Tender For Engineering, Procurement And Construction Of 0.72 Mg Capacity Under Ground Reservoir And Booster Pumping Station Including Civil Works, E&M Works Along With Peripheral Mains & Feeder Line At G.T. Road Shahadra, (Tyr).
Tender Overview
Project Description
Tender for Engineering, Procurement And Construction Of 0.72 Mg Capacity Under Ground Reservoir And Booster Pumping Station Including Civil Works, E&M Works Along With Peripheral Mains & Feeder Line At G.T. Road Shahadra, (Tyr).
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 13-Nov-2026 | Corrigendum No.02 | Date | 27-Nov-2026 |
| 2 | 13-Nov-2026 | Corrigendum No.01 | Other | 27-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | MECHANICAL |
| 2 | Manufacture, inspection, Supply, installation, testing and commissioning of manually operated Sluice Gates of 1000 mm x 1000mm as per IS: 13349-1992 (Class II) and technical specifications & requirements. |
| 3 | Manufacture, inspection, supply, installation, testing and commissioning of Horizontal split casing type pumps (870 cu. m/hr @ 40 mwc) with motor and accessories such as coupling, coupling guard, base plate, foundation bolts, etc. |
| 4 | Manufacture, inspection, Supply, installation, testing and commissioning of motorized / manual DI sluice valves as per IS 14846 and technical specifications and requirement. |
| 5 | a) 400mm dia meter - 10 bar |
| 6 | b) 500mm dia meter - 10 bar |
| 7 | c) 600mm dia meter - 10 bar |
| 8 | Supply, installation, testing and commissioning of swing type DI check valves as per technical specifications and IS 5312 |
| 9 | a) 400mm diameter - 10 bar |
| 10 | b) 600mm diameter - 10 bar |
| 11 | Supply, installation, testing and commissioning of CI pipe D/F pipes and specials complete with fittings, gasket, SS- 304 bolts and nuts etc. of 500 mm dia pipe for suction side of pumps up to header line, as per layout plan, technical specification and requirements |
| 12 | 500mm dia bell mouth |
| 13 | 500mm dia DF pipe 750mm long |
| 14 | 500mm dia 90\\"bend |
| 15 | 500 mm dia DF puddle pipe 1250 mm long (600/650) |
| 16 | 500-300 mm dia DF ecentric taper |
| 17 | 500mm dia Dismantling joints 300 mm long |
| 18 | Rubber gaskets |
| 19 | Gl nuts bolts and washers M 24/110 |
| 20 | Supply, installation, testing and commissioning of 400 mm and 600 mm dia CI pipe for delivery main complete with AF Radial Tees, taper, bends, duct foot bend, dismantling joints, puddle pipe, pipe fittings with gaskets, GI bolts and nuts etc. as per layout plan, technical specification and requirements. |
| 21 | 400 - 250 mm dia DF concentric taper |
| 22 | 400mm dia Dismantling joints 300 mm long |
| 23 | 400 mm dia DF pipe 300 mm long |
| 24 | 600 -600- 400 mm dia DF radial TEE |
| 25 | 600 mm dia DF pipe 2000 mm long |
| 26 | 600 mm dia DF puddle pipe 2000 mm long |
| 27 | 600 mm dia DF pipe 1500 mm long |
| 28 | 600 mm dia DF pipe 1255 mm long |
| 29 | 600 mm dia DF 660 mm long |
| 30 | 600 mm dia DF 1400 mm long |
| 31 | 600 mm dia SF 2000 mm long |
| 32 | 600 mm dia DF duct foot bend |
| 33 | 600 mm dia DF 90\\"bend |
| 34 | Rubber Gaskets |
| 35 | 400 mm |
| 36 | 600 mm |
| 37 | Gl nuts bolts and washers |
| 38 | FOR 400 mm M 24/100 |
| 39 | FOR 400 mm M 27/100 |
| 40 | Supply, installation, testing and commissioning of Air valve, 150 mm as per technical specifications. |
| 41 | Supply, installation. testing and commissioning of double girder 3.0 tonne electrically operated travelling crane with span of 7 mts, 40mm square bar and shrouded bus bar type OSL (Cu Conductor) along with all accessories as per lS: 807 / lS: 3177 and technical specification & requirements. |
| 42 | Supply of double girder 3 0 tonne electrically operated travelting crane with span of 7 mts including square bar and DSL |
| 43 | Supply, of Submersible dewatering pump sets 25 cu/m hr. @ 15 mlc along with motors quick action coupling to couple pumps. control panel with 25 meters of cable and 50 meters of 80 mm dia heavy duty hose pape and 10 mts of chain complete as per technical specifications & requirements. |
| 44 | i) Supply, of Submersible dewatering pump sets 25 cu/m hr. @ 15 mlc along with motors quick action coupling to couple pumps, control panel with 25 meters of cable and 50 meters of 80 mm dia heavy duty hose pipe and 10 mts of chain |
| 45 | ii) 80 mm dia hose pipe |
| 46 | Supply, installation and commissioning of drain pump set 5 cu/m hr. @ 15 mlc along with motors and quick action coupling to couple pumps, control panel, 20 meters of weather proof cable with 50 MM dia medium duty GI pipe & pipe fittings and brass control valves complete as per technical specifications. |
| 47 | i)Supply, of Drain Pumps. 5 cum/hr, 15 mwc i/c motor, coupling, cable and control panel |
| 48 | ii) 32 mm dia NRV |
| 49 | iii) 32 mm brass control valves |
| 50 | iv) 32 mm dia GI pipe and fitting |
| 51 | Supply, installation, fabrication & comm. of structure steel members in section, trusses framed work i/c cutting, welding, grinding, drilling etc and applying a priming coat of approved steel primer and there after painting with Deluxe Multi Surface Paint to give an even shade two or more coats applied @0.90 lt / 10 sq m over and under coat of primer applied @ 0.75 lit / 10 sq m of applied brand or manufacture. |
| 52 | Supply, installation, fabrication & comm. of structure steel members in section, trusses framed work i/c cutting, welding, grinding, drilling etc and applying a priming coat of approved steel primer |
| 53 | Supply and providing paint for fabricated structure steel with Deluxe Multi Surface Paint to give an even shade two or more coats applied @0.90 lt / 10 sq m over and under coat of primer applied @ 0.75 lit / 10 sq m of applied brand or manufacture. |
| 54 | Supply, installation of MS chequred plate of 8 mm thickness at Cable Trenches including supports and handles for proper handling and applying epoxy painting etc |
| 55 | Supply, storage testing of the safety equipment’s and handing over to DJB after commissioning of the plant |
| 56 | a) Fire Extiquishers |
| 57 | Supply and installation of Portable fire extinguishers (CO2 – 4.5 kg) as per as per IS 15683, with high pressure seamless cylinder IS 7285, duly approved by Chief controller of Explosive. |
| 58 | Supply and installation of 9 litre foam Fire Extinguisher as per as per IS 15683, |
| 59 | Fire bucket Stand with four nos. of Sand Buckets |
| 60 | 25 mm thick Rubber Mats of 2m x 1 m for Electrical Equipment |
| 61 | Shock Treatment chart |
| 62 | First Aid Box. |
| 63 | ELECTRICAL |
| 64 | Supply, installation, testrng and commissioning of CSS 11/0.433 kV, 500 kVA, Oil type, Transformer outdoor type on platform HT and LT switchgear including all necessary accessories and hardwares, as per technical specification and Single Line Diagram all complete set, type tested in line with latest IEC standards |
| 65 | Supply, installation, testing and commissioning of 132 kw VFD STARTER: - starter panel to be installed separately on the platform with the necessary isolators, MCCB and control accessories to be taken separately on the respective cubicles. as per technical specification and requirement all complete works. |
| 66 | [3 working) |
| 67 | supply of spare |
| 68 | Supply, installation, testing and commissioning of Actuator Panel with protection as per technical specification and as per Single Line Diagram all complete works. (Scope includes steel supports for installation of PP, anchor fasteners, if necessary and associated civil works) |
| 69 | Supply, installation, testing and commissioning of Auxiliary Panel with protection as per technical specification and as per Single Line Diagram all complete works. (Scope includes steel supports for installation of PP, anchor fasteners, if necessary and associated civil works) |
| 70 | Supply, installation, testing and commissioning of 415V, 160 KVAR capacitor bank with APFC Panel including all necessary indications, metering and protection as per technical specification; all complete works. (Scope includes steel supports for installation of switchboard, danger board and associated civil works) |
| 71 | Supply, installation, testing and commissioning of 415V, 30 kVAR Static capacitor bank including all necessary indications, metering and protection as per technical specification; all complete works. (Scope includes steel supports for installation of switchboard, danger board and associated civil works) |
| 72 | Supply, installation, testing and commissioning of 1.5-ton split air conditioner in Control room as per technical specifications. |
| 73 | Supply, Laying with heat shrinkable indoor cable termination kits i/c glands, lugs & necessary steel support and commissioning of 11KV(UE) grade, 3C x 240 sq. mm aluminium conductor, screened, XLPE, armoured (A2XCEFY) cable in trench, cable trays as per requirement of technical specifications and site requirements |
| 74 | Supply of 11KV(UE) grade, 3C x 240 sq mm. aluminium conductor, screened, XLPE, armoured (A2XCEFY) cable in trench, cable trays; all complete works |
| 75 | Laying of XLPE Power cable of grade 1 1 kv not exceeding 240 sq. mm in open channel/ ladder |
| 76 | Supply. installation, testing & commissioning of heat shrinkable andoor cable termination kits i/c glands, lugs & necessary steel support as required for 1 1KV (UE) grade, 3C X 240 sq. mm al conductor XLPE armoured cable |
| 77 | Supply. installation, testing and commissioning of 1.1 kV grade aluminium conductor stranded, extruded, XLPE insulated, PVC sheathed, armoured power cables (AYFY/AYVVY) including fixing of Gl spacer/ clamps/ cleates/ nylon ties, tags etc with Supplying and making end termination with brass compression gland and aluminium lug of the following sizes as per SLD and requirement to complete all works |
| 78 | a ) supply of cables |
| 79 | 3.5C x 300 Sqmm |
| 80 | 3.5C x 185 Sqmm |
| 81 | 3.5C x 150 Sqmm |
| 82 | 3.5C x 120 Sqmm |
| 83 | 3.5C x 50 Sqmm |
| 84 | 4C x 16 Sqmm |
| 85 | 3C x 6 Sqmm (cu) |
| 86 | 4C x 1.5 Sqmm (cu) |
| 87 | 2C x 4 Sqmm (cu) |
| 88 | b) Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing lN EXPOSED CABLE TRAY/RCC/ HUME/ METAL pipe as required |
| 89 | i) Above 185 sq. mm and upto 400 sq. mm |
| 90 | ii) Above 95 sq. mm and upto 185 sq. mm |
| 91 | iii) Above 35 sq. mm and upto 95 sq. mm |
| 92 | iv) Upto 35 sq. mm |
| 93 | c) Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1 .1 kV grade as required |
| 94 | 3.5C x 300 Sqmm |
| 95 | 3.5C x 185 Sqmm |
| 96 | 3.5C x 150 Sqmm |
| 97 | 3.5C x 120 Sqmm |
| 98 | 3.5C x 50 Sqmm |
| 99 | 4C x 16 Sqmm |
| 100 | Supply, installation testing and commissioning of 1 1kV grade, tinned copper conductor, stranded, extruded PVC sheathed, armoured control cables (YWY) including Supply and fixing tinned copper lugs duly crimped with crimping tool including making cable ends ready for crimping and providing insulation tape with colour code etc fixing of Glspacer/ clamp/ cleates/ nylon ties, tags, etc. of the following sizes; all complete works |
| 101 | a) Supply of cables |
| 102 | i) 2C X 2.5 sq mm |
| 103 | ii) 12C X 2.5 sq mm |
| 104 | iii) 4C X 1.5 sq mm |
| 105 | b) Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade upto 35 sq mm in the existing CABLE TRAY/RCC/ HUME/ METAL pipe as required |
| 106 | INTERNAL LIGHTING |
| 107 | Supply, installation, testing & commissioning of following types of lighting fixtures/ luminaries (including lamps) with reflector and complete accessories like energy efficient low loss choke/ ballast, starter, igniter & terminal block duly pre-wired with copper conductor including all accessories e.g. control gear boxes, junction boxes, terminal blocks, wires, GI conduits, necessary cable glands & lugs for terminations, etc. for complete connections as required all complete works as per requirement |
| 108 | a) Supply, Installation, testing and commissioning of pre-wired, of 40 W LED industrial luminair complete with all accessories and tube/lamp etc directly on ceiling/ wall, including connections along with 1.5 meter long hang out suppoting pipes from the roof. BAJAJ |
| 109 | b) Supply, lnstallation, testing and commissioning of 1 x 1-LED, 24 W Decorative lumarnaire / (Surface / wall mounted) with square paralite white powdered coated CRCA housing seamless front frame with flat white transmission acryiic cover descent light complete with all accessories including connections etc. as required BAJAJ |
| 110 | c) Supply, Installation, testing and commissioning of 1 x 120 W LED Medium/Highway integral HID suspended luminaire and accessories to be fitted under ceiling of dry pump house complete with all accessories including connections etc. as required. |
| 111 | d) Supply, Installation, testing and commissioning of Single piece, cast aluminum housing with full glass integral luminaires (IP 66) with 45 W LED and 50 mm dia. G I pipe medium duty for support and fixing steel support complete with all accessories including connections etc. as required. BAJAJ |
| 112 | e) 1200 mm dia ceiling fans summer ornamental in white colour |
| 113 | f) Supply, installation and commissioning of Exhaust fans (375 mm dia.), and technical specifications. ORIENTAL |
| 114 | Supply, installation, testing and commissioning of Start-Stop Push Button stations including all necessary accessories e.g. anchor fastener, steel supporting stand for fixing PB station, hard wares, associated civil works etc. as per technical specifications and drawings; all complete works. |
| 115 | Supply, installation, testing and commissioning of 415V, TPN-E, 30 amps, Industrial, heavy duty Welding Receptacles (WR) including all necessary accessories e.g. anchor fastener & steel supports for fixing WR, hardware’s, associated civil works etc. i/c cabling of 4cx 6 sq mm armoured cable complete as per technical specifications and drawings; all complete works. |
| 116 | i) Supply, instaltation, testing and conmissioning of 415V, TPN-E, 30 amps, lndustrial, heavy duty Welding Receptacies (WR) |
| 117 | ii) supply of 4c x 6 sq mm copper armoured cable |
| 118 | iii) Laying of one number PVC insulated and PVC sheathed / XLPE power cable upto 35 sq mm of 1.1 kV grade of following sze in the existing RCC / HUME / METAL pipe as required |
| 119 | Supply, installation, testing and commissioning of 415V, TPN-E, metal clad industrial plug & socket (suitable for 5 kW motor feeder) including all necessary accessories e.g. anchor fastener & steel supports for fixing plug & socket, hardware’s, associated civil works etc. i/c cabling of 4cx 6 sq mm armoured cable complete as per technical specifications and drawings; all complete works. |
| 120 | i) Supply, instaltation, testing and conmissioning of 415V, TPN-E, 30 amps, lndustrial, plug & socket (suitable for 5 kW motor feeder) |
| 121 | ii) supply of 4c x 6 sq mm copper armoured cable |
| 122 | iii) Laying of one number PVC insulated and PVC sheathed / XLPE power cable upto 35 sq mm of 1.1 kV grade of following sze in the existing RCC / HUME / METAL pipe as required |
| 123 | Supply, installation, testing and commissioning of 100AH, 30V Sealed Maintenance Free (SMF) lead acid long life battery including battery stand, couplers/ connectors, hardware’s and all necessary accessories etc. as per technical specifications and asper DC single line diagram all complete works. |
| 124 | Supply, installation, testing and commissioning of ladder type hot dip galvanized cable tray (minimum galvanized thickness - 85 micron) with min. 1.6 mm thick GI cover plate including bend, coupler plates, hardware’s and all necessary accessories of different sizes as per technical specification and drawings to complete all works |
| 125 | 600 mm width, 75 mm depth 2 mm thick |
| 126 | 450 mm width, 62.5 mm depth 2 mm thick |
| 127 | 300 mm width, 62.5 mm depth 2 mm thick |
| 128 | Supply and laying of 200 mm dia HDPE pipe lSl marked with accessories conforming to lS 14930, Part ll complete for road/ wall crossing with all associated civil works including excavation, backfilling, etc All complete works. |
| 129 | Wiring for light point/ fan /exhaust fan points/call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FR PVC insulated copper conductor single core cable etc. as required. |
| 130 | Wiring for light /Power plug with 2X4 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed steel conduit along with 1 NO 4 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required. |
| 131 | Wiring for circuit / submain wiring along with earth wire with 2x2.5 sq.mm of FR PVC insulated copper conductor single core cable in surface/ recessed steel conduit as required + 1x2.5 sq.mm earth wire. |
| 132 | Wiring for circuit / submain wiring along with earth wire with 2x4 sq.mm of FR PVC insulated copper conductor single core cable in surface/ recessed steel conduit as required + 1x4 sq.mm earth wire. |
| 133 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 134 | Providing and fixing following capacity 63 A TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. |
| 135 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, Double door |
| 136 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (4 + 24), Double door |
| 137 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A |
| 138 | Wiring for circuit/ submain wiring along with earth wire with the (2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire) sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 139 | Wiring for circuit/ submain wiring along with earth wire with the (2 X 10 sq. mm + 1 X 6 sq. mm earth wire) sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 140 | EXTERNAL LIGHTING |
| 141 | Supply of Single piece, cast aluminium housing with full glass integral luminaires (lP 66) with 45 W LED and 50 mm dia. G I pipe medium duty for support and fixing steel support on the outer surface of pumping station |
| 142 | i) Supply of Single piece, cast aluminum housing with full glass integral luminaires (IP 66) with 45 W LED and 50 mm dia. G I pipe medium duty for support and fixing steel support on the outer surface of pumping station |
| 143 | ii) Supply of 2 c x 4 sq mm al conductor PVC Armoured cable of 1.1 KV grade |
| 144 | iii) Laying and fixing of one number of 2c x 4 sq mm of PVC Al Armoured cable of 1.1 grade clamped on wall with 1mm thick saddle as required |
| 145 | EARTHING |
| 146 | Supply, installation, testing & commissioning of treated earth pit with plate earthing as per the detailed specitication given at clause 6.3.12 Number of treated earth pit shall be designed as per the soil resistivity.(Note:- each Transformer neutral earthing shall be done with two earth pit exclusively in addition to above) in complete grid system. |
| 147 | i) Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 148 | ii) Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick earth strip connecting from individual electrical equipment to main earthing grid/ lightening protection grid/ earth pit in horizontal or vertical position including welding/bolting, laid in ground |
| 149 | iii) Supply, installation, testing & commissioning of directly buried earth pit with perforated earth pipe made out from heavy duty GI Pipe 40 mm dia,3M long including hard wares, earth pit marker and all accessories with alternate layer of salt and charcoal as per IS:3043, technical specifications |
| 150 | iv ) Supply, installation, testing and commissioning of earth strip connecting from individual electrical equipment to main earthing grid/ lightening protection grid/ earth pit in horizontal or vertical position including welding/bolting, laid in ground (including excavation and backfilling, if necessary)/ buried cable trench or on wall/ floor on saddle or embedded in concrete or in concrete cable trench, including interconnection with consumer earth and clamps/ connectors, test links for lightning protection down conductors, hardwares and necessary accessories etc. for the following sizes; all complete works. |
| 151 | a) 25mm X 5mm GI |
| 152 | b ) 6 SWG Gl Wire |
| 153 | c ) Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.l pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc as required. |
| 154 | d ) Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 155 | e ) Providing and laying earth connection from earth electrode with 6 SWG dia G I Wire in 15 mm dia G.l. pipe from earth electrode including connection with G l. thimble excavation and re-filling as required. |
| 156 | LIGHTNING |
| 157 | Providing and fixing of lightning conductor finial, made of 25mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. with G.I. tape 20 mm X 3 mm thick on parapet (horizontal or on vertical surface of wall for lightning conductor and 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required complete as required. |
| 158 | i) Providing and fixing of lightning conductor finial, made of 25mm dia 300 mm long Gl tube. having single prong at top, with 85mm dia 6mm thick GI base plate including holes etc. complete as required |
| 159 | ii) Providing and fixing G I tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For horizontal run) |
| 160 | iii) Providing and fixing G I lape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required (For vertical run) |
| 161 | iv) Providing and fixing testing joint, made of 20 mm X 3 mm thick G.l. strip, 125 mm long, with 4 Nos. of G.l. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 162 | v) Providing and laying G.l. tape 32 mm X 6 mm from earth electrode directly in ground as required. |
| 163 | INSTRUMENTION WORKS |
| 164 | Supply, installation, testing & commissioning of Instrument Control Panel along with PLC and associated hardware & software |
| 165 | Supply, installation, testing & commissioning of Ultrasonic type level measuring system |
| 166 | Supply, installation, testing & commissioning of Conductivity type level switches |
| 167 | Supply, installation, testing & commissioning of Pressure measuring system |
| 168 | Supply, installation, testing & commissioning of Pressure gauges along with accessories |
| 169 | Supply, installation, testing & commissioning of Full-bore Electromagnetic Flowmeter (600 mm) to be installed at suitable level of suitable size |
| 170 | Supply, installation, testing & commissioning of Batteries and battery charger (UPS) 24 v |
| 171 | Supply, Laying, testing & commissioning of Instrumentation signal, control, power & communication cables of different sizes as required to complete all works along with cable trays, lugs, glands, conduits, steel supports, clamps etc. |
| 172 | a) 2C X 1.5 |
| 173 | b) 12C X 1.5 |
| 174 | c) 6C X 1.5 |
| 175 | d) Laying of one number PVC insulated and pVC sheathed / XLPE power cable of 1.1 kV grade upto 35 sq mm in the existing channel |
| 176 | Supply, installation, testing & commissioning of Field cabinets for instruments and junction boxes as required to complete works |
| 177 | Supply, installation, testing & commissioning of PC based Data Acquisition and Monitoring System (DAMS) along with printers, DAMS software, all hardware & software required for interfacing with PLC system, computer desk etc. |
| 178 | Supply, installation, testing & commissioning of Ink jet coloured printer (Latest printer) |
| 179 | Supply, installation, testing & commissioning of Dot matrix 132 column printer (Latest printer) |
| 180 | Supply, installation, testing & commissioning of Laptop programming unit along with PLC programming software and necessary cables and connectors |
| 181 | Supply, installation, testing & commissioning of Surge protection devices for instruments as required |
| 182 | OPERATION & MAINTENANCE FOR TEN YEARS (2DLP + 8) |
| 183 | Year 1 with DLP |
| 184 | Year 2 with DLP |
| 185 | Year 3 |
| 186 | Year 4 |
| 187 | Year 5 |
| 188 | Year 6 |
| 189 | Year 7 |
| 190 | Year 8 |
| 191 | Year 9 |
| 192 | Year 10 |
| 193 | ENGINEERING, PROCUREMENT AND CONSTRUCTION OF 0.72 MG CAPACITY UNDER GROUND RESERVOIR AND BOOSTER PUMPING STATION INCLUDING CIVIL WORKS, E&M WORKS ALONG WITH PERIPHERAL MAINS & FEEDER LINE AT G.T. ROAD SHAHADRA, (TYR). |
| 194 | CIVIL WORKS Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
TodayCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 14 daysCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 14 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 14 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender