Tender For Creation Of Dedicated Essential Feeder From Receiving Station Boniyar For Providing Of Power Supply To Phc Boniyar Under District Capex
Tender Value
15.90 Lakhs
Estimated cost
Bid Submission
16 Nov 2026
14 days left
EMD
31800
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Baramulla → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Creation Of Dedicated Essential Feeder From Receiving Station Boniyar For Providing Of Power Supply To Phc Boniyar Under District Capex
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation, Testing and Commissioning of |
| 2 | Supply, Carriage upto site (including Loading/Unloading),Testing and Erection of Steel Tubular Pole, 09 Mtr. Long Pole(ST-410 SP-33) with planting depth of 1/6 th of the height of the pole, as per approved drawings/standards |
| 3 | Supply & Laying of Cement bottoming for 09 Mtr ST Pole in 1:2:4 mix as per Standards 0.48 cum / pole including the Loading/Carriage/Unloading of required material. |
| 4 | Providing & Fixing of Pole Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip.25x3mmas per approved drawings/standards |
| 5 | Providing & Painting of 09 Mtr ST Poles with one coat of Red Oxide and two coats of aluminium paint as per approved drawings/standards |
| 6 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of GI Channel/Angle/Flat of sizes including clamps as per approved drawings/standards |
| 7 | Supply,Testing,Loading,Carriage,Unloading and fixing of Galvanised Nuts & Bolts of sizes |
| 8 | Providing & Fixing of Danger Plates with Clamps (enameled) as per approved drawings/standards |
| 9 | Providing & fixing Anti-Climbing Devices with Clampsas per approved drawings/standards |
| 10 | Supply, Carriage upto site (including Loading/Unloading),Testing and fixing of 200 mm² ACSR Conductor( Panther) as per approved drawings/standards |
| 11 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm as per approved drawings/standards |
| 12 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting as per approved drawings/standards |
| 13 | Supply, Carriage upto site (including Loading/Unloading) Testing & fixing of T Clamps as per approved drawings/standards |
| 14 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :400-200/5-5A,TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (Reputed Make) |
| 15 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Incomer SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :600-300/5-5A,Epoxy Casted PT with PTR :11KV/110 V, TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (Reputed Make) |
| 16 | Dismantling of existing outdated 11 kV VCB Panels, including careful removal, handling, loading, transportation/carriage up to Divisional Stores, unloading and stacking at Divisional Stores, complete in all respects as directed by the Engineer-in-Charge |
| 17 | Spares/Contengencies/T&P Items |
| 18 | Supply, installation, testing and commissioning of A4 Monochrome LaserJet Printer, minimum 30 PPM, 1200 × 1200 dpi, automatic duplex printing, USB/Ethernet connectivity, complete with all standard accessories and one-year warranty (HP/ Canon/ Epson or equivalent) (to be provided at Divisional Office) |
| 19 | Supply, installation, testing and commissioning of wall-mounted RO water purifier with RO+UF purification technology, UV LED, TDS control and built-in TDS meter, having 8 litre storage tank and minimum 20 LPH purification capacity, with automatic shut-off facility, suitable for continuous operation, complete with all necessary filters, fittings, tubing, electrical connections, mounting accessories and charger/power supply, complete in all respects Aquaguard/Kent/Urban or equivalent make |
| 20 | Supply, Carriage upto Divisional Office (including Loading/Unloading) of Laminated File Covers standard quality Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 16, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysNov 18, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