Tender for Construction Work Of 33/11 Kv Electric Sub-Station (Civil Works), Staff Quarters, And Boundary Wall Under Sector-3B Of Saumitra Vihar Yojna, Lucknow.
BOQ
| Sl. No. | Item Description |
| 1 | Main Building cum control room (Civil Work) Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.2.8.1All kinds of soil. |
| 2 | Earth work in cutting or in embankment in ordinary soil, excavation to be in the regular pits not exceeding 0.5m in depth and earthwork in mbankment to be in 20cm. layers, including ramming and dessing the surface to required levels & slopes & also including 1.5 lift & 30m. lead. The earth from cutting to be used in making embankment or to be deposited as spoil banks within 30m. Distance as directed by the engineer incharge (Including Royalty). & Also including cartage up to 5 Km from out side the site of work & including cost of earth, watering, dressing & compacting the soil to achieve 95% proctor density. |
| 3 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering All work up to plinth level: 1:4:8 (1 Cement: 4 coarse sand (zone-III) derived from natural sources: 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 4 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 5 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 6 | Providing and Injecting chemical emulsion for pre-constructional anti termite treatment and creating and chemical varrier under and around the coloumn pits wall, trenches, basement, excavation top surface of plinth filling junction of wall and floor along the external of the building expention joints surrounding of pipes and conduits etc complete plinth area of the building at the ground floor only shall be measured as per IS 6313 (part-II 1981) aldrine emulsifiable concrete or any other apporoved material such as hepthachlor or cholordance will be used. The rate of application 5 Lit/per sqm of chemical emulsion shall be as follows- 1- Treatment for masonary and foundation. 2- Back fill in immediate contact with foundation 7.50 Lit per sqm. 3- Treatment of top surface of plinth filling 5 Lit per sqm. 4- Treament of soil along external perimeters of building 7.50 lt/sqm. 5- Treatment of soil under appron along external perimeter 5 lit per sqm. |
| 7 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement: 1.5 coarse sand(zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). for plinth and lintels of doors and window |
| 8 | Centering and Shuttering including strutting, propping etc. and removal of form for Lintel, beams, plinth beams, girders, bressumers and cantilevers. |
| 9 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases above plinth level up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with 1:1.5:3 (1 cement: 1.5 coarse sand incuding manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 20%: 3 graded stone aggregate 20 mm nominal size including Recycled Concrete Aggregate (RCA) upto 20%) For Slab |
| 10 | Centering and Shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform |
| 11 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement: 1.5 coarse sand(zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). For Lighter Beam |
| 12 | Centering and Shuttering including strutting, propping etc. and removal of form for Lintel, beams, plinth beams, girders, bressumers and cantilevers. |
| 13 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement: For Foundation and Footing 1:1.5:3 (1 cement: 1.5 coarse sand (zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 14 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 15 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement: For Columns 1:1.5:3 (1 cement: 1.5 coarse sand (zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 16 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 17 | Class-150 brick work in 1:6 (one cement and six coarse sand sand of 1.5-2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labours, T & P etc required for proper completion of the work. |
| 18 | Class-150 brick work in 1:6 (one cement and six coarse sand sand of 1.5-2.00 fineness modulus) mortar in super-structure including necessary cutting and moulding of brick work as required and also including honeycombed brick work. Thickness of wall not to be less than one brick thick wall including supply of all material labours, T & P etc required for proper completion of work. |
| 19 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 20 | 15mm thick plaster with cement mortar consisting of 1 part cement and 4 part of approved coarse sand including supply of all material labours, T & P etc required for proper completion of work. |
| 21 | 15mm thick plaster with cement mortar consisting of 1 part cement and 6 part of approved coarse sand including supply of all material labours, T & P etc required for proper completion of work. |
| 22 | 12mm thick plaster with cement mortar consisting of 1 part cement and 6 part of approved coarse sand including supply of all material labours, T & P etc required for proper completion of work. (Outer side) |
| 23 | Engraving lines in the plaster of outer face wall vertically and horizontally to display the surface as stone facing as directed by the Engineer-in-charge including labour and T&P etc. required for proper completion of the work. Add for extra labour to allitems of plaster. |
| 24 | 62mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 25 | 25mm thick Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing omplete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick |
| 26 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm average) thick cement mortar 1:4 (1 cement: 4 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, ncluding rubbing and polishing complete. |
| 27 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/sq.m including jointing the joints with white cement and matching pigments etc., complete. |
| 28 | 40mm thick Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 29 | Providing and fixing 40 mm wide and 4 mm thick glass strips in joints of terrazo/ cement concrete floors. 5.5cm thick and 2.2cm depth |
| 30 | Providing and laying vitrified floor tiles in Size of Tile 600x600 mm (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. |
| 31 | Providing and fixing ISI marked 35mm thick flush door shutters conforming to IS : 2202 (Part I) nondecorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters, including ISI marked stainless Steel butt hinges with necessary screws. But excluding all remaining door fittings with necessary screws. |
| 32 | M.S. or Iron work of small sizes and sections such as holding down bolts, hold fast tie rods, gratings etc.(when not included in an over all rates) wrought to required from including supply of steel and its wastage etc and their fixing required for proper completion of work. Providing & fixing of hold fast for chaukhats of doors and windows. grill as per design. |
| 33 | Fixing Chowkhats in existing opening including complete as per direction of Engineer in charge. (a) Door chaukhats |
| 34 | (b) Window chaukhats |
| 35 | (c) Ventilator chaukhats |
| 36 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour. New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre |
| 37 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) |
| 38 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete |
| 39 | Making drip course in sun shade or facia as per direction of Engineer inchage including supply of all material |
| 40 | Providing and fixing 150 mm bright finished floor brass door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 41 | Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete 300x16 mm |
| 42 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 150x10mm |
| 43 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : |
| 44 | Providing and laying integral cement based treatment for water proofing on horizontal surface at all depth below ground level for under ground structures as directed by Engineer-in-Charge and consisting of :(i) Ist layer of 22 mm to 25 mm thick approved and specified rough stone slab over a 25 mm thick base of cement mortar 1:3 (1 cement : 3 coarse sand) including applying of twice ( at base and top of mortar ) cement slurry @ 2.2kg/m2 (each time) mixed with water proofing compound conforming to IS:2645 in the recommended proportion over the leveling course (leveling course to be paid separately). Joints sealed and grouted with cement slurry mixed with water proofing compound.(ii) 2nd layer of 25 mm thick cement mortar 1:3 (1 cement: 3 coarse sand) mixed with water proofing compound in recommended proportions.(iii) Finishing top with stone aggregate of 10 mm to 12 mm nominal size spreading @ 8 cudm/sqm thoroughly embedded in the 2nd layer. |
| 45 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and fanufacture. |
| 46 | Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @0.75 ltr/10 sqm of approved brand and manufacture. |
| 47 | Providing & fixing 4mm thick glass panes with putty and glazing clips in steel doors, windows, clerestory windows, with : 4.0 mm thick glass panes with brad, putty, clips etc. required including supply of all materials, labours, T&P etc. complete in all respect. |
| 48 | Supply & fixing of rolling shutter of approved make, made of required size 80x1.25 mm thick M.S. laths inter locked through their entire length and joined together at the end locks and mounted on specially designed pipe shaft with brackets side guides and arrangements for inside and outside locking with push and pull operation complete. |
| 49 | i/c the cost of providing & fixing necessary 27.5 cm long wire spring manufactured from high tensile steel wire of adequate strength confirming to IS: 4454 - part 1 |
| 50 | M.S. top cover of required thickness for rolling shutters 18 gauge |
| 51 | ball bearing for rolling shutter |
| 52 | Providing & fixing fly proof galvanized M. S wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both direction with wire of dia 0.63mm all complete with 12mmm mild steel U beading |
| 53 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) |
| 54 | Main Building cum control room (Sanitary and water suppy work) SANITARY FIXTURES & ACCESSORIES : I Providing and fixing white vitreous china pedestal type water closet ( Indian type W.C. pan ) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid. |
| 55 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require a) White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar pillar tap. |
| 56 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 57 | Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet 100 mm diameter |
| 58 | Providing and Fixing Stainless Steel grating of approved quality and colour. 125 mm diameter (M.R.) |
| 59 | Providing and fixing 8 mm dia C.P./S.S. Jet with flexible tube upto 1 meter long with S.S. triangular plate for Eureopean type W.C. of quality and make as approved by engineer-in-charge. 15mm nominal bore |
| 60 | Providing and fixing CP Brass 32 mm size Bottal Trap of approved quality & make and as per thedirection of Enginer-in-charge. |
| 61 | Providing and fixing CP Brass Single lever lelephonic wall mixture of quality & make and as per thedirection of Enginer-in-charge. 15mm dia nominal dia. |
| 62 | Providing & fixing PTMT towel rail complete with brackets fixed to wooden cleats with cp brass screws with concealed fitting arrangement of approved quality and colour. 600 mm. long towl rail length of 645 mm. width 78 mm. and effective height of 88 mm, weighing not less than 190 gms. |
| 63 | Providing and fixing PTMT Liquid soap container 109 mm wide ,125 mm high and 112 mm distance from wall of standerd shape with bracket of the same material with snap fittings of approved quality and colour weighing not less than 105 gms |
| 64 | SOIL WASTE & VENT PIPES AND FITTINGS - II Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion . (i) Single socketed pipes. (DSR-2023, Rate= 377.40) 110mm diameter |
| 65 | Supply and fixing of UPVC S.W.R. pipe type-B confirming to IS-13592 including jointing the pipes with rubber ring,lubricant and UPVC SWR cupler confirming to IS-14735. Also including excavation of treanches cutting of walls and holes and repairing the walls,floors and refilling the trenches as before but excluding supply and cost of other fIttlings such as elbow,bend,tee and y-tee including supply of al marerial labour and T&P.Required for proper completion of work. 90 mm O.D. |
| 66 | 110 mm O.D. |
| 67 | Supply and fixing of UPVC S.W.R. pipe nahni trap size 100x75,110/90 mm confirming to IS-14735 self cleaning design fixed in PCC 1:2:4 and supply and fixing of 125 mm dia heavy duty CP brass jali. |
| 68 | Supply and fixing of UPVC S.W.R. plain bend confirming to IS-14735. Size 90 mm |
| 69 | Size 110 mm |
| 70 | Supply and fixing of UPVC S.W.R. Cowel confirming to IS-14735. Size 90 mm |
| 71 | Size 110 mm |
| 72 | Supply and fixing of UPVC S.W.R. plain tee confirming to IS-14735. Size 90x90x90 mm |
| 73 | Size 110x110x110 mm |
| 74 | Supply and fixing of UPVC S.W.R. plain Y confirming to IS-14735. Size 90 mm |
| 75 | Size 110 mm |
| 76 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. 110mm |
| 77 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50mm hard wood plugs, screwed with M.S. screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110mm |
| 78 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 79 | SOIL WASTE & VENT PIPES AND FITTINGS - III Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion . (i) Single socketed pipes. (DSR-2023, Rate= 377.40) 15mm dia nominal dia pipes |
| 80 | 25mm dia nominal dia pipes |
| 81 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testiang of joints complete as per direction of Engineer in Charge. Concealed work including cutting chases and making good the walls etc. 15mm dia nominal outer dia pipes |
| 82 | 20mm dia nominal outer dia pipes |
| 83 | 25mm dia nominal outer dia pipes |
| 84 | Providing & fixing CP brass bib cock of approved quality conforming to IS 8931 15mm nominal bore |
| 85 | Providing & fixing C.P. brass angle valve for basin mixer and gyser points of approved quality conforming to IS 8931 15mm nominal bore |
| 86 | Providing and fixing gun metal gate valve with wheel of approved quality(screwed end).. 25mm dia nominal bore |
| 87 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete 25 mm nominal bore |
| 88 | Supply and hoisting of Sintex or equivalent high density polyethylene seemless of piece moulded tanks and placing the same in proper position including all taxes, labour and T&P etc. for proper completion of work. Tnak should be ISI marked, Sintex or equivalent. |
| 89 | Providing and fixing gun metal gate valve with wheel of approved quality. 20 mm dia nominal bore |
| 90 | Providing and fixing PTMT pillar cock of approved quality and colour.15 mm nominal bore, 125 mm long foam flow, weighingnot less than 120 gms |
| 91 | SCHEDULE OF QUANTITIES FOR INTERNAL SEWERAGE SYSTEM - IV Supply and fixing of UPVC S.W.R. pipe type-B confirming to IS-13592 including jointing the pipes with rubber ring,lubricant and UPVC SWR cupler confirming to IS-14735. Also including excavation of treanches cutting of walls and holes and repairing the walls,floors and refilling the trenches as before but excluding supply and cost of other fIttlings such as elbow,bend,tee and y-tee including supply of al marerial labour and T&P.Required for proper completion of work.a) Pipes 80mm to 300mm diameter. 110 mm diameter |
| 92 | 160mm diameter |
| 93 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : 100mm dia. S.W. Pipe in |
| 94 | 150mm dia. S.W. Pipe in |
| 95 | Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design 100 x 150 mm. dia. |
| 96 | Constructing brick masonry House connecting chambers size 600x600x600mm with 9\\" brick work walls in cement mortar 1:6 (1 cement :6 coarse sand) RCC top slab 8 cm thick with 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20mm nominal size), foundation concrete 10 cm thick with 1:6:12 mix (1 cement :6 coarse sand :12 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with floating coat fo neat cement and making channels in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20mm nminal size) finished with a floating coat of neat cement complete as per standard design Inside size 600x600X600mm and 500mm deep including R.C.C. Cover. |
| 97 | Inside size 900x900 mmm & 1.0 meter deep including R.C.C. cover |
| 98 | Main Building cum control room (Internal Electrification) Wiring point for light with 1.5 sq.mm FR P.V.C. insulated multistrand single core Copper Conductor cable in PVC conduit with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthing wire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & ceiling rose / angle / batten holder on 3 mm thick phenolic laminated backelite sheet etc complete in all respects as directed, including matching color wash. |
| 99 | Wiring point for two ways light with 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & ceiling rose / angle / batten holder on 3 mm thick phenolic laminated backelite sheet etc complete in all respects as directed, including matching color wash |
| 100 | Wiring point for fan with 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & ceiling rose / angle / batten holder on 3 mm thick phenolic laminated backelite sheet etc complete in all respects as directed, including matching color wash |
| 101 | Wiring point for exhaust fan with 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & ceiling rose / angle / batten holder on 3 mm thick phenolic laminated backelite sheet etc complete in all respects as directed, including matching color wash |
| 102 | Wiring point for plug 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & socket etc, complete in all respect including matching colour wash. |
| 103 | Add for Invertor Wiring in wiring Point for light/Fan with 1.5 mm Cu Wire |
| 104 | Supply & wiring of submains with two number 2.5 sq.mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in 20mm dia heavy duty (2mm thick) PVC conduit with 1 Number 1.5 sq.mm. FRLSH PVC insulated 1100 V grade multistrand copper conductor cable as earth continuity wire drawn inside the conduit complete in all respect. |
| 105 | Supply & wiring of submains with two number 4 sq.mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in 20mm dia heavy duty (2mm thick) PVC conduit with 1 Number 2.5 sq.mm. FRLSH PVC insulated 1100 V grade multistrand copper conductor cable as earth continuity wire drawn inside the conduit complete in all respect. |
| 106 | Supply and wiring of submain with 4 number 10 sqmm . FRLSH PVC insulated 1100 V grade multistranded single core copper conductor cable in 32 mm dia heavy duty (2mm thick ) PVC conduit partly concealed in wall and partly laid in slab along with reinforcement befor concreting with two number 10 SWG copper earth contunity wire including colour wash etc. complete in all respects. |
| 107 | Supply & fixing of single wall bracket on matching M.D.F.E.G. board base etc. complete in all required. Cat. A |
| 108 | Supply & fixing ofrecess/Surface/Pendent mounting round 12 to 15 watt LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/Reflector and driver set complete in all respects. Cat. AAA |
| 109 | Supply and Fixing of LED Tube Light with batten suitable for up to 1X22 watt LED tube light fitting complete including tube on surface complete in all respect.1 X 22 W CAT-AAA |
| 110 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required BEE 5 Star rated-1200mm sweep |
| 111 | Supply and burying safe earthing Electorde T-19 (Hot Dip Galvanized), Length 2000 mm, outer pipe 50mm, inner pipe 25, terminal Dia 12mm ,outer G.I.pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Gavanized up to 100 mircon filled with crystalline conducative mixture (CCM) having anti corrosive & conducative property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaning capacity along with 30 cm squre C.I. frame with hinged cover & masonry housing (from electode terminal to switch board , cost of 25 x 3 G.I. strip will be extra) Make: As approved in U.P.P.W.D. & C.P.R.I. Certified |
| 112 | Supplying & Laying of 25mmx3mm G.I. Strip from earth electrode in ground as required complete in all respects. |
| 113 | Supply & fixing of two number 8 SWG G.I. wire for earthing purpose as required complete in all respects. |
| 114 | Supply and fixing of 6 Amp to 32 Amp MCB(10KA)C Curve 6 - 32 amps.Cat. A |
| 115 | Supply and fixing of 63 Amp. 4 Pole MCB (10KA) CAT A |
| 116 | Supply and fixing of surface/ flush mounting 6 way TPN distribution board with additional metal door without MCB complete in all respect, as directed at site by Engineer Incharge. CAT A |
| 117 | Supply & fixing of Crimping, solder, less, copper ton electroplated lugs of Dowel/ismail make suitable for 1.5 sqmm to 6sqmm cables, including tapping with insulating tape, etc. complete in all respects. |
| 118 | Supply and fixing of single pole MCB blanking plate CAT A |
| 119 | Supply and fixing of power plug with 20A/250 V flush type modular switch and 5 Pin 20 A/250 Volt flush type universal modular socket switch on concealed M.S. box including supply of all material, labour T & P etc required for proper completion of work. |
| 120 | Erection and testing of ceiling fan and regulator for room height upto 3.5mts. including supply of 3mm thick G.I. down rod 19mm dia duly painted, complete in all respects. |
| 121 | Erection and testing exhaust fan on the exhisting hole with suitable size of rag bolts nuts and washers etc. complete in all respects. |
| 122 | Supply & fixing of 16 gauge M.S.drum duly painted including making hole in the wall for exhaust fan and finishing properly etc. complete as required. |
| 123 | Supply & fixing hexagonal/Round G.P. Fan box of approved make made up of 1.0 mm thick ISI marked G.P. Sheet spot welded four to Eight holes of 25.4mm for pipe entry of the box. Holes should be semi-shuttered type with 0.5mm G.P. Sheet made upper & lower cover duly screwed fitted with 300mm round zink coated M.S. Bar x 12mm & brand name should be embossed. Fixing with wiring conduit laid in the R.C.C. roof before concreting alongwith supply of all material labour, T & P etc required for proper completion of the work. |
| 124 | Supply fixing of electronic fan regulator (Modular) 120-280 V. ISI marked, on the existing switch board including making connetion, required material, labour T/P etc for proper completion of work to the satisfaction of Engineer in charge of work. |
