Project Description
Tender for Re-Configuration Of Existing Terminal Building At Raja Bhoj Airport, Bhopal (Phase-2). Sh: Hvac Work.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 12-Nov-2026 | Corrigendum 1 | Financial Bid | 18-Nov-2026 |
| 2 | 12-Nov-2026 | Corrigendum 1 | Financial Bid | 21-Nov-2026 |
| 3 | 18-Nov-2026 | Corrigendum 2 | Date | 21-Nov-2026 |
| 4 | 20-Nov-2026 | Corrigendum 3 | Date | 24-Nov-2026 |
| 5 | 18-Nov-2026 | Corrigendum 2 | Date | 21-Nov-2026 |
| 6 | 12-Nov-2026 | Corrigendum 1 | Financial Bid | 24-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supplying, installation, testing and commissioning of factory built, of double skin Horizontal floor mounted double skin type Air Handling Units with Chilled Water coil. The AHU housing shall be made of 48±2mm thick panels consisting of 0.8 mm thick galvanized pre- plasticised/powder coated sheet on outside and 0.63 mm thick plain GI sheet inside with polyurethane foam (PUF) 45±2 kg/m3 density insulation factory injected between them by injection moulding machine. AHU housing framing structure shall be thermal break structure type. The AHU shall have a fan section with Plug Fan, TEFC drive, IE-3 motor suitable for 215/415+ 10% volts, 1/3 phase 50 Hz AC supply, motor mounting arrangement inside the casings, stainless steel (18G) drain pan with PUF insulation, Coil section with ARI 410A compliant Cu Tube / Al finned 6 Row deep -12 FPI CHW coil, suitable for Chilled Water application, aluminium damper on the outlet of AHU, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, double fire retardant canvas connections and access doors to attend the motor/fan, etc. complete as per drawings and specifications. Filters shall have efficiency of 90 % down to 10 micron as per ASHRAE standard. AHU should be designed in such a way considering 20 to 30% clogged filters. The AHU without mixing box shall be complete in all respects .The motor shall be suitable for operation with VFD. |
| 2 | 40000 CFM, 6RD Cooling Coil, Plug Fan, 65 mm SP |
| 3 | 35000 CFM, 6RD Cooling Coil, Plug Fan, 65 mm SP |
| 4 | 23000 CFM, 6RD Cooling Coil, Plug Fan, 65 mm SP |
| 5 | 6200 CFM, 6RD Cooling Coil, Plug Fan, 65 mm SP |
| 6 | Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cum density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including canvas cloth & Star Bond 30 - 36 complete and repairing of damage to building etc. required complete in all respect. as directed by EIC Note:-The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S.Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.Neccesary MS support as per the CPWD norms, shall be provided to cater the load of chilled water piping including all accessopries like walls, flanges etc |
| 7 | 200 mm dia. (32 mm thick insulation) including 7ml with star bond |
| 8 | 125 mm dia. (32 mm thick insulation) including 7ml with star bond |
| 9 | 65 mm dia. (32 mm thick insulation) including 7ml with star bond |
| 10 | Supply, installation, testing and commissioning U-PVC pipe with fittings of 10 kg /cm3. with 6mm thick Nitrile rubber of Class \\"1\\" including all fittings and jointing with solvent cement and , including cutting chieseling / holes in walls ,wherever required and making good the same, complete as directed by the Engineer in charge. |
| 11 | 65 mm nominal dia Pipes |
| 12 | 40 mm nominal dia Pipes |
| 13 | 32 mm nominal dia Pipes |
| 14 | 25 mm nominal dia Pipes |
| 15 | Supplying, fixing, testing and commissioning of Butterfly Valve (Mannual) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified., strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications |
| 16 | 125 mm dia |
| 17 | 65 mm dia |
| 18 | Supplying, fixing, testing and commissioning of Balancing Valve with built in measuring facility with CI body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.200 mm dia |
| 19 | Providing & fixing of C.I double flange suction \\" Y\\" type strainer fabricated out of minimum 1.6 mm thick Stainless Steel sheet with 3 mm dia. perforation holes with stainless steel flange including nuts, bolts and 3 mm thick rubber insertion complete & tested to 16 Kg/Sq.cm pressure complete as required and as per tender specification. |
| 20 | 125 mm dia |
| 21 | 65 mm dia |
| 22 | Providing and fixing 65 mm dia size ball valve (brass) of approved quality, High or low pressure. |
| 23 | Providing and fixing in position the industrial type pressure guages with gun metal / brass valves complete as required, PSI range 0 to 100. |
| 24 | Providing & fixing in position the mercury in glass industrial type thermometers with temperature range -10°C to 60°C. |
| 25 | Providing & fixing of Auto Air Vent 15mm complete as required. |
| 26 | Supplying and erection of MS channel/ angle iron of suitable size including with MS flat iron clamps nut and bolts, washer, drilling of holes, complete with 2 coats of red oxide and 2 coats of Aluminium paint etc as reqd. |
| 27 | GSS RECTANGULAR DUCTINGSupply, Installation, Balancing & Commissioning of factory fabricated GSS sheet metal ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness including all accessories complete as required for installation. Splitter & vanes etc .shall be apart of ducting no extra cost shall be paid for the same.All support selection shall be based on gripple wire. No other support shall be acceptable. |
| 28 | 1.25 mm sheet duct |
| 29 | 1.00 mm sheet duct |
| 30 | 0.80 mm sheet duct |
| 31 | 0.63 mm sheet duct |
| 32 | GSS RECTANGULAR DUCTINGSupply, Fabrication, installation and testing of sheet metal ducts (Site FABRICATED DUCTS For Connection /Plenum etc.) in accordance with the approved shop drawings complete with all accessories like vanes, flanges, suspension rods, anchor bolts, GI bolts & nuts, etc., as per specifications. |
| 33 | 1.25 mm sheet duct |
| 34 | 1.00 mm sheet duct |
| 35 | 0.80 mm sheet duct |
| 36 | 0.63 mm sheet duct |
| 37 | INSULATION WORKSupply & Installation of Thermal Insulation on Duct using Closed Cell Class O Nitrile Rubber Elastomeric Insulation of Density 40 Kg/m3 (Minimum), Thermal Conductivity as per ASTM / EN standard and with Factory Laminated Aluminium Foil of 60 microns using manufacturer's recommended Rubber based Adhesive in a blend of solvents complete as per Specifications.16mm thick Class O Nitrile Rubber Insulation with Aluminium Foil of 60 microns |
| 38 | Supply and Application of Acoustic Insulation Inside the Duct with Nitrile Rubber open cell foam with minimum Density 140 Kg/m3, passing Class 1 Fire Performance test as per BS 476 Part 7 and with built-in EPA approved Microban antimicrobial protection; to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents.15 mm thickness (Internal Lining of Ducts) |
| 39 | Supply, fixing, testing and commissioning of Motorised dampers with 150 mm sleeves as where required of required sizes . The damper shall be motorized and spring return so as to close the damper in the event of power faliure automatically and open the same in case of power being restored. The spring return action shall be built mechanism and not externally mounted. The damper shall also be closed in the event of a fire signal which shall be provided by Fire Alarm System in each AHU's/ Smoke extract fans panel etc. as per specifications as required. (Makes: / Dynamic Equipments/Ecoair/Swirl Air Equipments Pvt. Ltd.) |
| 40 | Motorized Damper |
| 41 | Actuator with Control Panel |
| 42 | Supplying and fixing of following sizes of medium class MS conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 43 | 40 mm |
| 44 | Supplying, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 45 | SITC of double layer flexible connections Canvas for ducting connection shall be constructed of fire resistant double resin sleeve as per the approved shop drawings and specification |
| 46 | Supply, fixing, testing and commissioning of Expansion Bellow alongwith connection with flange , nut bolt, insulation complete etc as required |
| 47 | 125 mm dia. |
| 48 | 65 mm dia. |
| 49 | Dismantling of Existing following rating AHUs and keep in AAI store at the lead of 5 KM as directed by EIC. |
| 50 | 35000 CFM |
| 51 | 32000 CFM |
| 52 | 23000 CFM |
| 53 | 5000 CFM |
| 54 | Dismantling of Existing MS Chilled Water Piping of different sizes including supports and keep in AAI store at the lead of 5 KM as directed by EIC. |
| 55 | INLINE FAN SITC of single skin inline fan capacity of 300 CFM and 20 mm WC static pressure, direct driven, cabinet type, single phase/three phase motor complete with mounting brackets/suspensions arrangement from ceiling and flexiable connector at inlet/outlet,internal wiring including support structure & interconnection with existing duct. |
| 56 | SITC of Powder coated extruded aluminium construction linear grills with removable core as per approved drawings and specifications |
| 57 | Supply Installation,Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), microprocessor based Controller, top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V+/-10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. Connecting refnet is the part of the Outdoor Unit. SITC of MS Stands for outdoor units made in 100 mm wide C Channel duly painted with one coat of red oxide & two coats of synthetic enamel paint. |
| 58 | 32 HP |
| 59 | 12 HP |
| 60 | Supply, installation, testing and commissioning of Ceiling Mounted 4-Way Cassette Type Air Conditioning Unit complete with all associated accessories including complete fixing arrangement etc. |
| 61 | 1.5 TR |
| 62 | Supply, Installation, testing and Commissioning of Communication cable between indoor to outdoor 2C x 1.0 Sqmm Copper Shielded cable in medium class PVC Conduit Complete etc as required. |
| 63 | Supply, Installation, testing and Commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/harddrawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquidlines, all accessories as per specifications etc. as required : |
| 64 | 41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation |
| 65 | 38.10 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation |
| 66 | 34.90 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation |
| 67 | 31.60 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation |
| 68 | 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.20 mm with 19 mm thick insulation |
| 69 | 25.20 mm dia (OD) (Hard drawn) with tube thickness 1.20 mm with 19 mm thick insulation |
| 70 | 22.20 mm dia (OD) (Hard drawn) with tube thickness 1.0 mm with 19 mm thick insulation |
| 71 | 19.00 mm dia (OD) (Hard/soft drawn) with tube thickness 1.0 mm with 19 mm thick insulation |
| 72 | 15.9 mm dia (OD) (Hard/soft drawn) with tube thickness 1.0 mm with 19 mm thick insulation |
| 73 | 12.7 mm dia (OD) (Hard/soft drawn) with tube thickness 0.80/1.00 mm with 19 mm thick insulation |
| 74 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 0.80/1.00 mm with 19 mm thick insulation |
| 75 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 0.80/1.00 mm 19 mm thick insulation |
| 76 | Supply and fixing of 4 Core X 4 Sq.mm sizes of Power Cables multi stranded Copper conductor, XLPE Insulated flexible FRLS cable. |
| 77 | Supply and fixing of 4 Core X 16 Sq.mm sizes of Power Cables multi stranded Copper conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath, Armour, FRLS at outer sheath, 1100V grade as per IS 7098 (Part 1) 1988 with upto date amendments. |
| 78 | Supplying and fixing of Pre wired 8 way (4 + 24), Double door surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. |
| 79 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 80 | Supplying and fixing 63 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Four pole |
| 81 | Supplying and fixing 63 A rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 82 | Supply,installing,testing of Following size perforated Hot Dipped Galvanized cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling/fixing to the wall/RCC beam/iron structures as per site requirement complete in all respects i/c M.S/GI Supports |
| 83 | 300 x 100 x 1.6mm thick cable tray |
| 84 | 150 x 50 x 1.6mm thick cable tray |
| 85 | Supply Installation, testing and commissioning of Y-joints of suitable size as per site requirements. |
| 86 | Supply, Installation, testing and Commissioning of VRF/VRV system with additional eco-friendly refrigerant gas. |
| 87 | Supply of following sizes of Power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath, Armour, FRLS at outer sheath, 1100V grade as per IS 7098 (Part 1) 1988 with upto date amendments.3.5 x 240 sq.mm. |
| 88 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on cable tray as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 89 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required3½ X 240 sq. mm (62mm) |
| 90 | Supplying and laying 4 x 10 sq. mm sizes of FRLSH PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 91 | Supply, Installation, Testing and Commissioning of cubicle type LT panel,as per 61439-1 & 61439-2, suitable for 415V+/-10%, 3 Phase, 4 wire 50 Hz AC supply system, fabricated in compartmentalized 4b modular design IP 42 for indoor & IP 65 for outdoor application, from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having TPN Aluminium alloy bus bars for high conductivity, SMC bus bar supports,with short circuit withstand capacity of 50 KA for 1 sec, Internal arc withstand capacity 50 KA for 0.3 second, minimum impact resistance IK10 with each compartment front & back sheet steel metal door,, entire panel shall have a common GI earth bar of size 50 mm x 6 mm at the rear with 2 Nos. earth stud, solid / flexible connections from main bus bar to switchgears and from switchgear output to cable termination in cable alley with required size of AL conductors / bus bars and control wiring with 2.5 sqmm PVC insulated copper conductor cable (FRLSH), cable alleys, Top entery cable entery provision etc. . Bottom base support : grouting raised pedestal cum base frame,250 mm height for LT panel madeout of MS channel should not less than 200 mm x 50 mm x 5 mm thick |
| 92 | INCOMING- I & II 2 Nos MCCB 400 A microprocessor based, 50 kA(Ics=Icu), 4 Pole, with inbuilt O/L, S/C & E/F protection. Each incomer shall have one set of following item :- 1 Set of RYB phase indicating LED lamps controlled by 2 amp MCB. 1 Set of ON/ OFF/TRIP Indicating LED Lamps With 2 Amp MCB For MCCB 1 No. Digital MFM meter.digital multifunction meter suitable to measure voltage, Ampere, Frequency, Power Factor, Measurement of both kVA/kW/kVAH with RS-485 port.electrical and mechanical interlocking for incomer. |
| 93 | BUSBARS I & II 4P, Aluminium bus bars of 600A capacity with heat shrinkable coloured sleeves incl. SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 50 kA for 1 sec. |
| 94 | OUTGOING SECTIONOutgoing 1 - Suitable rating VFD with By pass arrangement(DOL/ Star -Delta starter) to run 40000 CFM AHU , (approximate capacity of AHU motor is 20 HP/15KW, 2 Nos)Outgoing 2 - Suitable rating VFD with By pass arrangement(DOL/ Star -Delta starter) to run 35000 CFM AHU , (approximate capacity of AHU motor is 15 HP/11KW , 2 Nos) Outgoing 3 - Suitable rating VFD with By pass arrangement(DOL/ Star -Delta starter) to run 35000 CFM AHU , (approximate capacity of AHU motor is 15 HP/11KW , 2 Nos) Outgoing 4 - Suitable rating VFD with By pass arrangement(DOL/ Star -Delta starter) to run 23000 CFM AHU , (approximate capacity of AHU motor is 20HP/15KW , 1 Nos) Outgoing 5 - Suitable rating VFD with By pass arrangement(DOL/ Star -Delta starter) to run 6200 CFM AHU , (approximate capacity of AHU motor is 10HP/7.5KW , 1 Nos) Outgoing 6 - MCCB 63 A microprocessor based, 50 kA(Ics=Icu), 4 Pole, with inbuilt O/L, S/C & E/F protection as per specification., Outgoing 7 - MCCB 63 A microprocessor based, 50 kA(Ics=Icu), 4 Pole, with inbuilt O/L, S/C & E/F protection as per specification., Outgoing 8 - MCCB 63 A microprocessor based, 50 kA(Ics=Icu), 4 Pole, with inbuilt O/L, S/C & E/F protection as per specification.VFD design for HVAC application for supply air fan, each VFD panel to be provided with digital display showing electrical parameters like voltage, current and power etc.VFD should have following I/O points i.e. AI-4, AO-4, DO-4, DI-6; VFD to be configured / programmed as the site requirements, Note : Actual capacity of VFD rating/starter shall be fixed as per AHU OEM design submission. |
| 95 | Each outgoing shall have one set of the following items:Each outgoing have digital MFM meter. digital multifunction meter suitable to measure voltage, Ampere, Frequency, Power Factor, Measurement of both KVA/KW/kVAH.1 Set of 'ON', 'OFF','TRIP LED lamps controlled by 2 amp MCB with each MCCB outgoing. |
| 96 | Each outgoing shall have one set of the following items:NoteAll MICROPROCESSOR based MCCBs shall be provided with inbuilt O/L, S/C & E/F protection. |
| 97 | LT panel |
| 98 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 99 | Testing & commissioning of existing chiller system(4x350 TR, Make -Daiken) with the presence of OEM after reconfigured the system such as reshifting of exiting chiller line & replacement of AHU including water balancing (Dewatering & recharging) work complete in all respects to commissioning of system as required & as directed by EIC. |
| 100 | Supply, Installation, testing and commissioning of Pressure independent type 2 way Balancing and modulatingControl valves in a single Unit of Valve along with Digital thermostat & its connecting wiring. PN10 Rating. DN 15 to DN 32 in Brass Body Ext. Threaded, DN 40 & DN 50 in Cast Iron Body, Ext. Threaded DN 65 to DN 100 Cast Iron body, flanged connection Duly mounted with Modulating actuator IP42/54. Accordingly type suitable for 24V/230V AC. As per specifications of following sizes:125 mm dia Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-4 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 2 daysCorrigendum-5 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-6 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 2 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents