Tender For Supply Installation Testing and Commissioning of Electrical Panel For Atd-1&3 Oxygen Generation Plant At Ssbh, Kota
Tender Value
2.66 Lakhs
Estimated cost
Bid Submission
03 Nov 2026
1 days left
EMD
5320
Bank guarantee accepted
Document Fee
200
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kota → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Supply Installation Testing and Commissioning of Electrical Panel For Atd-1&3 Oxygen Generation Plant At Ssbh, Kota
BOQ
| Sl. No. | Item Description |
| 1 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-(a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided(b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 2 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.(f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 3 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. Electrolytic grade Aluminium bus bar 6010 grade |
| 4 | Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. |
| 5 | Three phase Ammeter with Inbuilt Selector Switch |
| 6 | Three phase Voltmeter with Inbuilt Selector Switch |
| 7 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . Ring type tape wound CTC T Class 1, Ratio 200/5 to 600/5, Burden 10 VA |
| 8 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. Red/yellow/Green colour |
| 9 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 10 | 4 pole MCCB With Thermal Magnetic release250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 11 | 4 pole MCCB With Thermal Magnetic release400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 12 | 4 pole MCCB With Thermal Magnetic release630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, |
| 13 | Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. |
| 14 | Spreaders for 250A, 4 Pole MCCB |
| 15 | Spreaders for 400A, 4Pole MCCB |
| 16 | Spreaders for 630A, 4Pole MCCB |
| 17 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. |
| 18 | Supply and Installation of unshielded/360 degree shielded PCB based Information outlets made of high impact plastic body with ABS, Flammability rating UL 94 V-0 with provision for protection against dust in jack or Faceplate, suitable for Cat 6/6A application complying to latest amendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat 6/6A standards at frequencies 250/ 500 MHz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have toolless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA 568 C.2 & ISO/IEC 11801 or latest standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocol (VOIP) Specifications in existing modular/MS Boxes along with necessary connections as required. All as per pre approved by Engineer in charge. Cat 6, Un-sheilded Information Outlet |
| 19 | Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture with dust cover, material should be High-impact, flame retardant, thermoplastic, UL listed material, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge. Single Aperture |
| 20 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 21 | 95.0 Sq. mm, 3.5 core |
| 22 | 120.0 Sq. mm, 3.5 core |
| 23 | 185.0 Sq. mm, 3.5 core |
| 24 | SITC of Strip in Pipe Earthing using hot-dip galvanized 'B' class G.I. pipe, as secondary conductor. The system shall incorporate a crystalline conductive compound between the primary and secondary conductors to enhance conductivity and long-term stability. of following size and length and as per point mentioned (a), (b), [c), (d), (e) (f) as below (a) Bore a hole of dia. 150 mm of required length, Place the rod in the centre of Hole (b) Earth enhancing compound to ensure the moisture content and electrical conductivity, 30 kg for 3000 mm. 20 Kg. for 2000 mm The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7© Connect the Strip Terminal (110 mm long) with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt(d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.(e) Testing of earth resistance for value of 5 ohms or less as required.(f) Test certificates for confirming above standards from OEM is mandatory. Outer Pipe - 76 mm dia GI pipe , Inner Conductor- GI strip 50x6 mm Length 3meter. Terminal 50x6mm GI. |
| 25 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. 8 SWG G.I. ( Hot Dipped ) Wire |
| 26 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size. |
| 27 | 70.0 Sq.mm |
| 28 | 95.0 Sq.mm |
| 29 | 120.0 Sq.mm |
| 30 | 150.0 Sq.mm |
| 31 | 185.0 Sq.mm |
| 32 | P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and two coats enamel paint including cutting, welding, holes etc.of following sizes as required.35mm x 35mm x 5mm |
| 33 | Add Extra in item no. 11.1 to 11.4 for Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Up to 35 Sq.mm fixed with 25 mm x 2 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps. |
| 34 | Add 18.00% GST Amount (Rs.) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 03, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayNov 04, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender