Tender For Supply, Installation, Testing And Commissioning Of Apfc Panel, 11Kv Compact Switchgear, Mv Panel, Bus Duct, Earthing And Loop Earthing, Cable Laying Along With Safety Equipment And Other Allied Work At Newly Proposed Substation In Iitg C U
Tender Overview
Project Description
Tender for Supply, Installation, Testing And Commissioning Of Apfc Panel, 11Kv Compact Switchgear, Mv Panel, Bus Duct, Earthing And Loop Earthing, Cable Laying Along With Safety Equipment And Other Allied Work At Newly Proposed Substation In Iitg C Us
BOQ
| Sl. No. | Item Description |
| 1 | PART-C |
| 2 | ESTIMATE -III : ( Supply installation, testing and commissioing of APFC panel,11KV compact Switchgear, MV Panel, Bus duct, Earthing and loop earthing, Cable laying along with safety equuipment and other allied work |
| 3 | Installation of Transformer |
| 4 | Erection, Testing & Commissioning of following dry transformers including transportation from the store, loading & unloading wherever required and placement in the sub-station building including provision and connection of bus-duct, cable connection to the H.V. & L.V sides, neutral body earth connections etc. as required. |
| 5 | a) 1600 KVA, 11/0.433 kV |
| 6 | Supply & installation of APFC Panels |
| 7 | Supply of 440V automatic power factor correction panels mixed dielectric low loss type complete with MCCB as incomer of following sizes & types - |
| 8 | i) 300 KVAR (with harmonic filter) |
| 9 | Installation, testing & commissioning of 440V, automatic power factor correction panels of following sizes in cable connection at the incoming & outgoing sides, earthing etc. as directed |
| 10 | i) 300 KVAR |
| 11 | Design, manufacture, supply, installation, testing and commissioning of indoor cubicle type, floor mounted, free standing, totally enclosed, dust and vermin proof, metal clad MV panel boards of following sub-stations in sectionalised and compartmentalised construction, made of steel sheet not less than 2 mm thick with necessary stiffeners, complete with cable allays, hinged sectionalised doors, common earth-bars, necessary connections interconnection etc. as specified in Part - III of the techno-commercial bid. The MV panels for all the sub-stations shall have two sections having one incomer ACB each and different outgoing feeders as specified against the respective sub-stations and both the sections connected by one bus coupler ACB. The MV panels shall have following instrumentation / indication facilities common to all sub-stations - |
| 12 | a) Multifunction digital meter for measurement of current, voltage, KW, KWh & power factor - complete with compatible CT. |
| 13 | b) Indicating lamps (RYB) - LED type - 6 nos. - 3 nos. in each section. |
| 14 | c) Instrumentation fuse HRC type, space heaters & interior light points etc. |
| 15 | For ESS - 4C |
| 16 | a) Incomers - |
| 17 | 2500 Amps. 4 Pole Air Circuit Breaker - MDO - Microprocessor type with shunt overload, short circuit and earth fault releases - 2 nos. (one for each section) |
| 18 | b) Bus Couplers - |
| 19 | 2500 Amps. 4 Pole Air Circuit Breaker - MDO type without release - 1 no. |
| 20 | c) Bus-bars - |
| 21 | 4 nos. high conductivity, electrolytic quality aluminium bus-bars rated for 4000 A. (Current density not exceeding 130 amp. per sqcm). - 2 sets. (one for each section) |
| 22 | d) Outgoing – |
| 23 | i) 1600 A - 4 Pole ACB MDO - Microprocessor type with shunt, overload, short circuit and earth fault releases - 2 nos. (1 nos. in each section) |
| 24 | T.P. MCCBs :- |
| 25 | ii) 1000 A, 50 KA Breaking capacity with adjustable setting -4 nos. (2 no in each section) |
| 26 | ii) 630 A, 50 KA Breaking capacity with adjustable setting - 4 nos. (two in each section) |
| 27 | iii) 400 A, 35 KA Breaking capacity with adjustable setting - 4 nos. (2 nos. in each section) |
| 28 | iv) 200 A, 35 KA Breaking capacity – 2 nos. (1 no. in each section) |
| 29 | v) 100 A, 25 KA Breaking capacity – 2 nos. (1no in each section) |
| 30 | MCBs :- |
| 31 | vi) 63 A TP MCB - 2 nos. (one in each section) |
| 32 | vii) 32 A SP MCB - 2 nos. (one in each section) |
| 33 | Rate of Item No 8 ( Specification is from Sl. No. 8.01 to 8.21) |
| 34 | Supply Installation testing and commissioning of 11KV Compact switchgear consisting of two section coupled with one bus coupler 630A load break switch (SF6 insulated). Section 1 shall have 2 nos 630A load break switch & 2 nos 630A vaccum circuit breaker .Section -2 shall have 1 o 630A load break switch and 3 nos 630A CB. All the the CBs shall have O/C & earth fault protection .Details as per technical specification & SLD -11KV switch gear-type2 mAke ABB/Scheneider |
| 35 | Cable Laying |
| 36 | b) Laying of one number 11 KV grade, 240 sq.mm, 3 Core XLPE insulated cable directly underground, including excavation, refilling, sand-filling, protective brick-covering etc. all complete. |
| 37 | d) Laying of one additional number 11 KV grade, 240 sq.mm, 3 Core XLPE insulated armoured aluminium cable directly underground, including excavation, refilling, sand-covering, protective brick-covering etc. all complete. |
| 38 | e) Laying of one number 11 KV grade, 300/240 sq.mm, 3 Core XLPE cable in pipe |
| 39 | g) Laying of one number 11 KV grade, 300/240 sq.mm, 3 Core XLPE cable in open duct |
| 40 | i) Laying of 11 KV grade 3.5 Core aluminium cable of 300 sq.mm / 400 sq.mm size in open duct / trench. |
| 41 | Cable termination / Joints - |
| 42 | Supply and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories inclding lugs suitable for 11 kV grade, 3 core, 240 sq.mm XLPE aluminium conductor cable as required. |
| 43 | Supply & making straight through cable jointing of 11 kV, 240 sq.mm, 3 Core XLPE aluminium conductor cable including supply of outdoor heat shrinkable jointing kit, ferrules & all accessories. |
| 44 | Supplying and making end termination with brass compression gland and aluminium lugs for 3½ core for following size PVC insulated/ sheathed 1.1 kV grade underground cable as required. |
| 45 | i) 400 sqmm, 3½ Core |
| 46 | ii) 300 sqmm, 3½ Core |
| 47 | Supply & laying of following G.I. Pipes for road crossings including excavation / boring & repairing the road to original finish - |
| 48 | a) 100 mm dia, medium |
| 49 | a) 150 mm dia, medium |
| 50 | EARTHING AND LOOP EARTHING - |
| 51 | Earthing with G.I. earth plate 600mm x 600mm x 6 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipes, etc.(but with charcoal or coke and salt complete as required) . |
| 52 | Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connection etc. as required. |
| 53 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metrebelow ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nutbolt & spring washer spaced at 50mm) |
| 54 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I.pipe from earth electrode including connection with G.I. nut,bolt, spring, washer excavation and re-filling etc. as required. |
| 55 | Steel work welded in built up section s/framed work including cutting hoisting fixing position and applying a priming coat of approved steel primmer using structural steel etc as required |
| 56 | In stringers,treads,landing etc of staircasees including use of chequered plate whereever required all complete |
| 57 | SAFETY EQUIPMENT : |
| 58 | Supply & fixing of Carbon-di-oxide (CO2) type fire extinguisher of capacity 4.5 kg with Cylinder fully charged with all mounting bracket etc. as required. (Minimax or equivalent make) |
| 59 | Supply & fixing of Dry Powder Stored Pressure type fire extinguisher of capacity 5 kg with Cylinder fully charged with all mounting bracket etc. as required (Cease fire / Minimax brand) |
| 60 | Supply of G.I. fire buckets of 10 litres capacity made of 20 SWG sheet painted red on external surface and white on internal surface inscribing “FIRE” on the external surface and mounting the same on brackets stand including providing of brackets stand and filling the buckets with sand, as required - 6 nos. brackets per stand. |
| 61 | Supply of rubber gloves (best quality) of 22 kV grade in compliance with relevant IS specification. |
| 62 | Supply of rubber mat chequered on top surface black in colour nonskidding type, plain border of 12mm thick & 1 m width to withstand 11 kV in compliance with relevant IS specification. |
| 63 | Supply & installation of 11KV Danger Plate Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 12 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender