grade conforming to IS: 694 / 1990 for 35 sqmm including taking down all as specified and directed.Make : Richa/Havells/RR Kabel. |
| 25 | S & F PVC insulated multi stranded single core cable with copper conductor 1100 Volts grade conforming to IS: 694 / 1990 for 25 sqmm including taking down all as specified and directed.Make : Richa/Havells/RR Kabel. |
| 26 | Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 25×4mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including taking down including testing on completion |
| 27 | S&F and replacement of TPN MCCB 160 Amp , 415 v, 50 Hz AC suitable for 36 KA breaking capacity complete conforming to IS 8828 of 1996 all as specified. |
| 28 | S&F and replacement of 4 pole MCCB 200 Amp , 415 v, 50 Hz AC suitable for 36 KA breaking capacity complete conforming to IS 8828 of 1996 all as specified. |
| 29 | S&F and replacement of 4 pole MCCB 250 Amp , 415 v, 50 Hz AC suitable for 36 KA breaking capacity complete conforming to IS 8828 of 1996 all as specified. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 4 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender