Tender For Addn/Altn Of Lt Distribution Network Near Konark Mess At Army Area Under Ge (A) No.1 Jodhpur.
Tender Overview
Project Description
Tender for Addn/Altn Of Lt Distribution Network Near Konark Mess At Army Area Under Ge (A) No.1 Jodhpur.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 06-Nov-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 13-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supplying, laying, jointing and testing LT 1100 volt grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, cross sectional area 240 Sq.mm, 3.5 Core including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. (3) Sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 2 | Supplying, laying, jointing and testing LT 1100 volt grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, cross sectional area 185 Sq.mm, 3.5 Core including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. (3) Sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 3 | Supplying, laying, jointing and testing LT 1100 volt grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, cross sectional area 120Sq.mm, 3.5 Core including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. (3) Sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 4 | Supplying, laying, jointing and testing LT 1100 volt grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, cross sectional area 70 Sq.mm, 3.5 Core including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. (3) Sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 5 | Supplying, laying, jointing and testing LT 1100 volt grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, cross sectional area 50 Sq.mm, 3.5 Core including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. (3) Sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 6 | Supplying, laying, jointing and testing LT 1100 volt grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, cross sectional area 35Sq.mm, 3.5 Core including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. (3) Sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 7 | Supplying, laying, jointing and testing LT 1100 volt grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, cross sectional area 16Sq.mm, 4.0 Core including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. (3) Sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 8 | Supplying, laying, jointing and testing LT 1100 volt grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, cross sectional area 10Sq.mm, 2.0 Core including fixing acessories for laying on wall/ roof/mild steel sturcture ,laid in trenches/ducts, floors etc complete all as specified and directed. (Note:- 1. Excavation & earthwork shall be measured & paid seperately under respective item of BOQ. (2) All Necessary T & P required shall be arranged by the Bidder. (3) Sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 9 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, erection of poles, struts/stays, leveling of yard etc not exceeding 10 Sqm on plan and not exceeding 1.5 m in depth and getting out in all type soil, complete all as specified and directed |
| 10 | Supply and spreading clean, dry, fine river tibba sand for under ground electric cable in two layers (8cm thick before laying of cable & 15cm thick after laying cable to a total of 23cm) including gentle punning the sand upto 18cm (total thickness) and consolidated around cable for protection of UG cable complete all as specified and directed. NOTE:- For measurement purpose punned thickness shall be considered as per clause 19.75 of SSR Part-I. |
| 11 | Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x 150 mm x 40 mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm over underground cables for protection, complete all as specified and as directed. |
| 12 | Returning, filling in including spreading, levelling, watering and well ramming in layers of not exceeding 25 cm thick after the cables & pipes etc. are laid, jointed & tested and foundations complete all as specified and directed by Engineer-in-Charge. |
| 13 | Removal of surplus excavated spoil not exceeding 50 mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 14 | M&L for Earthing complete with GI earth plate electrode 60cmX60cmX6mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to GI earth strip of size 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No-3 of SSR Part-I (2009) connected to LT panel boards all as specified and directed including excavation and connected earth work in hard/dense soil, PCC 1:3:6 type C-1(using 20 mm graded crushed stone aggregate ) as in pit, 20mm dia GI pipe medium grade for watering pipe, 40 mm dia bore GI light grade as earth strip protection pipe, 50 mm thick pre-cast RCC 1:2:4, type B-1 (using 20 mm graded crushed stone aggregate ) as in cover slab of size 300 mm x300 mm x 50mm as earth pit cover slab with & including 8 mm dia TMT bars @ 100 mm C/C both ways and with handle made out of 10 mm dia bars, funnel, strainer, charcoal and testing on completion complete all as specified and directed. Note-(i) Unit rate quoted by bidder deemed to be included excavation a(ii) Rate included for excavation & earth work in any type of strata as shown in electric plate no-3 in SSR Part-I. |
| 15 | Dismantling of unserveciable ACSR of any size,any type and size from existing pole, at various location all as directed by Engineer-in Charge complete all as specified |
| 16 | Dismantling cross arms of mild steel channel or angle section(clamo ,nut, bolt etc) care fully from site all as directed by Engineer-in Charge complete all as specified |
| 17 | Dismantling/disconnecting and taking down insulators of any size and capacity, from existing poles all as directed by Engineer-in Charge complete all as specified |
| 18 | Taking down old unserveciable L T cable of any type and any size for reuse and re laying in ground/along wall at site complete all as specified and directed. (Note: Excavation ,earth work ,sand cushioning,cable cover for cable protection,GI protection pipe shall be measured and paid separately under respective of BOQ.) |
| 19 | S& F security light junction boxes of size 240 mm x 130 mm x 110 mm fabricated /made out of 2 mm thick CRCA steel sheet junction box with shockproof,rustproof,termite resistant,weather proof,cable entry from bottom,for street light pole mounted suitable for mounting o arrangement alongwith three phase ,4 wire aluminium bus bar with insulators and including one single pole MCB 0.5 Amp rating breaking capacity 10 KA ,\\"C\\" series with cable glands .lungs including including 2.5 Sqmm three core copper cable with suitable size PVC conduit (ISI mark) from junction box to existing LED fittings & suitable arrangement for fixing of junction box such as bracket,clamp,nut & bolt etc.,complete all as specified and directed. |
| 20 | S& F for cable jointing kit suitable for 1100 volts grade cable , for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5 core/4 core ,XLPE ,armoured,aluminium conductor cable of size 120 Sqmm to 150 Sqmm complete including preparing ends of cable complete all as specified and directed. |
| 21 | S & F cable path indicators made out of thick roughly hammer dressed stone slab size 300 mm x750mm x 75 mm with applying two coat of paint,marking of voltage and size of cable,route including necessary earth work required all as directed by Engineer-in Charge complete all as specified |
| 22 | Excavation in trenches not exceeding 1.5 m wide and exceeding 1.5 m in depth upto 3.0 m for erection of poles, struts/stays, leveling of yard etc not exceeding 10 Sqm on plan and getting outhard rockl, complete all as specified and directed. |
| 23 | Supply and erection of steel tubular pole swaged type 410-SP -22 (08.50 mtr long pole) complete conforming to IS: 2713 complete with mild steel base plate, finial taper plug pole cap, mild steel bolt, nuts and screws,painting of pole externally with one coat of black bituminous paint (upto planting depth) and remain exterior portion of the pole shall be painted with two coats of aluminium paint over a coat of primer with blue & white strip upto 1.20 m height above GL and all as specified and directed with two coat of aluminum paint over a coat of red oxide primer including preparation of surface including painting of 30 cm wide bands 5 Nos with yellow and black paint of radium/photosinthetic paint alternately on external surface above base / copingr upto the height of 1.5mtr above plinth block,writing letter or figures (Block Roman) with thick synthetic enamel paint of approved shade not exceeding 5 cm height including numbering of pole, Painting coping with two coats of cement based paint etc including dismantling old and unserviciable prestressed concrete poles of any type including breaking cement concrete complete all as specified and directed.NOTE : (i) All excavation and earthwork ,PCC shall be measured and paid separately under respective items of BOQ.(ii) Manufacture's test certificate for pole shall be produced before execution work. |
| 24 | M&L for plain cement concrete 1:2:4, type B-1 (using 20 mm graded crushed stone aggregates) as in kerb/benching/ copings including weathering, slightly rounded or chamfered angle and throating including use & waste of necessary form work etc complete all as specified and directed |
| 25 | M&L for plain cement concrete 1:3:6 ,type C-2 (using 40 mm graded crushed stone aggregate) as in sub base of flooring, foundations,filling & mass concrete for fencing posts, foundation of pole ,struts & stay assembly etc complete all as specified and directed. |
| 26 | M&L for plain cement concrete 1:4:8 ,type D-2 (using 40 mm graded crushed stone aggregate) as in sub base of flooring, foundations,filling & mass concrete for fencing posts, foundation of pole ,struts & stay assembly etc complete all as specified and directed. |
| 27 | S&F of bracket made of GI pipe light grade 1.5 Mtr long of size 32/40 mm bore, bend to shape as per site requirement fixed to pole/wall with flat iron clamp size 40 x 5 mm -02Nos with suitable bolts, Nuts, washers etc including two coats of synthetic enamel aluminium paint over a coat of red oxide primer on exposed surface of mild steel surface including taking down of existing bracket complete all as specified and directed. |
| 28 | Supply and fixing smart 60 W LED street light with PDC housing, energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having top opening seperate driver compartment with IP66 protection any capacity including taking down of old unserveciable existing street light of any type complete all as specified and directed. |
| 29 | Boring of hole/ motorized auguring/drilling under road, pavement, hard standing without disturbing existing surface by trenchless technology using ultra sound technique by manual and necessary machine complete all as specified and directed by Engineer-in-Charge.Note : Pipes shall be laid minimum 1.00 mtr below/under existing road surfaces/ apron /floors etc.complete all as specified and as directed. |
| 30 | S&F for GI water tubing light grade, ISI marked, galvanised, 40 mm bore with all fittings, (such as tee, elbow, socket, union & short pieces) fixed to walls and ceiling or laid in floors,at road crossing/under concrete for cable protection including with M.S. clamps, bolts and nuts of approved size complete all as specified & directed. |
| 31 | S&F for GI water tubing light grade, ISI marked, galvanised, 50 mm bore with all fittings, (such as tee, elbow, socket, union & short pieces) fixed to walls and ceiling or laid in floors,at road crossing/under concrete for cable protection including with M.S. clamps, bolts and nuts of approved size complete all as specified & directed. |
| 32 | S&F for GI water tubing light grade, ISI marked, galvanised, 80 mm bore with all fittings, (such as tee, elbow, socket, union & short pieces) fixed to walls and ceiling or laid in floors,at road crossing/under concrete for cable protection including with M.S. clamps, bolts and nuts of approved size complete all as specified & directed. |
| 33 | S&F street light timer switch, with using digital timer switch for switching of street lights based on timing set manually on digital timer .The digital timer switchalong with suitable power contactors.MCBs incoming and outgoing circuit for support,copper cable of 16Sqmm for incoming and outgoing 40 Amps MCBs\\"C\\" series and 02 Nos support terminals to support the timer box on pole and wall ,including suitable lugs andcable glands,enclosure made of rust proof,electric shock proof ,termite proof and junction box suitable for three phase dule wether proof cabinate conforming to I P-65 protetion complete all as specified and as directed. |
| 34 | Supply, install, testing and commissioning of cubical type LT Panel board, outdoor type, gable roof, floor mounted, factory made (CPRI approved) suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of R,Y,B colour of suitable rating mounted on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made double door made outer side and minium size of panel 1.8mtrsX1.5mtrsX0.45mtrs, double door made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame made out of size not less than 100X50X5 mm.Entire panel shall have common aluminium earth bar of size 25 mm x 5 mm at the rear with two nos earth stad connection from main bus bar to switch gears with required size of bus bar and controlling wiring with 1.5 Sqmm PVC insulated copper conductor cable for metering and LED lamp.The ground clearance should be minimum 600mm .Mild steel section angle 50 mm x50 mm x 6 mm frame with front & back with louvers and air vent gasket and including of lowers on both sides including embedding the panel in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed and including danger board and including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of I P54 desired complete all as directed by Engr-in-charge & comprising of the following:- |
| 35 | (A) IN COMING |
| 36 | (a) MCCB 4 Pole, 415 Volts, breaking capacity 36 KA, 350 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -01 No |
| 37 | (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. |
| 38 | (c) Panel mounted multi function energy (voltmeter & ammeter) meter of accuracy CL-1.0 rating including CT of ratio 200/5 - 01 No |
| 39 | (B) OUT GOING |
| 40 | (a) MCCB 4 Pole, 415 Volts , breaking capacity 36 KA, 250 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -01 No. |
| 41 | (b) MCCB 4 Pole, 415 Volts, breaking capacity 25 KA, 100 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -02 Nos |
| 42 | (c) MCCB 4 Pole ,415 Volts,breaking capacity 35/36 KA, 160 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -01 No. |
| 43 | (d) MCCB 4 Pole ,415 Volts,breaking capacity 16 KA, 63 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -02 Nos. |
| 44 | Supply, install, testing and commissioning of cubical type LT Panel board, outdoor type, gable roof, floor mounted, factory made (CPRI approved) suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of R,Y,B colour of suitable rating mounted on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made double door made outer side and minium size of panel 1.20mtrsX 0.90 mtrsX0.45mtrs, double door made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame made out of size not less than 100X50X5 mm.Entire panel shall have common aluminium earth bar of size 25 mm x 5 mm at the rear with two nos earth stad connection from main bus bar to switch gears with required size of bus bar and controlling wiring with 1.5 Sqmm PVC insulated copper conductor cable for metering and LED lamp. The ground clearance should be minimum 600mm .Mild steel section angle 50 mm x50 mm x 6 mm frame with front & back with louvers and air vent gasket and including of lowers on both sides including embedding the panel in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed and including danger board and including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of I P54 desired complete all as directed by Engr-in-charge & comprising of the following:- |
| 45 | (A) IN COMING |
| 46 | (a) MCCB 4 Pole, 415 Volts, breaking capacity 35/36 KA, 250 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -01 No |
| 47 | (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. |
| 48 | (c) Panel mounted multi function energy (voltmeter & ammeter) meter of accuracy CL-1.0 rating including CT of ratio 200/5 - 01 No |
| 49 | (B) OUT GOING |
| 50 | (a) MCCB TPN, 415 Volts , breaking capacity 16 KA, 63 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -01 No. |
| 51 | (b) MCCB 4 Pole, 415 Volts, breaking capacity 35 KA, 160 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -02 Nos |
| 52 | Supply, install, testing and commissioning of cubical type LT Panel board, outdoor type, gable roof, floor mounted, factory made (CPRI approved) suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of R,Y,B colour of suitable rating mounted on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made double door made outer side and minium size of panel 1.20mtrsX 0.90 mtrsX0.45mtrs, double door made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame made out of size not less than 100X50X5 mm.Entire panel shall have common aluminium earth bar of size 25 mm x 5 mm at the rear with two nos earth stad connection from main bus bar to switch gears with required size of bus bar and controlling wiring with 1.5 Sqmm PVC insulated copper conductor cable for metering and LED lamp. The ground clearance should be minimum 600mm .Mild steel section angle 50 mm x50 mm x 6 mm frame with front & back with louvers and air vent gasket and including of lowers on both sides including embedding the panel in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed and including danger board and including internal wiring with multistranded copper conductor cable of suitable size includings lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of I P54 desired complete all as directed by Engr-in-charge & comprising of the following:- |
| 53 | (A) IN COMING |
| 54 | (a) MCCB 4 Pole, 415 Volts, breaking capacity 16 KA, 63 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -01 No |
| 55 | (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. |
| 56 | (c) Panel mounted multi function energy (voltmeter & ammeter) meter of accuracy CL-1.0 rating including CT of ratio 200/5 - 01 No |
| 57 | (B) OUT GOING |
| 58 | (a) MCB TPN, 415 Volts , breaking capacity 16 KA, 40 Amp \\"C\\" series -05 Nos. |
| 59 | Supply, install, testing and commissioning of cubical type LT Panel board, outdoor type, gable roof, floor mounted, factory made (CPRI approved) suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of R,Y,B colour of suitable rating mounted on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made double door made outer side and minium size of panel 1.50mtrsX 1.20mtrsX0.45mtrs, double door made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame made out of size not less than 100X50X5 mm.Entire panel shall have common aluminium earth bar of size 25 mm x 5 mm at the rear with two nos earth stad connection from main bus bar to switch gears with required size of bus bar and controlling wiring with 1.5 Sqmm PVC insulated copper conductor cable for metering and LED lamp. The ground clearance should be minimum 600mm .Mild steel section angle 50 mm x50 mm x 6 mm frame with front & back with louvers and air vent gasket and including of lowers on both sides including embedding the panel in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed and including danger board and including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of I P54 desired complete all as directed by Engr-in-charge & comprising of the following:- |
| 60 | (A) IN COMING |
| 61 | (a) MCCB 4 Pole, 415 Volts, breaking capacity 35/36 KA, 200 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -01 No |
| 62 | (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. |
| 63 | (c) Panel mounted multi function energy (voltmeter & ammeter) meter of accuracy CL-1.0 rating including CT of ratio 200/5 - 01 No |
| 64 | (B) OUT GOING |
| 65 | (a) MCB TPN, 415 Volts , breaking capacity 16 KA, 63 Amp, \\"C\\" series -02 Nos. |
| 66 | (b) MCCB 4 Pole, 415 Volts, breaking capacity 25 KA, 100 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -02 Nos Please Enable Macros to View BoQ information |
| 67 | (b) MCCB 4 Pole, 415 Volts, breaking capacity 25 KA, 100 Amp rating thermal magnetic adjustable release type including spreaders, nut, bolts, lugs etc (Icu=Ics=100%) -02 Nos Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 1 dayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender