Housing Urban and Rular Development Local Bodies Closing in 5 days TDR #58149131

Tender For maintenance of Various Colonies Under Nazul Account Ii Dwarka Zone. Sh:- Reconditioning, Rectification, Repair, Supply & Replacement Of Firefighting System, Fire Alarm/Pa System And Ventilation System In Community Halls At Sector 2 Sector-

Issued by Local Bodies · Delhi, Delhi
Tender Value
87.35 Lakhs
Estimated cost
Bid Submission
28 Oct 2026
5 days left
EMD
1.74 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for maintenance of Various Colonies Under Nazul Account Ii Dwarka Zone. Sh:- Reconditioning, Rectification, Repair, Supply & Replacement Of Firefighting System, Fire Alarm/Pa System And Ventilation System In Community Halls At Sector 2 Sector-03, Bindapur Pocket-Iii, Sector 7, Sector-9, Haf Pkt Sector 13, Room And Library Sector 13 ,Dhulsiras Village, Sector-24, Village Pochanpur Adjoining Sector-23 & Haf Pocket, Sector-16B Dwarka.

BOQ

Name of Work:- M/o various colonies under nazul account II Dwarka Zone. SH:- Reconditioning, Rectification, Repair, Supply & Replacement of Firefighting System, Fire Alarm/PA System and Ventilation System in community halls at sector 2 Sector-03, Bindapur Pocket-III, Sector 7, sector-9, HAF Pkt sector 13, room and library sector 13 ,Dhulsiras Village, Sector-24, Village Pochanpur adjoining Sector-23 & HAF Pocket, Sector-16B Dwarka.
Sl. No. Item Description
1Supplying and Installation of wall mounted Electrical Starter panel of 1.6mm thick CRCA sheet constructed, dust and vermin proof, cubical type, powder coated painted of approved colour and shade with aluminium Bus Bar of suitable raitings as per CPRI valid approval and norms etc for operation on 440 Volt, 3 Phase, 50 Hz AC Supply with other accessories IP 44 Protection complete in all respects including internal wiring, labels, ferrules conforming to specification as per followings : INCOMING a) 100 Amp 3 Pole MCCB (35 KA) with netrual link -- 1 no. b) Digital Multimeter - 01 No. c) LED Indication for phase with 2 Amp SP MCB OUTGOING 3 Pole MCCB with DOL Starter with contactors and relays, accessories suitable to above motor, Push Button, ON/OFF indicator etc. with safety circuit and control wiring etc wuth necessary controls as per requirement -- 3 nos.
2Supplying and fixing 63 mm dia, 15 m long stainless steel RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required.
3Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Stainless Steel
4Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required 150 mm
5100 mm
680 mm
7Supplying and fixing single headed internal hydrant valve with instantaneous Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Stainless Steel cap and chain as required :
8Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Pendent/Upright
9Painting of pipe with two coats of enamel paint of required shade after cleaning the pipes surface of following size complete as required.200 mm
10150 mm
11100 mm
1280 mm
1365 mm
1450 mm
1540 mm
1632 mm
1725 mm
18Supplying and fixing of MS hose cabinet of size 900 mm x 600 mm x 500 mm made of 2 mm thick with 6mm thick glazed glass doors including necessary locking arrangement suitable to accommodate external hydrants, 2 nos 63mm dia synthetic hose pipe 15 m long, 1 no branch S.S. pipe with 4 nos MS angle ( 40 x 40 x 8 ) supports grouted in floor and duly coated with post office red external and white internal paint complete in all respects.
19Supplying, Fixing, Testing and Commissioning of 100 mm dia draw out connection screw type complete with nut-bolt, rubber gasket, complete, etc. as required.
20Supplying, cutting and fixing of 1500 x 1200 mm size plain glass, 4 mm thick in MS Fire Shaft doors using screw, aluminium Channel and washer etc. complete as required.
21Providing, fixing, testing & commissioning of installation 150 mm control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required :
22Checking, servicing, repairing as required, testing & commissioning of existing Cast iron double flanged non return valves including repairs of internal defective parts as required, greasing, oiling, so as to make them in proper working condition etc. complete as required.150 mm
23100 mm
2480 mm
25Overhauling, checking, reconditioning, servicing, greasing of the deisel engine driven pump set including necessary repairs of internal dective parts, alignment of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
26Overhauling, checking, reconditioning, servicing, greasing of the Electric driven Main pump including necessary repairs of internal dective parts, alignment of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode of the Main pump set to make it functional as per Delhi Fire Service requirements.
27Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairs of internal dective parts, alignment of 15 HP Jockey pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
28Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairs of internal dective parts, alignment of 10 HP Jockey pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
29Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairsof internal defective parts alignment of 7.5 HP Jockey pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
30Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairs of internal defective parts, alignment of 7.5 HP Booster pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
31Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairs of internal defective parts, alignment of 5 HP Booster pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
32Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairs of internal dective parts, alignment of 12.5 HP terrace pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
33Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairs of internal dective parts, alignment of 7.5 HP terrace pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
34Checking, repairing, reconditioning, servicing of the 7.5 HP terrace pump starter including necessary repairs of internal dective parts and re-testing & commissioning of the same complete as required.
35Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairs of internal dective parts, alignment of 1 HP Drainage pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements.
36Reconditioning, overhauling, servicing, cleaning of existing installed Hose Reel Drum including repairs/replacement of internal defective parts, greasing, oiling, tracing leakages & repairing and repair of pipe connection with GI Fittings, painting so as to make them in proper functional condition etc complete as required as per site requirement.
37Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required
38Reconditioning of the Main Electrical panel along with starter for Diesel Engine, Main Pump, Jockey pump, Booster pump, Drainage Pump, checking, servicing, the same after effecting necessary repairs/replacement of internal defective parts etc. as required i/c re-testing & commissioning etc., complete as required. The job includes to control operation of Main Electric Fire Pump, Diesel Engine Pump, Main sprinkler fire pump, Pressurization Pumps in sequence as per specification consisting of relays, timers, sensors for fault indication, complete as per specification.
39Checking, servicing, Pressure testing and refilling of 4.5 kg Co2 type Fire extinguisher complete as required.
40Checking, servicing and refilling of 6 kg Dry powder for A,B&C Class of fire ISI marked MAP 50% fire extinguisher complete as required.
41Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 + 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.2 Loop
42Supply, installatin, testing & commissioning of 16 zone microprocessor based main fire alarm panel wall mounted type fabricated out of 1.2/1.6 CRCA sheet, dust and vermin proof, powder coated, complete in all respect suitable for operation 220V AC 50 Hz, power supply and battery charger. The panel shall be ERTL/AC/CE/LPCB approved complete as required. (Make Agni)
43Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.
44Supplying, installation, testing & commissioning of heat detector operating at 54°C/57”C with rate of rise cum fixed tempreature (dual thermistor) type with mounting base complete with all connection etc. as required.
45Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required.
46Supplying, installation, testing & commissioning of addressable manual call point complete as required.
47Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
48Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
49Supplying, installation, testing & commissioning of addressable horn cum strobe ABS body complete as required.
50Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in A.B.S. box with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
51Supplying, installation, testing & commissioning of digital audio amplifier 100 Watt, operating at 240 Volt AC Supply complete as required.
52Supplying, installation, testing & commissioning of digital audio amplifier 250 Watt, operating at 240 Volt AC Supply complete as required.
53Reconditioning of existing Agni Make main fire alarm control panel of 10 Zone i/c overhauling checking, servicing, testing & commissioning of the same after effecting necessary repairs/replacement of internal defective parts viz power supply card, zone card, re-wiring i/c re-testing & commissioning etc. complete as required, operating at 24 VDC comprising of audio & visual alarm indication of Fire, continuous status indications of Health/Fire/Faulty Zones, Fire/Fault test switches, zone isolation switch with indicators and also test switch for system test, sounder alarm. Silence alarm and a switch for resetting the whole system with audio-visual indications etc as required. The Job i/c's checking the entire system tracing and removing the faults in system, denting & painting the Fire Alarm control panel complete, i/c credit for defective/unserviceable spare parts etc as reqd.
54Reconditioning of existing main fire alarm control panel of 6 Zone i/c overhauling checking, servicing, testing & commissioning of the same after effecting necessary repairs/replacement of internal defective parts viz power supply card, zone card, re-wiring i/c re-testing & commissioning etc. complete as required, operating at 24 VDC comprising of audio & visual alarm indication of Fire, continuous status indications of Health/Fire/Faulty Zones, Fire/Fault test switches, zone isolation switch with indicators and also test switch for system test, sounder alarm. Silence alarm and a switch for resetting the whole system with audio-visual indications etc as required. The Job i/c's checking the entire system tracing and removing the faults in system, denting & painting the Fire Alarm control panel complete, i/c credit for defective/unserviceable spare parts etc as reqd.
55Dismantling/ removing, checking, servicing, repairing and re-fixing existing pressurization fan unit comprising of 15 HP booster fan/blower for lift well pressurization and making them functional of to boost the air to meet the requirement as per fire norms and code of NBC 2016. Fans shall be complete including flexible connection at both ends and shall be installed using vibration isolation suspension of rubber in shear type. The job includes providing, replacing, testing and commissioning of fire proof Canvas to absorb vibration, reduce noise, and allow for movement and duly supported at regular intervals with GI Sheet and connecting with metallic flanges/piece on both the end of booster fan complete as required. The job also includes design and Fabrication of suitable sized GI sheet Jointer to fix with Fan & canvas to make it in proper working condition and providing metallic support to fan complete as required. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58149131
AUTHORITY Local Bodies
TENDER VALUE 87.35 Lakhs
LAST DATE 28-10-2026
Authority
Authority Name Delhi Development Authority
Work Description Tender for maintenance of Various Colonies Under Nazul Account Ii Dwarka Zone. Sh:- Reconditioning, Rectification, Repair, Supply & Replacement Of Firefighting System, Fire Alarm/Pa System And Ventilation System In Community Halls At Sector 2 Sector-03, Bindapur Pocket-Iii, Sector 7, Sector-9, Haf Pkt Sector 13, Room And Library Sector 13 ,Dhulsiras Village, Sector-24, Village Pochanpur Adjoining Sector-23 & Haf Pocket, Sector-16B Dwarka.
Basic Detail
Tender No 30/EE/ELD-5/DDA/2026-27
Bidding Type Tender
Location
City Delhi
State Delhi
Key Dates
Publish Date 21 Oct 2026
Submission Date 28 Oct 2026
Open Date 29 Oct 2026
Finance
Tender Value 87.35 Lakhs
Tender Fee Ref. Documents
EMD 1.74 Lakhs
Exemption Not Available
Document List
BOQ_978527.xls
c328b513-e31f-4380-bcb4-5a53527e2318.html
NIT30PDF.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 21, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 28, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 5 days
Oct 29, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 6 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_978527.xls

html

c328b513-e31f-4380-bcb4-5a53527e2318.html

pdf

NIT30PDF.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender