Tender For Detail Estimate On Account Of Design, Supply, Installation, Testing And Commissioning Of 01 No. Of 10 Passenger Lift(Elevator) (G+2), Approved Make Otis, Schneider For Munsif Court Complex At Padum, District Zanskar
Tender Overview
Project Description
Tender for Detail Estimate On Account Of Design, Supply, Installation, Testing And Commissioning Of 01 No. Of 10 Passenger Lift(Elevator) (G+2), Approved Make Otis, Schneider For Munsif Court Complex At Padum, District Zanskar
BOQ
| Sl. No. | Item Description |
| 1 | Design,supply,installation, testing and commissioning of 680 kg,10 person MRL passenger elevator (G+2) approved make OTIS/Schneider, complete specifications in Technical specifications sheets, CAPACITY (kgs) 680kgs, 10 person,Type MRL,SPEED (mps) 1 mps,RISE (m) (G)2)building STOPS 3stops with (all opening on the same side) CONTROLLER TYPE ACD 5-MRL DRIVE VF Regenerative (Closed Loop) POWER SUPPLY 400/415 Volls (3 phase AC) OPERATION Full collective operations etc complete.CAR GROUP One car (simplex) MACHINE PM Gearless (located in shaft on top of guide rail) TRACTONMEDIA Flat Coated Steel Belt CAR FINISH Rear Mid Panel=Stainless Steel= (Hairline)Rear Corner panes=stainless steel =(Hairline) Side Panels =stainless stee= (Hairline) Front panel= Stainless = (Hairline)FALSEELUNGTYPE CD-41 FLASECELINGFINSH Stainless steel= 304 (Hairline) LANDINGDOORRSFINISH Stainless =304(Hairline) FIRE RATED DOORS Fire rating -120 mins PIT DEPTH 1400mm OVERHEAD 4200MM HOISTWAYDISMENSONS 1700mmWx1100mmDx2200mmD CARDIMENSIONS(WxD)1000mmWx1100mmDx2200mmD CAR & HOISTWAYDOOR TYPE Central opening (CO) doors DOOR OPENING (WxH) MM 700x2000mmD DOOR OPERATOR DC Door Operator COP COP for stops=12 (950mm)SS=4(Hairline) |
| 2 | SITC of 30 KVA fully automatic oil-cooled servo voltage regulator, approved makes servokon/AE/Brentford Electric SITC of 30KVA Servo Voltage Regulator filled with recommeded oil up to full capacity TYPE= Fully Automatic Servo Voltage Rating =30 -KVA input Voltage Range (Phase To Phase )= 250-460 V Output Voltage Range (Phase To Phase )=415+1% Output Wave form= True To Input input Frequency =45-55Hz Response Time=10Msec Correction Speed=25-65V/Sec Correction Method= stop less correction cooling =oil Efficiency=Better Than 98% Control Circuit =Fully Automatic lc Based Solid Stat,Operation Automatic Suitability = suitable for 3-phase, Unbalanced supply,unbalanced load operating Temperature Ambient=15 oc to 45 oc above ADDITIONAL FEATURES=i)single phase prevention system.iv ) phase sequence change protection .v) earth fault protection vi) high grade CRGO lamination,vii) simple rugged construction, viii) 99.9% pure copper ix)high efficiency x) Negligible wave form and power factor distortion xi) smooth and stepless voltage control |
| 3 | MAINTENANCE -free electrolytic earthing system including pit excavation copper electrodes backfilling and accessories (02 nos specified in the source , long life maintenance free electrolytic earthing system with 10 feet vertical k type copper not less than 2\\" (50.8mm) ID and not less 0.08\\" (2.03mm) wall thickness which does not require manual addition of water.The system should be corrosion resistant pre--filled with hygroscopic powder and provided with suitable breathing and laching ports at the ends.Rated for high fault currents basbar rated for 10 KA, fault current bus bar connections type as \\"Terraweld \\" to with hold temerature of 7000 C,The earthing port shall be designed and supplied with poly plastic cover non conductive, environment friendly and lockable the job includes Pit digging,instalation of the rods, filling earth, levelling and disposal etc. |
| 4 | Providing/laying Electric Wiring & Lighting in lift well, switches, conduits and socket outlets, approved makes Havells/Polycab/KEL Providing/laying 20 sq.mm 1100V, 4-core copper armoured cable from main panel to machine-room panel, including conduits, fasteners and terminations Source quantity 70 m, no separate rate amount shown. light points shall be provided in the lift well at a space not exceeding 3mm.All the light point shall have control with proper switches and conduits.Sockets out lets may also be provide at a suitable place for use by the maintenance staff above the ground floor landing complete.light point shall have control with proper switches and conduits. Socket outlets may also be provided at a suitable place for use by the maintenance staff abov the ground floor landing 20MM,1100Volt, 4-coreamoured cable with copper conductor from main panel in the control room to the Machine room panel fixing with proper PVC conduct brackets,/fasteners etc and lugs/ thimbling. etc. |
| 5 | SITC of Factory-built electrical LT control panel including MCCBs, bus bars, metering and accessories; approved makes L&T/Schneider/Siemens b5. SITC of Electric Control Panel. LT CONTROL PANEL:Fabrication,supplying ,instalations,Testing and commissioning of dust, damp and vermin proof free, floor mounted with base channel,indoor type factory built sheet steel enclosed modular construction panel,suitable for operation on 415+ 10% volts SOHz AC 3phase 4 wire system fabricated out of suitable sized square tubular sections and covered with CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plastes i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade. All the MCCB up to 250 Amp shall have thermal release with adjustable over load,short circute & earth fault protection, Bus bar rating 200A Take Bus-Bar Density :0.8A/mm2incoming 01) 100A 4P changeover switch =01Nos 02) 100A 38KA, four pole MCCB=01 No 03) 100A TPN ALU Bus bnar size of bus bar (30mmx6mm)=01 set04) Indication lights=01 set 05) Digital voltmeter (0-500V) for input and output, selector switch to read input/output voltage in each phase =01 No06) Digital ammeter (0-100A)=01 No 07) CT for ammeter 100/5A ratio frequency metet=01 set 08) Selector switchs =01 set out going 09) 40A, 26KA, four pole MCCB =04 No. |
| 6 | Comprehensive maintenance for 3 years following expiry of 12-month warranty including OEM spare parts to maintain fully operational elevator comprehensive Maintenance contract of carrying out repairs and providing/fitting of OEM spare parts to keep the elevator in fully operational condition for a period of 3 years after expiry of 12 months warranty period complete. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender