Power Government Departments Closing in 6 days TDR #58114441

Tender For Construction Of Block Drug Warehouse With Vaccination Store Point At Ghat (Gf+1F) By Way Of Dismantling Of Old Dilapidated Bmo Quarter At Ghat (Electrification Work).

Issued by Government Departments · Doda, Jammu and Kashmir
Tender Value
12 Lakhs
Estimated cost
Bid Submission
28 Oct 2026
6 days left
EMD
24000
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Doda → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction Of Block Drug Warehouse With Vaccination Store Point At Ghat (Gf+1F) By Way Of Dismantling Of Old Dilapidated Bmo Quarter At Ghat (Electrification Work).

BOQ

Name of Work:- Construction of Block Drug Warehouse with Vaccination Store point at Ghat (GF+1F) by way of dismantling of old dilapidated BMO Quarter at Ghat (Electrification Work).
Sl. No. Item Description
1Construction of Block Drug Warehouse with Vaccination Store point at Ghat (GF+1F) by way of dismantling of old dilapidated BMO Quarter at Ghat (Electrification Work). Note:-(The material /equipments mentioned in the BOQ must be of standard makes and meet the latest standard of quality.All the material shall be checked and verified by the Engineer in charge before execution or installation)
2Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group-A
3Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
41 x 1.5 sq. mm
5Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
62 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
72 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
82 X 4 sq. mm + 1 X 4 sq. mm earth wire
92 X 6 sq. mm + 1 X 6 sq. mm earth wire
10Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
11Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as require
125/6 A switch
1315/16 A switch
143/5pin 5/6 A socket outlet
156 pin 15/16 A socket outlet
16Bell push
17Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.
183 Module (100mmX75mm)
196 Module (200mmX75mm)
208 Module (125mmX125mm)
2112 Module (200mmX150mm)
22Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
23Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
24Supply and fixing of concealed metal box 3\\"
25Supply and fixing of metal junction box 4\\"
26Supply and fixing of light indicator
27Supply and fixing PVC batten/angle holder including connections etc. as required
28Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
29Providing and fixing M.S. Fan clamps of 16 mm dia M.S. bar, bent to shape with Hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete
30)Providing and fixing circular/Hexagonal G.I. Box for ceiling fan clamps, of internal dia 140 mm, 73 mm height, top LID of 1.5 mm thick G.I. sheet with its top surface hacked for proper bonding, top LID shall be screwed into the G.I. box by means of 3.3 mm dia rounded screws, one lock at the corners. Clamps shall be made of 12 mm dia M.S. bar bent to shap as per standard drawing.
31Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%,suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
321200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
33Supply,Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
34300 mm Sweep (Metallic)
35Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching)
368-10 Watt
37LED Batten light (System lumen efficacy ≥105 85%, Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
3818-22 Watt
39Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Origina Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only
401.5 TR with 5 Star BEE Rating
411.5 TR with 3 Star BEE Rating (Hot and Cold)
42Musical Call Bell
43Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
444way (4 + 12), Double door
45Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
466way Double door
47Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
48Four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required 100A
49Single pole and neutral
50Single Pole
51Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. (but without charcoal/ coke and salt ) as required.
52Providing and fixing 25 mmX 5 mm G.I strrip on surface or in recessfor connections as required
53SITC of wall/free standing floor mounted dust and vermin proof compartmentalized cubical panel for electrical Works, made out of CRCA sheet. Other parameters required as per point(a) Thickness of sheet shall not be less than 1.6 mm up to 600 mm length/width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartment shaving bolted type doors with/without detachable extension type structure(b) Panel shall be duly treated for derusting in 7 tank process with de phosphating and with powder coating of minimum 70 microns on both side of panel in desired shade The panel having PU/Neoprene rubber gasket of not less than 3mm thickness, required hardware, separate detachable gland plate M.S. base channel (min 75mm), hinged door with locking arrangement for equipment/switchgear(c) Interconnection between bus bar and switch gears/cable shall be rigidly supported and made out by flexible copper wires (upto 125 amp) and by solid bus bar (> 125)(d) Only outer area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge.
54Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (Thermal Magnetic type, Adjustable type)
55100 Amp,30KA,FP MCCB ICU=100% ICS
56ON Load Change Over Switch FP 100 Amp (Front Operated)
57Aluminium Bus Bar 200Amp set of 4 strips 18\\"
58Aluminium Bus Bar 300Amp set of 4 strips 18\\"
59Digital Metering Devices,comprising of Voltmeter ,Ammeter,Selector Switch,Indicating Lamp,CT etc.
60Inverter ( Sine Wave ) 200VA, With two LI-Ion Tubular Batteries of 200Ah each Including racks,cover etc
61Supply Installation Testing and commissioning of Standard Medical Deep Freezer for (-15 to -25 ) 200 Ltr
62Supply Installation ,Testing and Commissioning of Standard Medical ILR 150Ltr
63Supply and Laying of PVC insulated and PVC sheathed/XLPE Aluminium power cable of 1.1KV grade of following size on surfaces/direct in ground including excavation, sand cushioning protective covering and refilling the trench etc as required (Armoured cable )
6450 Sqmm 3.5 Core Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58114441
AUTHORITY Government Departments
TENDER VALUE 12 Lakhs
LAST DATE 28-10-2026
Authority
Authority Name Power Development Department
Work Description Tender for Construction Of Block Drug Warehouse With Vaccination Store Point At Ghat (Gf+1F) By Way Of Dismantling Of Old Dilapidated Bmo Quarter At Ghat (Electrification Work).
Basic Detail
Tender No ED Doda/JPDCL/73 of 2026-27
Bidding Type Tender
Location
City Doda
State Jammu and Kashmir
Key Dates
Publish Date 19 Oct 2026
Submission Date 28 Oct 2026
Open Date 30 Oct 2026
Finance
Tender Value 12 Lakhs
Tender Fee 1000
EMD 24000
Exemption Not Available
Document List
401ad6b2-74dc-46d2-85da-99db984524e7.html
BOQ_1112953.xls
Tendernotice_1.pdf
Tendernotice_2.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 19, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 28, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 6 days
Oct 30, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 8 days

Tender Documents

Download All (ZIP) ↓
html

401ad6b2-74dc-46d2-85da-99db984524e7.html

xls

BOQ_1112953.xls

pdf

Tendernotice_1.pdf

pdf

Tendernotice_2.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender