Defence Statutory Bodies & Commissions/Committees Closing in 9 days TDR #58148650

Tender For Repair/ Maintenance Of Lt Oh Lines, Ug Lines, Panels, Vcbs Etc At D1b Zone Under Age E/M-I Of Ge (N) Mamun

Issued by Statutory Bodies & Commissions/Committees · Pathankot, Punjab
Tender Value
33 Lakhs
Estimated cost
Bid Submission
11 Nov 2026
9 days left
EMD
66000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Pathankot → Punjab
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Repair/ Maintenance Of Lt Oh Lines, Ug Lines, Panels, Vcbs Etc At D1b Zone Under Age E/M-I Of Ge (N) Mamun

BOQ

Name of Work:- REPAIR/ MAINT OF LT OH LINES, UG LINES, PANELS, VCBs ETC AT D1B ZONE UNDER AGE E/M-I OF GE (N) MAMUN
Sl. No. Item Description
1S&F in replacement of LED street light 45 Watt, 230 volts with surge protection not less than 4 KV and 10 KV separate in the lighting housing, IP 65, Energy saving & environmental friendly long life Versatile pressure die-cast aluminium roadway luminaire with high power LEDs as light source and electronic driver fixed on pole/wall along with service bracket as per sample, clamps, nuts, bolts, and washers including making electric connection with 1.5 Sqmm multistranded twin core aluminium conductor cable PVC insulated complete all as specified and directed.
2All as per item No 1 but for LED street light 60 Watt.
3All as per item No 1 but for LED street light 90 Watt.
4All as per item No 1 but for LED flood light 90 Watt including fixing arrangements i.e . clamps, nuts, bolts and washers etc.
5All as per item No 1 but for LED flood light 120 Watt including fixing arrangements i.e . clamps, nuts, bolts and washers etc.
6Disconnecting and taking out LT cable up to 25 Sqmm 2/3.5/4 core from trenches/cable duct/through wall/pole carefully complete all as specified and directed. Note: Earth work, sand, bricks will be measured and paid separately.
7All as per item No 6 but for LT cable 35 to 70 Sqmm 3.5 core.
8All as per item No 6 but for LT cable 95 to 240 Sqmm 3.5 core.
9All as per item No 6 but for LT cable 300 to 400 Sqmm 3.5 core.
10Relaying of LT cable up to 25 Sqmm 2/3.5/4 core in same or other indicated location and testing on completion including making good all distributed wall surfaces/ flooring/tilling/road to match with existing specifications complete all as specified and directed.
11All as per item No 10 but of LT cable 35 to 70 Sqmm 3.5 core
12All as per item No 10 but of LT cable 95 to 240 Sqmm 3.5 core
13All as per item No 10 but of LT cable 300 to 400 Sqmm 3.5 core
14Supply, laying in trenches or fixing to wall/pole or passing through pipe and testing XLPE PVC insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 10 Sqmm 4 core including making good all distributed wall surfaces/ flooring/tilling/road to match with existing specifications complete all as specified and directed.
15All as per item No 14 but cable of size 16 Sqmm 2 core.
16All as per item No 14 but cable of size 10 Sqmm 2 core.
17All as per item No 14 but cable of size 16 Sqmm 4 core.
18All as per item No 14 but cable of size 25 Sqmm 3.5 core.
19All as per item No 14 but cable of size 35 Sqmm 3.5 core.
20All as per item No 14 but cable of size 50 Sqmm 3.5 core.
21All as per item No 14 but cable of size 95 Sqmm 3.5 core.
22All as per item No 14 but cable of size 150 Sqmm 3.5 core.
23All as per item No 14 but cable of size 185 Sqmm 3.5 core.
24All as per item No 14 but cable of size 240 Sqmm 3.5 core.
25M&L for Cable jointing kit for 1100 volt grade cable for outdoor termination end joint heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 16 to 35 Sqmm 3.5/4 core complete all as specified and directed.
26All as per item No 25 but for cable of size 50 to 95 Sqmm 2/3.5 core.
27All as per item No 25 but for cable of size 120 to 185 Sqmm 3.5 core.
28All as per item No 25 but for cable of size 225 to 300 Sqmm 3.5 core.
29M&L for Cable jointing kit for 1100 volt grade cable for straight through termination, heat shrinkable type with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 10 to 16 Sqmm 2/3.5/4 core.
30All as per item No 29 but for cable of size 25 to 50 Sqmm 3.5 core.
31All as per item No 29 but for cable of size 70 to 150 Sqmm 3.5 core.
32All as per item No 29 but for cable of size 185 to 240 Sqmm 3.5 core.
33All as per item No 29 but for cable of size 300 to 400 Sqmm 3.5 core.
34M&L for Galvanised Iron tubing light grade 50mm bore with fittings laid for protection of cable under road crossing/ fixed to walls or pole complete all as specified and as directed. Note: Clamps for fixing pipe, nuts, bolts washers etc shall be measured and paid for separately.
35All as per srl item No 34 but of size 40mm bore.
36All as per srl item No 34 but of size 80mm bore.
37Disconnecting, dismantling aluminium conductor of any description from LT/HT overhead lines after unbinding from insulators and removal and deposited to MES store yard or taking over credit to contractor complete all as specified and as directed.
38M&L for ACSR of LT OH line including securing with insulators using aluminium binding wire, jointing jumpers etc including all disconnected cables, jumpers with proper binding complete all as specified and as directed.
39Unbinding ACSR conductor any size from insulators of LT/HT over head line for repairs, re-stretching of ACSR conductor to achieve proper sag, re-binding to the insulators using new aluminium/GI binding wire and making all existing cable connections as required complete all as specified and as directed.
40Dismantling GI earth wire from LT/HT OH line after unbinding from pole for re-use or for shifting to MES store for taking credit to contractor complete all as specified and as directed.
41M&L for Galvanised steel earth wire of service feeder or distributor span of street light poles including binding with insulators using GI binding wire, jointing jumpers etc making connections of incoming and out going cables complete all as specified and as directed.
42Re-stretching the GI earth wire to achieve proper sag, re-binding to the insulators using new aluminium/GI binding wire after repair complete all as specified and as directed.
43Dismantling cross-arms of MS channel or angle iron etc from LT poles setting aside for re-use or removal from site complete all as specified and as directed.
44Fixing only the cross arms items with supports/ angle iron frame etc includiing nuts, bolts, washers, welding, bending, hot or cold drilling holes for insulators bolts in any size or shape complete all as specified and as directed.
45M&L for Cross arms, bracings, supports, clamps, back plates etc fabricated from structural steel sections including nuts, bolts, washers, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed, welding and inclusive of one primer coat, one under coat and one finishing coat with synthetic enamel paint complete all as specified and as directed.
46Dismantling and taking out old/unserviceable stay assembly including Stay wire and insulator and removal from site complete all as specified and as directed.
47M&L for stay assembly complete with MS stay plate of size 300x300x6mm thick, stay rod 20 mm dia, stay bow, nuts, bolts and check nuts of GI all as shown in Electrical Plate No 01 of SSR Part-I, 2009 complete all as specified and as directed. Note: Excavation, PCC, saty wire and loop type insulators will be measured and paid for separately
48M&L for galvanized stay strand of 7/4mm size complete all as specified and directed.
49Dismantling insulators of any type, any size from LT overhead lines, setting aside or removal from site complete all as specified and as directed.
50Fixing only insulators any type/size in LT overhead lines complete all as specified and as directed.
51M&L for loop type insulator large size with overall dimensions (90 x140) mm with clearance of hole 25.5 mm vitreous white brown or green complete all as specified and as directed.
52M&L for shackle type insulator porcelain, vitreous, white, brown or green insulator 100 mm height,115 mm dia, 31x5 mm GI strap,14 mm dia bolts, washers and nuts complete all as specified and as directed.
53M&L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and as directed.
54Disconnecting, dismantling and taking out old steel tubular/PCC pole any size/ length, making good all disturbed surface to match with existing and removal to a distance exc 100m but not exc 250m complete all as specified and as directed.
55Supply, erection and installation of steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long) duly painted with two coats of black bituminous paint through out, internally and externally up to planning depth, and painting remaining portion of pole with two coats of aluminium paint to the entire exposed surfaces over one coat of red oxide primer, making/painting three Nos circular strips each of 30 cm wide with one yellow and 02 Nos black colour strip with synthetic enamel paint, marking pole number with black paint complete all as specified and directed. Note : Excavation, earth work, PCC work shall be measured and paid for separately.
56Disconnecting electrically, dismantling from foundation with due care, setting aside LT feader pillar box any type any size with all accessories complete all as specified and as directed.
57Supply, installation, commissioning with making connections LT feeder pillar box, outdoor type suitable for factory fabricated made out of CRCA sheet of thickness 3.15 mm front door openable with locking arrangement with 400 amps rated aluminium bus bar suitable for 3 phase 4 wire supply system duly drilled holes, making all cable connection with proper thimbles mounted on epoxy based post insulators, MCCB 250 Amps 4 pole 415 Volt, 25 KA -01 No, MCCB 3 pole 100 Amps 16 KA- 03 Nos, MCB DP 63 Amps 03 Nos, digital multimeter showing ampare, voltage etc., feader pillar mounted on MS angle iron legs of size 40x40x6mm, 1.5 mtr long, 1.0 mtr above ground level and 0.50 mtr duly painted with two coats of synthetic enamel paint over a coat of red oxide primer embedded in PCC 1:2:4 type B1 using 20mm graded crushed stone aggregates blocks of size 0.30x0.30x0.50 mtr- 04 Nos complete all as specified and directed.
58M&L for painting complete LT panels of any size from outer side, legs etc with grey colour neamel paint, complete all as specified and directed.
59Disconnecting of all cables, repair broken doors for LT panel and bus bars by welding, fixing of new hinges and other materials as required at site, making all connection as per existing complete all as specified and directed.
60Removal of vegetation/bushes/small plants shrubs around the water/electric supply installations/ inside the valve pit etc and surface excavation not exceeding 15 cm depth leveling the ground, removing the excavated material to a distance exceeding 50 M complete all as specified and directed.
61M&L for cutting, trimming of branches along the OH conductor of LT/ HT line within 2 mtr distance along both side of line and strictly all branches in one place complete all as specified and directed.
62Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth for laying of cables/taking out of cables, foundation of poles or stays, for re-routing of cables complete all as specified and directed.
63All as per item No 62 but depth exc 1.5 mtr but not exc 3.00 mtr.
64Returning filling, in including spreading , levelling, watering and well ramming in layers not exc 25 cm each complete all as specified and directed.
65Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
66M&L for river sand filling in trenches as cushion to under ground cables 8 cm thick before laying the cable and 15 cm thick when cables are laid and tested complete all as specified and directed. Note: Only punned thickness i.e 18cm shall be measured and paid.
67M&L for Sub class ‘B’ bricks old size laid dry, flat over the cable abutting each other, length of cable equal to width of brick complete all as specified and directed.
68Relaying of old bricks obtained from Srl No 69 above that over the cable abutting each other, length of cable equal to width of brick all as required.
69M&L for cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregrate for foundation, filling as mass concrete including necessary form work complete all as specified and directed.
70M&L for cement concrete 1:3:6 type C-1 using 20 mm graded stone aggregrate for foundation of stay, filling as mass concrete including necessary form work complete all as specified and directed.
71Cleaning grass/mud in and around the earth pits after taking out earth pit cover, pouring of salt solution i.e salt and water ratio 1:5 (appx 15 ltr) to existing pit there after put on the existing pit cover on pit, restoring existing connection to the equipments complete all as specified and directed.
72S&F in replacement MCCB 4 pole 415 volts fixed type 63 Amps with braking capacity16 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
73S&F in replacement MCCB 3 pole 415 volts fixed type 100 Amps with braking capacity 25 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
74S&F in replacement MCCB 3 pole 415 volts fixed type 200 Amps with braking capacity 25 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
75S&F in replacement MCCB 4 pole 415 volts fixed type 100 Amps with braking capacity 16 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
76S&F in replacement MCCB 4 pole 415 volts fixed type 200 Amps with braking capacity 25 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
77S&F in replacement MCCB 4 pole 415 volts fixed type 200 Amps with braking capacity 36 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
78S&F in replacement MCCB 4 pole 415 volts fixed type 400 Amps with braking capacity 36 KA, thermal release adjustable from 80 to 100% & fixed magnetic release from 5 to 10 In with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
79S&F in replacement MCCB 4 pole 415 volts fixed type 630 Amps with braking capacity 36 KA, thermal release adjustable from 80 to 100% & fixed magnetic release from 5 to 10 In with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
80Supply, install, testing and commissioning in replacement of LT busbar chamber box, indoor type, made out of CRCA sheet 2.00 mm thick, CPRI approved, weather proof, dust and vermin proof, IP -43, powder coated with 8 tank process, sleeve insulated aluminium bus bar 150 Amps, 3 Phase, 4 wire 415 volts including MCCB of 100 Amps, 4 pole, 415 volts 25 KA, 50 Hz with fixed megnatic and thermal release, making connection from bus bar to cables with proper thimble single side openable with locking arrangements mounted on angle iron legs made of angle iron of size 40x40x6mm, 1.5 Mtr long, 1 mtr above ground level and 0.50 mtr embedded in PCC blocks of size 0.30x0.30x0.50 mtr - 04 Nos duly painted with two coats of synthetic enamel paint over a coat of red oxide, complete all as specified and directed.
81All as per ser item No 80 but bar of cap of bus bar 300 Amps, MCCB 200 Amps, 4 pole, 415 volts 25 KA, 50 Hz.
82M&L for painting to steel tubular pole up to 9 mtr long including cross arms without removing all accessories, preparation of old steel surfaces and painting the pole - (above coping) with 5 Nos circular strips each of 30 cm (of colour combination as directed) with synthetic enamel paint duly marked pole number in a 12 cm dia yellow circle, number writing with black synthetic paint. The remaining pole alongwith cross arms shall be painted with two coats of aluminium paint, PCC coping of pole shall be painted with one coat of cement base paint complete all as specified and directed.
83M&L for painting of PCC pole 9/11 mtr long including cross arms without removing accessories after preparation of surfaces, the pole shall be painted (above coping) with 5 Nos strips each of 30 cm (of colour combination as directed) with synthetic enamel paint duly marked pole number in a 12 cm dia yellow circle with number writing with black synthetic paint. Colour washing the remaning pole and coping by using snowcem of approved colour including painting of cross arms by applying one coat of alumn paint all as required at site or directed.
84Supply and laying synthetic rubber insulated mats 2mm thick sizes 2m x 1m suitable for electrical shock dafety for voltage upto 3.3 kv for electrical purpose confirming to I5652-2006, complete all as specified and directed.
85All as per item No 84 above but 2.5mm thick suitable for 11 KV.
86M&L for boring of holes under road, pavement hard standing by mannually or trenchless technology using ultra sound technique for laying pipe/cables complete all as specified and directed.
87S&F danger notice plate of 1.6mm thick MS sheet of size 20x15cm, vitreous enamelled white, with letters, figures and conventional skull and bones in singal red colour (as per sample), fixed with MS clamps, bolts and nuts of approved size for LT complete all as specified and directed.
88All as per item No 87 above but for HT, of size 25x20cm.
89M&L for earthing complete with GI earth plate electrode of size 60cm X 60cm and thickness not less than 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers etc and connected to and including GI strip of size 32x6 mm by means of bolts, nuts, check nuts and washers made of brass and protected by light grade 40mm dia GI pipe connected to equipments and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover 50mm thick and PCC chamber pit with PCC 1:2:4 type C2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 making test point and all connections complete all as specified & directed.
90Supply only aluminium lugs 6 to 10 Sqmm complete all as specified and directed
91Supply only aluminium cable lugs end terminals 16 Sqmm complete all as specified and directed
92Supply only aluminium cable lugs end terminals 25 to 35 Sqmm complete all as specified and directed
93Supply only aluminium cable lugs end terminals 50 to 70 Sqmm complete all as specified and directed
94Supply only aluminium cable lugs end terminals 95 Sqmm complete all as specified and directed
95Supply only aluminium cable lugs end terminals 120 to 150 Sqmm complete all as specified and directed
96Supply only aluminium lugs 240 to 300 Sqmm complete all as specified and directed
97Supply only LT OH line PVC spacers high quality for 5 wires, complete all as specified and directed
98Supply only LT OH line PVC spacers high quality for 3 wires, complete all as specified and directed
99Supply only LT OH line PVC spacers high quality for 2 wires, complete all as specified and directed
100Material and labour for construction of earth pit (excluding pit cover) as required at site and as per specification of Electrical plate No-03 of SSR part-1 complete all as specified and directed .
101Material and labour for construction of earth pit cover of size 450x450x75mm of RCC 1:2:4 type B-0 (using 12.50mm crushed stone aggregate with lifting handle complete (as per sample) and placing on earth pit complete all as specified and directed.
102Disconnecting, dismentling and taking down carefully GI strip of any size up to 32x6mm, seggregating unserviceable or serviceable parts incl removing from site or setting aside for reuse complete all as specified and as directed. .
103Fixing only GI strip obtained from site as per srl item No-88 above buried in ground upto 50 cm depth or fixed to wall etc including jointing by welding for loop earthing complete all as specified and as directed. .
104M&L for Galvanised iron strip size 32x6mm, buried in ground upto 50 cm depth/ fixed to wall with nut, bolt, saddles, insulators etc for loop earthing including welding of joints all as required at site including necessary excavation and earth work complete all as specified and directed or directed.
105S&F in replacement of heavy duty cable 1100 Volts 6 Sqmm 2 core flat PVC insulated aluminium stranded conductor served with inner sheathing of PVC tape and overall PVC sheathed for service connection complete all as specified and directed.
106S&F in replacement of heavy duty cable 1100 Volts 10 Sqmm 2 core flat PVC insulated aluminium stranded conductor served with inner sheathing of PVC tape and overall PVC sheathed for service connection complete all as specified and directed. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58148650
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 33 Lakhs
LAST DATE 11-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/ Maintenance Of Lt Oh Lines, Ug Lines, Panels, Vcbs Etc At D1b Zone Under Age E/M-I Of Ge (N) Mamun
Basic Detail
Tender No GE(N)/M-70/2026-27
Bidding Type Tender
Location
City Pathankot
State Punjab
Key Dates
Publish Date 21 Oct 2026
Submission Date 11 Nov 2026
Open Date 18 Nov 2026
Finance
Tender Value 33 Lakhs
Tender Fee 500
EMD 66000
Exemption Not Available
Document List
BOQ_891644.xls
e191f860-5312-4529-9aa6-5c469a7bb41a.html
Tender70.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 21, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 11, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 9 days
Nov 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 16 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_891644.xls

html

e191f860-5312-4529-9aa6-5c469a7bb41a.html

pdf

Tender70.pdf

pdf

Tendernotice_1.pdf

Disclaimer