Tender For Providing Iei & Eei For Vehicle Charging Station At Radhanagar Beach Parking Swaraj Dweep Under Sd-Iv E&M Division, Apwd, Prothrapur.
Tender Value
2.18 Lakhs
Estimated cost
Bid Submission
06 Nov 2026
5 days left
EMD
4377
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
South Andamans → Andaman And Nicobar Islands
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Providing Iei & Eei For Vehicle Charging Station At Radhanagar Beach Parking Swaraj Dweep Under Sd-Iv E&M Division, Apwd, Prothrapur.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. a) 2x1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 2 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required |
| 3 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 4 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required |
| 5 | Providing earthing with safe earthing electrode of galvanization 80 to 100 microns, length 2 mtr, outer dia 50 mm, inner dia 19 mm and inner space be filled with crystalline conductive mixture including filling -up with electrolite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. (Ashlok) |
| 6 | Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 7 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 8 | Supplying of following size of XLPE insulated heavy duty armoured copper conductor UG cable of 650/1100 V grade conforming to IS: 7098 (Part-1) 1988 as applicable 5 Make: RR/CCI/Gloster/ Havells/ Polycab/Finolex etc as reqd.a)35 Sq.mm x 4.0 Core |
| 9 | Supplying of following size of XLPE insulated heavy duty armoured copper conductor UG cable of 650/1100 V grade conforming to IS: 7098 (Part-1) 1988 as applicable 5 Make: RR/CCI/Gloster/ Havells/ Polycab/Finolex etc as reqd.a) 16 Sq.mm x 4.0 Core |
| 10 | Supplying and making end termination with copper lugs for following size of PVC insulated and PVC sheathed /XLPE copper conductor cable of 1.1 KV grade as required.a) 4.0 core X 16 sq. mm |
| 11 | Supplying and Laying 77/63 mm DWC Pipe conforming to IS: 16205 (Part-24-2018) directly in ground at the depth of 50 cm i/c excavation and refilling the trench etc., as required. |
| 12 | Supplying and Laying 77/63 mm DWC Pipe conforming to IS: 16205 (Part-24-2018) in surface by clamping etc., as required. |
| 13 | Supplying and Laying 50/38 mm DWC Pipe conforming to IS: 16205 (Part-24-2018) in surface by clamping etc., as required. |
| 14 | Laying of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required.a) Upto 35 sq. mm |
| 15 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.a) Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 16 | Supplying and fixing of 30W Flood light, IP65 rating Make: Crompton Gleam Neo or its equivalent as required |
| 17 | Supplying, installation, testing and commissioning of Outdoor type, floor-mounted, water-resistant, cubicle type LT Electrical Panel of size 1.00 m (L) × 0.70 m (B) × 0.40 m (D), suitable for 415 Volts, 3-phase, fabricated out of 2.0 mm thick CRC sheet, duly reinforced with M.S. angle and M.S. flat sections and supported on four numbers M.S. legs of 0.80 m height from ground level. The panel shall be of double door construction with suitable locking arrangement, dust and vermin proof, compartmentalised to accommodate switchgear of various ratings such as copper busbar of suitable length, MCCB, switch fuse units, cut-outs, isolators and energy meter. The panel shall have adequate space for installation of energy meter with transparent acrylic/glass window for meter reading. The copper busbar system shall be mounted on suitable SMC/DMC insulators. The panel shall be provided with earthing studs for body earthing. The panel shall be treated with one coat of epoxy zinc phosphate primer and finished with two coats of weather-proof enamel paint (Silver). The work shall include providing and laying PCC foundation of suitable size, danger notice plate/sticker and all necessary hardware required for proper installation, complete in all respects as directed by the Engineer-in-Charge.The panel shall be complete with supplying and fixing of the following switchgear and accessories:a) Copper Bus bar 25 x 5mm : 1Setb) 4-Pole MCCB, 63 Ampere, 32-39 kA breaking capacity – 01 No.c) Cut Outs 63 A - 03 Nos., d) 40A DP Isolator: 01 No.e) 6A/16A SP MCB: 02 Nos., f) 2-Pole Contactor, 18 A rating – 01 No.g) 24-Hour Analog Time Switch (SST – 15 minutes interval) – 01 No. etc., as requiredh) Installation with PCC work.Note: Internal wiring and interconnections shall be carried out using 16 sq.mm FRLS copper conductor wire, including provision of 3 metres extra wire for future energy meter connection. However, for items (d) to (g), interconnections shall be carried out using 4 sq.mm FRLS copper conductor wire. All wiring shall be neatly dressed, properly ferruled and terminated with suitable copper lugs, complete in all respects as per specifications and as directed by the Engineer-in-Charge. |
| 18 | Supplying & fixing of CO2 fire extingusher (Stored Pressure) 4.5 kg capacity, BIS Approved (IS 2878:2004) consisting discharge nozzle suspension bracket etc Make: Kanex or its equivalent etc., as required. |
| 19 | Supplying & fixing of AVD fire extingusher, 4.0 kg capacity suitable for extinguishing fire in Lithium-ion battery, BIS Approved (IS 2878:2004) consisting discharge nozzle suspension bracket etc Make: Kanex or its equivalent etc. as required. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 26, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 06, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysNov 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender