Tender For 08 Mld Stp Ramganj Devpura Electrical, Mechnical And Instrumentation Works.
Tender Value
1 Crore
Estimated cost
Bid Submission
12 Nov 2026
19 days left
EMD
2 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bundi → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for 08 Mld Stp Ramganj Devpura Electrical, Mechnical And Instrumentation Works.
BOQ
| Sl. No. | Item Description |
| 1 | A. Electrical & Instrumentation Works |
| 2 | Electromagnetic Flow MeterProviding, installation, testing and commissioning of Electromagnetic Flow Meter etc. including all materials (excluding CI/DI fittings) and making connection with existing pipeline required for Electromagnetic Flow Meter including cutting the existing pipe line etc. complete in all respect as per technical specification and as per direction of Engineer.EMF250 for DN 250 mm |
| 3 | ULTRASONIC DIFFERENTIAL LEVEL TRANSMITTERProviding, installation, testing and commissioning of ULTRASONIC DIFFERENTIAL LEVEL TRANSMITTER: Principle : Time of Flight / Sensor MOC PP / Process Connection 1 1/2 inch BSP or 2 inch BSP Threaded type / Power Supply: 24 V DC / Output: 4- 20 mA / Display: Integral display for programming and Display Reading / IP 66 and as per direction of Engineer |
| 4 | Ultrasonic Level TransmitterProviding, Installation, Testing and Commissioning of Ultrasonic Level Transmitter : Principle : Time of Flight / Sensor MOC PP / Power Supply: 24 V DC / Output: 4- 20mA / Display: Integral display for programming and Display Reading / IP 66/ Accuracy ±1%0-8 mtr. |
| 5 | Pressure GaugeProviding, installation, testing and commissioning of Diaphragm Type Pressure Gauges Dial size 150 mm glycerine filled shatterproof glass, Over range protection: 125% of maximum pressure, Material of sensor and other wetted parts: SS type 316, Housing material: Die cast aluminium |
| 6 | Dissolved Oxygen AnalyserDissolved Oxygen Analyser : Measuring range: 0 to 20mg/l, Optical fluorescence technology , Membrane free operation ;Accuracy:0.01mg/l or +/-1% of measured value ; With digital transmitter having output: 4-20mA HART, IP66/67 Protection |
| 7 | Level SwitchProviding, installation, testing and commissioning of Level Switch (Conductivity) Conductivity Probes, Probe insulation: Teflon, Probe head protection class: IP 65 of IS 13947 Part I, Probe head housing material: AluminumRigid for lengths of up to 3 Mtr. |
| 8 | Ultrasonic Open Channel Flow MeterProviding, Installation, Testing and Commissioning of Ultrasonic Open Channel Flow Meter (Upto 5 metre Head rise): Principle : Time of Flight / Sensor MOC PP / Power Supply: 24 V DC / Output: 4-20mA / Display: Integral display for programming and Display Reading / IP 66/ Accuracy ±1% |
| 9 | PLC and SCADA PanelDesign, Manufacture, Supply, Installation, Testing and Commissioning of Indoor type PLC Panel of size approx. 1000 mm X 600 mm X 2000mm (LBH) , Fabricated out of min. 2 mm thick CRCA sheet complete with latest configuration, necessary programming software for PLC & SCADA and comprising of all accessories not limited to the following:-Programmable Logic Controller (PLC) with Dual Hot Redundant CPU, Power supply, Communication Module, IO & Processor rack (Standard DC), Back up Interface/Expansion Module, Rack (Backplane) 10 slots for IO and Processor. SCADA software shall have facility VPN, OPC, Smart Client, Web Enabled, Automation Report Generation, Archiving, Treands, Data Logging, etc.DI 118 No.DO 114 No.AI 24 No.AO 12 No.MCB 16A DP 2 No.MCB 6A DP 6 No.SMPS 100-240VAC/ 4.5A / 24 VDC 1 No.Selector Switch (Auto/Manual) & Local / Remote 2 No.Control Relays 1 LotAnnunciator with 24 Windows NO to NC TypeMicroprocessor Based, Window Size 75*42mm,110VAC, with 1 No.Electronic Hooter 1 No.Control Transformer 200VA 1 No.Emergency STOP Push Button 1 No.Panel Cooling Fan & Filter 2 No.Panel Light with Door Switch, 7W 1 No.Control Indication Lamp for 24VDC, 220VAC 3 No.Push Button 3 No.Power Wiring+Control Wiring + Control TB/ Fuse2A,TB etc 1 LotPanel Hardware, lugs, terminations, ferruls,name plate Ect. 1 LotUTILITY SOCKET 16A, 3 PIN 2 No.HMI Display 15 Inch, Colour 1 No.Isolators Dual Output, 24VDC 1 LotEthernet Switch ( Managed) 2 No.Operator Station including, Core i5 processor, 8GB RAM, 1TB SSD, DVD RW Drive, RS-232/485/RJ45 Port, 1 Parallel Port, 4 nos. USBPort, 2x Ethernet Cards, Keyboard, Opticalmouse, 32'' LED monitor, Latest windowsprofessional, Anti Virous, etc. 2 No.Engineering Station including, Core i7processor, 8 GB RAM, 1TB SSD, DVD RWDrive, RS-232/485/RJ45 Port, 1 Parallel Port, 4nos. USB Port, 2x Ethernet Cards, Keyboard,Optical mouse, 32'' LED monitor, Latest windowsprofessional, Anti Virous, etc. 2 No.Run Time & Development Programming andTroubleshooting software for PLC, HMI, SCADA,VPN, Web Client - OWS 1 No.Black and white, A4 Size Lazer Printer , copier,Scan.Hi-Speed USB 2.0 port; built-in Fast Ethernet 2 No.10/100Base-TX network port; built-in WiFi802.11b/g/nOnline UPS 3 KVA with 60 min Backup time. |
| 10 | UPS SYSTEMProviding, installation, testing and commissioning of ONLINE UPS SYSTEM, Single Phase 230 V, 50 Hz with 2 hour backup SMF battery bank as per specification5 KVA |
| 11 | Compact RTUCompact RTU complete with DI, DO, AI and modbus communication ports and power supply. // Compact RTU for variable power supply using batteries, rechargeable batteries, solar or 10.8 V DC to 28.8 V DC with integrated modem; connection to control center via Tele Control Basic, DNP3, IEC60870-5-104 and Communcation protocols, on-board I/O (8 DI, 4 DQ, 4 AI), configuration and diagnostics per web interface, RJ45 port, mobile communication antenna (GSM/UMTS), Mini SIM card, with adapter Micro SIM card also, GPRS (Multi-slot Class 10), 35 mm DIN rail mounting, TCP/IP, DNP 3, Open VPN-Client. Panel Enclosure for Compact RTU Location, wall/floor mounted along with wiring and related accessories and arrangement of mounting of RTU, Modem and having IP-5X Protection. Panels shall be self-fabricate type only with Canopy. |
| 12 | Junction BoxP & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two coats of red oxide and with earthing terminal of following sizes (nominal size) in recessed/surface as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR1.2 mm thick M. S. Sheet boxes250mm x 300mm x 100mm |
| 13 | copper conductorSupplying and drawing PVC insulated & sheathed solid/ stranded copper conductor multi core control cable ISI marked (IS:1554) of 1.1 kV grade of approved make as per chapter E11,in existing surface or recessed conduit/ casing capping including making connections etc. as required.1.5 sq. mm. armoured |
| 14 | 6 Core |
| 15 | 12 Core |
| 16 | copper conductorProviding & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR1.5 sq.mm |
| 17 | 2 core |
| 18 | 6 core |
| 19 | Multi Core copper conductoSupply and laying PVC Insulated and PVC Round Sheathed Multi Core copper conductor (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 20 | 2.5 sq.mm x 3 core |
| 21 | end termination with heavy duty Copper lugsSupplying and making end termination with heavy duty Copper lugs ( ANY type ) confirming to IS 8337 -1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 22 | 1.5 Sq.mm |
| 23 | 2.5 Sq.mm |
| 24 | LED Street LightProviding & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current <750mA. The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 25 | LED Street Light fixture with Minimum lumen output 11225 lm |
| 26 | LED flood lightProviding & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff@>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR |
| 27 | High Power LED Flood Light Minimum lumen output 12400 lm |
| 28 | Outdoor Light PoleSupply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular crosssections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 29 | 7 Mtr. |
| 30 | Fuse BoxProviding and fixing of fuse box size 250(H) x 200(W) x 150(D) mm fabricated of 1.6mm MS sheet with hinged cover, dust and vermin proof, rubber gasket, locking arrangement, duly holded with 2 nos pole clamps of 20 mm x 3 mm flat with nut and bolts, complete with anticorrosive treatment, finished with two coat of approved enamel paint. The box shall be provided with 2 / 4 nos copper bus bar 125 x 20 x 3 mm with brass screws suitable supports,earth terminal, inter connection, knock outs for 20 / 25 mm cable gland, 1 no. 6 Amp MCB complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 31 | B Mechanical Works |
| 32 | Inlet Chamber of Pumping stationManual Suice Gate - Repair works |
| 33 | Coarse Screen channelMechanical Coarse screen (depth aprrox. 9m and width 900mm), motor and panel- Repair works |
| 34 | Distribution chamberDistribution chamber-Manual Suice Gate - Repair works |
| 35 | Wet WellWet Well-Manual Suice Gate - Repair works |
| 36 | Wet Well PumpsSupply delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Non clog submersible pumping set of 2% Ni CI Cascading, Impeller CF 8M, ,Shaft SS 410,mechanical seal with 10M Power & Control cable , 5M Galvanized Chain,,10M, 50mm MS galvanized Guide pipe, Duck Foot Bend, with Guide wire SS 304 etc. complete with all respect as per specification-Replace |
| 37 | Replace 33.5Kw |
| 38 | Replace 18.5Kw |
| 39 | Replace 18.5Kw |
| 40 | Replace 33.5Kw |
| 41 | Replace 45Kw |
| 42 | Valves at Individual deliveryKnife gate valves and NRV- Service of sizes upto 400mm |
| 43 | Primary Treatement Unit |
| 44 | Stiling chamberStiling chambar gate jam (50mm x 500m)- Repair works |
| 45 | Fine Screen Mechanical Fine screen (depth aprrox. 1.5m and width 700mm) and panel- Repair works |
| 46 | D/S gate jamFine Screen D/S gate jam (500mm x 500mm) - Repair Works |
| 47 | Grit mechanismOrganic pump not working- Replace works |
| 48 | Secondary Treatement |
| 49 | SBR BasinsSBR inlet gate actuator not working- Replace |
| 50 | SBR BasinsRAS & SAS PUMP- Repair works |
| 51 | SBR BasinsActuator for RAS and SAS Valves -Replace |
| 52 | Outlet gates- Repair works |
| 53 | SBR BasinsAir blower pipe at SBR platform and also need paint- Repair works |
| 54 | Sludge Handling and Other Units |
| 55 | CentrifugeCentrifuge requires - Repair and service |
| 56 | Centrifuge1 motor of centrifuge not working- Repair |
| 57 | Poly dozing system1 poly dozing tank agitator- Repair |
| 58 | Poly dozing systemPoly dozing pump- Repair |
| 59 | Chlorination RoomChlorine tonner EOT - Repair |
| 60 | Service water PumpService water pump from Over head tank- replacement |
| 61 | Stair for service water TankMS Stair for service water Tank |
| 62 | 1 Blower water circulation pipe 1 Blower water circulation pipe & Blower gets trip- Repair works |
| 63 | Blower deliver pipe washerBlower deliver pipe washer- Replace Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 22, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 12, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysNov 13, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender