Tender For Conversion Of Ht Overhead Line To Ug Cable With Allied Works In Area-I & Ii At Saugor Mil Stn
Tender Value
1.97 Crore
Estimated cost
Bid Submission
19 Nov 2026
16 days left
EMD
2.73 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Sagar → Madhya Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Conversion Of Ht Overhead Line To Ug Cable With Allied Works In Area-I & Ii At Saugor Mil Stn
BOQ
| Sl. No. | Item Description |
| 1 | Note: (i) Please refer schedule 'A' notes before quoting the tender. (ii) Amount of Schedule of credit shall be deducted off line by the department. |
| 2 | Dismantling concrete poles/struts, any size complete all as specified and directed. |
| 3 | Dismantling steel poles/struts, any size complete all as specified and directed. |
| 4 | Dismantling of ACSR Conductor complete all as specified and directed by Engr-In-Charge. |
| 5 | Dismantling stay assembly complete all as specified and directed by Engr-In-Charge. |
| 6 | Dismantling insulators any type, any size complete all as specified and directed. |
| 7 | Dismantling cross arms MS channel of angle sections etc complete all as specified and directed |
| 8 | Dismantling of Earth Wire Complete all as specified and directed by Engr-In-Charge. |
| 9 | Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc. complete all as specified and directed by Engr-in-Charge |
| 10 | Supply Laying & testing cable XLPE insulated screened pre bedded galvanized steel strip armoured electric power cable with stranded aluminium conductor 11 KV grade of size 3 Core 95 Sqmm complete all as specified and directed. |
| 11 | Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m depth for foundation, laying of cables/pipes/poles etc, and getting out in soft/ loose soil complete all as specified and directed. |
| 12 | Excavation in trenches not exceeding 1.50m wide and exceeding 1.50m but not exceeding 3.0m depth for foundation, laying of cables/pipes/poles etc, and getting out in soft/ loose soil complete all as specified and directed. |
| 13 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding of 25 cm thick in soft/loose soil complete all as specified and directed |
| 14 | Removal of surplus soils obtained from excavation to a distance not exc. 50 Mtr and depositing where directed at a level not exc. 1.5 Mtr above the starting point complete all as specified and directed. |
| 15 | Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable including spreading levelling watering and consolidation complete all as specified and directed by Engineer-in-charge. Note:-Punned thickness only shall be measured and paid separately |
| 16 | Supply and laying of typ 2 with peak, size 450mm x 180mm x 40mm unreinforced precast cable cover as the mechanical protection to cable laid in trenches flat complete all as specified and directed by Engineer-in-charge. |
| 17 | Supply, Jointing and testing outdoor type cold shrinkable End termination cable joint including all material and accessories suitable for 3 core x 95 Sqmm XLPE cable of 11000 Volts grade all as per manufacturer's recommendations complete all as specified and directed. |
| 18 | S&F Cable jointing kit for 11 KV(Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed. |
| 19 | S & F gang operated air break switch with DO fuse assembly, three poles, outdoor type, nominal system voltage 11 KV, rated voltage 12 KV, rated normal current 400 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 28 KV(rms) (ii) across the isolating distance 32 KV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 75 KV (Peak) (ii) across the isolating distance 85 KV (Peak), Rated short-time withstand current 25 KA for 3 seconds, rated peak withstand current 63 KA for climatic conditions at the site, mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed. |
| 20 | S & F in repairs gang operated air break switch with DO fuse assembly, three poles, outdoor type, nominal system voltage 11 KV, rated voltage 12 KV, rated normal current 200 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 28 KV (rms) (ii) across the isolating distance 32 KV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 75 KV (Peak) (ii) across the isolating distance 85 KV (Peak), Rated short-time withstand current 25 KA for 3 seconds, rated peak withstand current 63 KA for climatic conditions at the site, mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed. |
| 21 | M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) in foundation of PCC poles/struts as specified including necessary form work, complete all as specified & directed. |
| 22 | M&L for plain cement concrete 1:3:6 type C-2 (using 40mm graded stone aggregate) in foundation of stay assembly etc including necessary form work, complete all as specified & directed. |
| 23 | M&L for plain cement concrete 1:2:4 type B-1 (using 20mm graded stone aggregate) for coping around poles, including necessary form work finishing even and smooth without using extra cement, complete all as specified & directed. |
| 24 | Supply, erecting and fixing of steel tubular swaged pole (410 SP - 55) conforming to IS 2713 (part 1 to 3), 11 mtr long with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, including two coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with one coat of red oxide primer and two coats of aluminium paint complete all as specified and directed. (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed)Note: (a) Cost of numbering of pole shall be deemed to included in unit rate.(b) Earth work and PCC will be measured and paid for separately under respective item here-in-after.(c) The pole shall be marked with designation, manufacturer's identification and year of manufacture(d) The Contractor shall submit test certificate of pole. |
| 25 | M&L Non linear expulsion type surge arrester (lightening arrestors) confirming to IS 3070 (Part 1) having voltage rating 12 KV, rated frequency-50 HZ, Nominal discharge capacity 65 kilo amp complete with all fittings, suitable for 11KV, 3-Phase, earthed distribution system complete all as specified & directed. |
| 26 | Supply, fabricating, fixing structural mild steel channel angle iron, flat iron and brackets etc for fabrications of cross arms, bracings, supports, D-clamps, stiffeners, eye hooks, bolts, pole clamps and back plates including nuts, bolts and washers, welding bending cold, or hot doing holes for insulators bolts in any shape or size as indicated or directed and inclusive of one red oxide primer coat, one undercoat and one finishing coat of aluminium paint complete all as specified & directed.(Insulators to be measured and paid for separately) |
| 27 | Supply and fix light grade 100mm GI pipe fix complete to road,culvert, Poles etc with suitable clamp for protection of cable complete all as specified & directed & directed. Please Enable Macros to View BoQ information |
| 28 | Supply and fix light grade 100mm GI pipe fix complete to road,culvert, Poles etc with suitable clamp for protection of cable complete all as specified & directed & directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 21, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 19, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysNov 23, 2026
Bid Opening Date
Technical bids will be opened and evaluated.