| 125 | Supply and fixing of surface/ flush mounting 6 ways V TPN distribution board with additional metal door without MCB complete in all respect, as directed at site by Engineer Incharge. CAT A |
| 126 | Supply and fixing of 160 Amp 4 pole MCCB(25 KA) Theramal Magnetic reaease Cat. A |
| 127 | Supply and laying of aluminium conducter, PVC insulated armoured, served, sheeted cable 1000 bolts grade at a depth of 750mm below ground level over a cushion of 75mm thick sand alround and protected with burnt bricks on sides and top on surface, the cable run shall be fixed on M.S. clamps etc. of suitable size. or as directed by the Engineer-Incharge, complete in all respect. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. 25 sqmm 3.5 core |
| 128 | S&F surface/flush mounting 4 ways SPN distribution board without MCB complete in all respect,as directed at site by Engineer in charge CAT A |
| 129 | PART (B): SCHEDULE ITEMS (AS PER DSR. E&M 2022) Supplying and drawing following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. 2 Pair |
| 130 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and refilling etc as required. 100 mm Dia |
| 131 | PART C - NON - SCHEDULED ITEMS (AS PER MARKET RATES ) Supply & erection of AC 230/250 Volts, 50 Hz exhaust fans including providing nuts, bolts, mounting frame and other accessories including connections etc. complete as required-Make: USHA Cat No. TURBO JET DLX 300mm sweep. |
| 132 | S/f of 10/20 pair Junction Boxes for Floors and building with Krone connectors , with connection and punching of same |
| 133 | S/f of Hexagonal fan box of 80mm depth fabricated from 20 SWG MS Sheet with 12mm round bar |
| 134 | Staff Quarter (Civil Work) Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.2.8.1All kinds of soil. |
| 135 | Earth work in cutting or in embankment in ordinary soil, excavation to be in the regular pits not exceeding 0.5m in depth and earthwork in mbankment to be in 20cm. layers, including ramming and dessing the surface to required levels & slopes & also including 1.5 lift & 30m. lead. The earth from cutting to be used in making embankment or to be deposited as spoil banks within 30m. Distance as directed by the engineer incharge (Including Royalty). & Also including cartage up to 5 Km from out side the site of work & including cost of earth, watering, dressing & compacting the soil to achieve 95% proctor density. |
| 136 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering All work up to plinth level: 1:4:8 (1 Cement: 4 coarse sand (zone-III) derived from natural sources: 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 137 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 138 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 139 | Providing and Injecting chemical emulsion for pre-constructional anti termite treatment and creating and chemical varrier under and around the coloumn pits wall, trenches, basement, excavation top surface of plinth filling junction of wall and floor along the external of the building expention joints surrounding of pipes and conduits etc complete plinth area of the building at the ground floor only shall be measured as per IS 6313 (part-II 1981) aldrine emulsifiable concrete or any other apporoved material such as hepthachlor or cholordance will be used. The rate of application 5 Lit/per sqm of chemical emulsion shall be as follows- 1- Treatment for masonary and foundation. 2- Back fill in immediate contact with foundation 7.50 Lit per sqm. 3- Treatment of top surface of plinth filling 5 Lit per sqm. 4- Treament of soil along external perimeters of building 7.50 lt/sqm. 5- Treatment of soil under appron along external perimeter 5 lit per sqm. |
| 140 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement: 1.5 coarse sand(zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). for plinth and lintels of doors and window |
| 141 | Centering and Shuttering including strutting, propping etc. and removal of form for Lintel, beams, plinth beams, girders, bressumers and cantilevers. |
| 142 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases above plinth level up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with 1:1.5:3 (1 cement: 1.5 coarse sand incuding manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 20%: 3 graded stone aggregate 20 mm nominal size including Recycled Concrete Aggregate (RCA) upto 20%) For Slab |
| 143 | Centering and Shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform |
| 144 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement: 1.5 coarse sand(zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). For Lighter Beam |
| 145 | Centering and Shuttering including strutting, propping etc. and removal of form for Lintel, beams, plinth beams, girders, bressumers and cantilevers. |
| 146 | Class-150 brick work in 1:6 (one cement and six coarse sand sand of 1.5-2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labours, T & P etc required for proper completion of the work. |
| 147 | Class-150 brick work in 1:6 (one cement and six coarse sand sand of 1.5-2.00 fineness modulus) mortar in super-structure including necessary cutting and moulding of brick work as required and also including honeycombed brick work. Thickness of wall not to be less than one brick thick wall including supply of all material labours, T & P etc required for proper completion of work. |
| 148 | Class-150 brick work in 1:6 (one cement and six coarse sand sand of 1.5-2.00 fineness modulus) mortar in super-structure including necessary cutting and moulding of brick work as required and also including honeycombed brick work. Thickness of wall not to be less than one brick thick wall including supply of all material labours, T & P etc required for proper completion of work. |
| 149 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 150 | 15mm thick plaster with cement mortar consisting of 1 part cement and 4 part of approved coarse sand including supply of all material labours, T & P etc required for proper completion of work. |
| 151 | 15mm thick plaster with cement mortar consisting of 1 part cement and 6 part of approved coarse sand including supply of all material labours, T & P etc required for proper completion of work. |
| 152 | 12mm thick plaster with cement mortar consisting of 1 part cement and 6 part of approved coarse sand including supply of all material labours, T & P etc required for proper completion of work. (Outer side) |
| 153 | Engraving lines in the plaster of outer face wall vertically and horizontally to display the surface as stone facing as directed by the Engineer-in-charge including labour and T&P etc. required for proper completion of the work. Add for extra labour to allitems of plaster. |
| 154 | 25mm thick Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing omplete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick |
| 155 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm average) thick cement mortar 1:4 (1 cement: 4 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, ncluding rubbing and polishing complete. |
| 156 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/sq.m including jointing the joints with white cement and matching pigments etc., complete. |
| 157 | 40mm thick Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 158 | Providing and fixing 40 mm wide and 4 mm thick glass strips in joints of terrazo/ cement concrete floors. 5.5cm thick and 2.2cm depth |
| 159 | Providing and laying vitrified floor tiles in Size of Tile 600x600 mm (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. |
| 160 | Providing and laying vitrified floor tiles in Size of Tile 600x600 mm (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. |
| 161 | Providing and fixing ISI marked 35mm thick flush door shutters conforming to IS : 2202 (Part I) nondecorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters, including ISI marked stainless Steel butt hinges with necessary screws. But excluding all remaining door fittings with necessary screws. |
| 162 | M.S. or Iron work of small sizes and sections such as holding down bolts, hold fast tie rods, gratings etc.(when not included in an over all rates) wrought to required from including supply of steel and its wastage etc and their fixing required for proper completion of work. Fabrication and supply & fixing of mild steel grill as per design. |
| 163 | M.S. or Iron work of small sizes and sections such as holding down bolts, hold fast tie rods, gratings etc.(when not included in an over all rates) wrought to required from including supply of steel and its wastage etc and their fixing required for proper completion of work. Fabrication of Z-section Steel window |
| 164 | M.S. or Iron work of small sizes and sections such as holding down bolts, hold fast tie rods, gratings etc.(when not included in an over all rates) wrought to required from including supply of steel and its wastage etc and their fixing required for proper completion of work. Fabrication and supply of T-iron 40x40x5mm doo/window chaukhat frame . |
| 165 | Fixing Chowkhats in existing opening including complete as per direction of Engineer in charge. (a) Door chaukhats |
| 166 | (b) Window chaukhats |
| 167 | (c) Ventilator chaukhats |
| 168 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour. New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre |
| 169 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) |
| 170 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete |
| 171 | Making drip course in sun shade or facia as per direction of Engineer inchage including supply of all material |
| 172 | Providing and fixing 150 mm bright finished floor brass door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 173 | Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete 300x16 mm |
| 174 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 150x10mm |
| 175 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : |
| 176 | Providing and laying integral cement based treatment for water proofing on horizontal surface at all depth below ground level for under ground structures as directed by Engineer-in-Charge and consisting of :(i) Ist layer of 22 mm to 25 mm thick approved and specified rough stone slab over a 25 mm thick base of cement mortar 1:3 (1 cement : 3 coarse sand) including applying of twice ( at base and top of mortar ) cement slurry @ 2.2kg/m2 (each time) mixed with water proofing compound conforming to IS:2645 in the recommended proportion over the leveling course (leveling course to be paid separately). Joints sealed and grouted with cement slurry mixed with water proofing compound.(ii) 2nd layer of 25 mm thick cement mortar 1:3 (1 cement: 3 coarse sand) mixed with water proofing compound in recommended proportions.(iii) Finishing top with stone aggregate of 10 mm to 12 mm nominal size spreading @ 8 cudm/sqm thoroughly embedded in the 2nd layer. |
| 177 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and fanufacture. |
| 178 | Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @0.75 ltr/10 sqm of approved brand and manufacture. |
| 179 | Providing & fixing 4mm thick glass panes with putty and glazing clips in steel doors, windows, clerestory windows, with : 4.0 mm thick glass panes with brad, putty, clips etc. required including supply of all materials, labours, T&P etc. complete in all respect. |
| 180 | Providing & fixing fly proof galvanized M. S wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both direction with wire of dia 0.63mm all complete with 12mmm mild steel U beading |
| 181 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) |
| 182 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc.,by applying cement slurry mixed with water proofing cement compound consisting of applying: (a) first layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm.This layer will be allowed to air cure for 4 hours. (b) Second layer of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonary with polymer mixed slurry as per SI no. -22.5 |
| 183 | Providing & laying of light cinder/coal filling under floor of toilets and other sunken roofs.as per DSR- 0370 |
| 184 | Staff Quarter (Sanitary and water suppy work) SANITARY FIXTURES & ACCESSORIES : I Providing and fixing white vitreous china pedestal type water closet ( Indian type W.C. pan ) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid. |
| 185 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require a) White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar pillar tap. |
| 186 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 187 | Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet 100 mm diameter |
| 188 | Providing and Fixing Stainless Steel grating of approved quality and colour. 125 mm diameter (M.R.) |
| 189 | Providing and fixing 8 mm dia C.P./S.S. Jet with flexible tube upto 1 meter long with S.S. triangular plate for Eureopean type W.C. of quality and make as approved by engineer-in-charge. 15mm nominal bore |
| 190 | Providing and fixing CP Brass 32 mm size Bottal Trap of approved quality & make and as per thedirection of Enginer-in-charge. |
| 191 | Providing and fixing CP Brass Single lever lelephonic wall mixture of quality & make and as per thedirection of Enginer-in-charge. 15mm dia nominal dia. |
| 192 | Providing & fixing PTMT towel rail complete with brackets fixed to wooden cleats with cp brass screws with concealed fitting arrangement of approved quality and colour. 600 mm. long towl rail length of 645 mm. width 78 mm. and effective height of 88 mm, weighing not less than 190 gms. |
| 193 | Providing and fixing PTMT Liquid soap container 109 mm wide ,125 mm high and 112 mm distance from wall of standerd shape with bracket of the same material with snap fittings of approved quality and colour weighing not less than 105 gms |
| 194 | SOIL WASTE & VENT PIPES AND FITTINGS - II Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion . (i) Single socketed pipes. (DSR-2023, Rate= 377.40) 110mm diameter |
| 195 | Supply and fixing of UPVC S.W.R. pipe type-B confirming to IS-13592 including jointing the pipes with rubber ring,lubricant and UPVC SWR cupler confirming to IS-14735. Also including excavation of treanches cutting of walls and holes and repairing the walls,floors and refilling the trenches as before but excluding supply and cost of other fIttlings such as elbow,bend,tee and y-tee including supply of al marerial labour and T&P.Required for proper completion of work. 90 mm O.D. |
| 196 | 110 mm O.D. |
| 197 | Supply and fixing of UPVC S.W.R. pipe nahni trap size 100x75,110/90 mm confirming to IS-14735 self cleaning design fixed in PCC 1:2:4 and supply and fixing of 125 mm dia heavy duty CP brass jali. |
| 198 | Supply and fixing of UPVC S.W.R. plain bend confirming to IS-14735. Size 90 mm |
| 199 | Size 110 mm |
| 200 | Supply and fixing of UPVC S.W.R. Cowel confirming to IS-14735. Size 90 mm |
| 201 | Size 110 mm |
| 202 | Supply and fixing of UPVC S.W.R. plain tee confirming to IS-14735. Size 90x90x90 mm |
| 203 | Size 110x110x110 mm |
| 204 | Supply and fixing of UPVC S.W.R. plain Y confirming to IS-14735. Size 90 mm |
| 205 | Size 110 mm |
| 206 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over PVC sheet 1m x 1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement,punning,rounding the edges and making and finishing the outlet complete. 110mm |
| 207 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50mm hard wood plugs, screwed with M.S. screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110mm |
| 208 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 209 | SOIL WASTE & VENT PIPES AND FITTINGS - III Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion . (i) Single socketed pipes. (DSR-2023, Rate= 377.40) 15mm dia nominal dia pipes |
| 210 | 25mm dia nominal dia pipes |
| 211 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testiang of joints complete as per direction of Engineer in Charge. Concealed work including cutting chases and making good the walls etc. 15mm dia nominal outer dia pipes |
| 212 | 20mm dia nominal outer dia pipes |
| 213 | 25mm dia nominal outer dia pipes |
| 214 | Providing & fixing CP brass bib cock of approved quality conforming to IS 8931 15mm nominal bore |
| 215 | Providing & fixing C.P. brass angle valve for basin mixer and gyser points of approved quality conforming to IS 8931 15mm nominal bore |
| 216 | Providing and fixing gun metal gate valve with wheel of approved quality(screwed end).. 25mm dia nominal bore |
| 217 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete 25 mm nominal bore |
| 218 | Supply and hoisting of Sintex or equivalent high density polyethylene seemless of piece moulded tanks and placing the same in proper position including all taxes, labour and T&P etc. for proper completion of work. Tnak should be ISI marked, Sintex or equivalent. |
| 219 | Providing and fixing gun metal gate valve with wheel of approved quality. 20 mm dia nominal bore |
| 220 | Providing and fixing PTMT pillar cock of approved quality and colour.15 mm nominal bore, 125 mm long foam flow, weighingnot less than 120 gms |
| 221 | SCHEDULE OF QUANTITIES FOR INTERNAL SEWERAGE SYSTEM - IV Supply and fixing of UPVC S.W.R. pipe type-B confirming to IS-13592 including jointing the pipes with rubber ring,lubricant and UPVC SWR cupler confirming to IS-14735. Also including excavation of treanches cutting of walls and holes and repairing the walls,floors and refilling the trenches as before but excluding supply and cost of other fIttlings such as elbow,bend,tee and y-tee including supply of al marerial labour and T&P.Required for proper completion of work.a) Pipes 80mm to 300mm diameter. 110 mm diameter |
| 222 | 160mm diameter |
| 223 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : 100mm dia. S.W. Pipe in |
| 224 | 150mm dia. S.W. Pipe in |
| 225 | Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design 100 x 150 mm. dia. |
| 226 | Constructing brick masonry House connecting chambers size 600x600x600mm with 9\\" brick work walls in cement mortar 1:6 (1 cement :6 coarse sand) RCC top slab 8 cm thick with 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20mm nominal size), foundation concrete 10 cm thick with 1:6:12 mix (1 cement :6 coarse sand :12 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with floating coat fo neat cement and making channels in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20mm nminal size) finished with a floating coat of neat cement complete as per standard design Inside size 600x600X600mm and 500mm deep including R.C.C. Cover. |
| 227 | Inside size 900x900 mmm & 1.0 meter deep including R.C.C. cover |
| 228 | Staff Quarter (Internal Electrification) Wiring point for light with 1.5 sq.mm FR P.V.C. insulated multistrand single core Copper Conductor cable in PVC conduit with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthing wire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & ceiling rose / angle / batten holder on 3 mm thick phenolic laminated backelite sheet etc complete in all respects as directed, including matching color wash. |
| 229 | Wiring point for two ways light with 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & ceiling rose / angle / batten holder on 3 mm thick phenolic laminated backelite sheet etc complete in all respects as directed, including matching color wash |
| 230 | Wiring point for fan with 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & ceiling rose / angle / batten holder on 3 mm thick phenolic laminated backelite sheet etc complete in all respects as directed, including matching color wash |
| 231 | Wiring point for exhaust fan with 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & ceiling rose / angle / batten holder on 3 mm thick phenolic laminated backelite sheet etc complete in all respects as directed, including matching color wash |
| 232 | Wiring point for plug 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with modular type switch & socket etc, complete in all respect including matching colour wash. |
| 233 | Add for Invertor Wiring in wiring Point for light/Fan with 1.5 mm Cu Wire |
| 234 | Supply & wiring of submains with two number 2.5 sq.mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in 20mm dia heavy duty (2mm thick) PVC conduit with 1 Number 1.5 sq.mm. FRLSH PVC insulated 1100 V grade multistrand copper conductor cable as earth continuity wire drawn inside the conduit complete in all respect. |
| 235 | Supply & wiring of submains with two number 4 sq.mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in 20mm dia heavy duty (2mm thick) PVC conduit with 1 Number 2.5 sq.mm. FRLSH PVC insulated 1100 V grade multistrand copper conductor cable as earth continuity wire drawn inside the conduit complete in all respect. |
| 236 | Supply and wiring of submain with 4 number 10 sqmm . FRLSH PVC insulated 1100 V grade multistranded single core copper conductor cable in 32 mm dia heavy duty (2mm thick ) PVC conduit partly concealed in wall and partly laid in slab along with reinforcement befor concreting with two number 10 SWG copper earth contunity wire including colour wash etc. complete in all respects. |
| 237 | Supply & fixing of single wall bracket on matching M.D.F.E.G. board base etc. complete in all required. Cat. A |
| 238 | Supply & fixing ofrecess/Surface/Pendent mounting round 12 to 15 watt LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/Reflector and driver set complete in all respects. Cat. AAA |
| 239 | Supply and Fixing of LED Tube Light with batten suitable for up to 1X22 watt LED tube light fitting complete including tube on surface complete in all respect. 1 X 22 W CAT-AAA |
| 240 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required BEE 5 Star rated-1200mm sweep |
| 241 | Supply and burying safe earthing Electorde T-19 (Hot Dip Galvanized), Length 2000 mm, outer pipe 50mm, inner pipe 25, terminal Dia 12mm ,outer G.I.pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Gavanized up to 100 mircon filled with crystalline conducative mixture (CCM) having anti corrosive & conducative property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaning capacity along with 30 cm squre C.I. frame with hinged cover & masonry housing (from electode terminal to switch board , cost of 25 x 3 G.I. strip will be extra) Make: As approved in U.P.P.W.D. & C.P.R.I. Certified |
| 242 | Supplying & Laying of 25mmx3mm G.I. Strip from earth electrode in ground as required complete in all respects. |
| 243 | Supply & fixing of two number 8 SWG G.I. wire for earthing purpose as required complete in all respects. |
| 244 | Supply and fixing of 6 Amp to 32 Amp MCB(10KA)C Curve 6 - 32 amps.Cat. A |
| 245 | Supply and fixing of 63 Amp. 4 Pole MCB (10KA) CAT A |
| 246 | Supply and fixing of surface/ flush mounting 6 way TPN distribution board with additional metal door without MCB complete in all respect, as directed at site by Engineer Incharge. CAT A |
| 247 | Supply & fixing of Crimping, solder, less, copper ton electroplated lugs of Dowel/ismail make suitable for 1.5 sqmm to 6sqmm cables, including tapping with insulating tape, etc. complete in all respects. |
| 248 | Supply and fixing of single pole MCB blanking plate CAT A |
| 249 | Supply and fixing of power plug with 20A/250 V flush type modular switch and 5 Pin 20 A/250 Volt flush type universal modular socket switch on concealed M.S. box including supply of all material, labour T & P etc required for proper completion of work. |
| 250 | Erection and testing of ceiling fan and regulator for room height upto 3.5mts. including supply of 3mm thick G.I. down rod 19mm dia duly painted, complete in all respects. |
| 251 | Erection and testing exhaust fan on the exhisting hole with suitable size of rag bolts nuts and washers etc. complete in all respects. |
| 252 | Supply & fixing of 16 gauge M.S.drum duly painted including making hole in the wall for exhaust fan and finishing properly etc. complete as required. |
| 253 | Supply & fixing hexagonal/Round G.P. Fan box of approved make made up of 1.0 mm thick ISI marked G.P. Sheet spot welded four to Eight holes of 25.4mm for pipe entry of the box. Holes should be semi-shuttered type with 0.5mm G.P. Sheet made upper & lower cover duly screwed fitted with 300mm round zink coated M.S. Bar x 12mm & brand name should be embossed. Fixing with wiring conduit laid in the R.C.C. roof before concreting alongwith supply of all material labour, T & P etc required for proper completion of the work. |
| 254 | Supply fixing of electronic fan regulator (Modular) 120-280 V. ISI marked, on the existing switch board including making connetion, required material, labour T/P etc for proper completion of work to the satisfaction of Engineer in charge of work. |
| 255 | Supply and fixing of surface/ flush mounting 6 ways V TPN distribution board with additional metal door without MCB complete in all respect, as directed at site by Engineer Incharge. CAT A |
| 256 | Supply and fixing of 160 Amp 4 pole MCCB(25 KA) Theramal Magnetic reaease Cat. A |
| 257 | Supply and laying of aluminium conducter, PVC insulated armoured, served, sheeted cable 1000 bolts grade at a depth of 750mm below ground level over a cushion of 75mm thick sand alround and protected with burnt bricks on sides and top on surface, the cable run shall be fixed on M.S. clamps etc. of suitable size. or as directed by the Engineer-Incharge, complete in all respect. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. 25 sqmm 3.5 core |
| 258 | S&F surface/flush mounting 4 ways SPN distribution board without MCB complete in all respect,as directed at site by Engineer in charge CAT A |
| 259 | PART (B): SCHEDULE ITEMS (AS PER DSR. E&M 2022) Supplying and drawing following pair 0.5 sqmm FR PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required. 2 Pair |
| 260 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and refilling etc as required. 100 mm Dia |
| 261 | PART C - NON - SCHEDULED ITEMS (AS PER MARKET RATES ) Supply & erection of AC 230/250 Volts, 50 Hz exhaust fans including providing nuts, bolts, mounting frame and other accessories including connections etc. complete as required-Make: USHA Cat No. TURBO JET DLX 300mm sweep. |
| 262 | S/f of 10/20 pair Junction Boxes for Floors and building with Krone connectors , with connection and punching of same |
| 263 | S/f of Hexagonal fan box of 80mm depth fabricated from 20 SWG MS Sheet with 12mm round bar |
| 264 | Boundary Wall Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.2.8.1All kinds of soil. |
| 265 | Providing & laying cement concrete 1:4:8 (1 cement :4 coarse sand:8 graded Stone ballast 40mm nominal size) including supply of all materials labour & T & P etc required for proper completion of the work and curing complete also including cost of formwork in foundation & floors. |
| 266 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 267 | M-150 class brick work in 1:6 cement coarse sand of 1.50 - 2.00 F.M mortar in foundation and plinth including supply of all materials, labour and T&P etc. required for the proper completion of the work. |
| 268 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement: 1.5 coarse sand(zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). For Plinth Beam |
| 269 | Centering and Shuttering including strutting, propping etc. and removal of form for Lintel, beams, plinth beams, girders, bressumers and cantilevers. |
| 270 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement: For Foundation and Footing 1:1.5:3 (1 cement: 1.5 coarse sand (zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 271 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 272 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement: For Columns 1:1.5:3 (1 cement: 1.5 coarse sand (zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 273 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 274 | M-150 class brick work in 1:6 cement coarse sand of 1.50 - 2.00 F.M mortar in super structure in one brick thick wall (230 mm) including necessary cutting and moulding of brick as required including supply of all materials, labour and T&P etc. required for the proper completion of the work. |
| 275 | 40mm thick Cast cement concrete in 1:2:4 cement, coarse sand of 2.20-3.60 FM and 20 mm graded stone grit comlete including supply of all materials, labour and T&P etc required for proper completion of work. DSR-2023 Code- 4.1.4 |
| 276 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 277 | 12 MM thick plaster in 1:6 cement coarse sand of 1.50 - 1.75 F.M mortar quality over one brick work minm thickness not to be less than 1 Cm. including supply of all materials, labour and T&P etc. required for the proper completion of the work. |
| 278 | Washed stone grit plaster on exterior walls height upto 10 metre above ground level, in two layers, under layer 12 mm cement plaster 1:4 (1 cement : 4 coarse sand ), furrowing the under layer with scratching tool, applying cement slurry on the under layer @ 2 Kg of cement per square metre, top layer 15 mm cement plaster 1:1/ 2:2 (1 cement: 1/2 coarse sand : 2 stone chipping 10 mm nominal size), in panels with groove all around as per approved pattern, including scrubbing and washing the top layer with brushes and water to expose the stone chippings ,complete as per specification and direction of Engineer-in-charge (payment for providing grooves shall be made separately). DSR 13.72 |
| 279 | Finishing wall with water proof cement paint of approved make and quality on new work with two coats to give an evenshade including preparing surface by the throughly cleaning & sand preparing and supply of all T&P & labour, required for proper completion of work and for each coat of water prooof painty after the first two coat to give even shade.DSR-2023 Code- 13.47.1 |
| 280 | Interlocking Tile Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.2.8.1All kinds of soil. |
| 281 | Providing & laying cement concrete 1:4:8 (1 cement :4 coarse sand:8 graded Stone ballast 40mm nominal size) including supply of all materials labour & T & P etc required for proper completion of the work and curing complete also including cost of formwork in foundation & floors. |
| 282 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 283 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of 80 mm thick cement concrete paver block of M-35 grade withapproved colour, design & pattern., made by table vibratory method using PU mould, laid in required colour & pattern over 50 mm thick compacted bed of sand, compacting and proper embedding/laying thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.(DSR23 S.N.16.91.1) 60 mm thick cement concrete paver blocks of M-35 grade with approved colour, design & pattern. |
| 284 | M.S. Gate Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.2.8.1All kinds of soil. |
| 285 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering All work up to plinth level: 1:4:8 (1 Cement: 4 coarse sand (zone-III) derived from natural sources: 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 286 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 287 | M-150 class brick work in 1:6 cement coarse sand of 1.50 - 2.00 F.M mortar in foundation and plinth including supply of all materials, labour and T&P etc. required for the proper completion of the work. |
| 288 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement: 1.5 coarse sand(zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). For Lighter Beam |
| 289 | Centering and Shuttering including strutting, propping etc. and removal of form for Lintel, beams, plinth beams, girders, bressumers and cantilevers. |
| 290 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement: For Foundation and Footing 1:1.5:3 (1 cement: 1.5 coarse sand (zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 291 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 292 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement: For Columns 1:1.5:3 (1 cement: 1.5 coarse sand (zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 293 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 294 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 295 | Mild Steel or iron work of small size and section such as holding down bolts hold fast tie roads gratings etc (when in included in overall rates) wrought to required form including supply of steel bolts nuts and wastages etc and its fixing required for proper completion work. |
| 296 | Painting or varnishing work in small area on wood /steel surface with one coat of ready mix priming paint &two coat of approved superior quality synthetic enamel paint including cleaning the surface all durt dust &other foreign materials sand papering &striping including supply of all materials ,labour and T&P etc. required for proper completion of work.DSR-2023 Code-13.48.3 |
| 297 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) |
| 298 | C.K. Type Drain Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.2.8.1All kinds of soil. |
| 299 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering All work up to plinth level: 1:4:8 (1 Cement: 4 coarse sand (zone-III) derived from natural sources: 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 300 | Centering and Shuttering including strutting, propping etc. and removal of form for form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 301 | Dry brick on edge flooring in required pattern with bricks of class designation 7.5 on a bed of 12 mm mud mortar, including filling joints with Jamuna sand, with common burnt clay non modular bricks.DSR-2023 Code-11.2 |
| 302 | M-150 class brick work in 1:6 cement and coarse sand in foundation and plinth including supply of all materials, labour and T&P etc. required for the proper completion of the work.. |
| 303 | Flush pointing with cement mortar consisting of 1 part cement &2 part of fine sand of 1.25 FM on brick work including supply of all material,labour and T&P etc.required for proper completion of work. |
| 304 | struck pointing with cement mortar consisting of 1 part cement &2 part of fine sand of 1.25 FM on brick work including supply of all material,labour and T&P etc.required for proper completion of work. |
| 305 | Rain Water Harwesting Excavation for depth upto 1.50 m below ground level for laying sewers, manholes, gully pits, chambers, sumps etc. in ordinary soil (earth, sand, loam and clay) including cutting or joint pits, trimming, dressing, levelling, refilling of trenches in 20.00 cm layers, watering, sand ramming the same including removal of surplus earth or other dimantled material upto a distance of 50.00 m from the centre of trenches. 0.00 to 1.50 Mt. |
| 306 | 1.50 to 3.0 Mt. |
| 307 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering All work up to plinth level: 1:4:8 (1 Cement: 4 coarse sand (zone-III) derived from natural sources: 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 308 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases above plinth level up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with 1:1.5:3 (1 cement: 1.5 coarse sand incuding manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 20%: 3 graded stone aggregate 20 mm nominal size including Recycled Concrete Aggregate (RCA) upto 20%) For Slab |
| 309 | Centering and Shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform |
| 310 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement: 4 coarse sand) |
| 311 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 312 | 15 mm cement plaster in single coat on rough side of single or half brick wall finished with a floating coat of neat cement. (1) 1 cement : 4 Coarse sand |
| 313 | Supply & Laying of 20-40mm Gauge stone ballast including all materials, labour and T&P etc. for proper completion of the work. |
| 314 | Providing M.S. foot rests including fixing in manoholes with 20x20x10 cm cement concrete blocks 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) as per standard design:(With 20x20mm square bar) |
| 315 | Providing and fixining of RCC manhole cover with frame 560mm dia of medium duty with locking arrangement etc. complete required for proper completion of the work. |
| 316 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level.. Drilling of 300mm dia bore hole manually. |
| 317 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 150 mm nominal size dia |
| 318 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. |
| 319 | Excavating trenches in all kinds of soil of required width for pipes. including excavation for sockets and dressing of sides, ramming of bottoms, including getting out the excavated soil & then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc & disposing of surplus excavated soil as directed within a lead of 50m. up to 1.50 m depth, Pipes 80 mm to 300 mm diameter |
| 320 | Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete 150 mm. dia. RCC Pipes |
| 321 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : 150 mm. dia. |
| 322 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of .class designation 7.5नोट - उक्त भवन सम्बन्धी कार्य हेतु क्षेत्र की साफ-साफ का कार्य फर्म द्वारा ही कराया जायेगा, जिसका कोई भी अतिरिक्त भुगतान नहीं किया जायेगा। Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 23, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 18, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 22 daysNov 19, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 23 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender