Tender for Replacement Of The Existing Damaged Panel Board At Administration Block

BOQ

Name of Work:- Replacement of the existing damaged panel board at Administration Block
Sl. No. Item Description
12.10.1Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
21.14.1Wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2x1.5 sq.mm + 1x1.5 sq.mm earth wire
31.14.2Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
41.14.3Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
51.14.4Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
61.17.30Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
71.21.1Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
81.21.2Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
91.31Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
101.32Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
111.56Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings).
122.10.4Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
132.11Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
142.13.1Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
152.15.2Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
162.12.1Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
172.14.2Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
182.13.3Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps
192.15.3Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
202.16Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required.
212.3.4Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)16 way, Double door
222.2.18Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 400 Amp, 50 KA, 4 pole
232.2.17Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 250 Amp, 50 KA
242.2.15Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 200 Amp, 36 KA
254.6.7Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 600mm width x 50 mm depth x 2.0 mm thickness
265.6Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
279.1.32Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
289.1.35Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 35 sq. mm (32mm)
299.1.33Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
309.1.34Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
319.1.23Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
329.1.27Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
3390.11.1.11Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper/brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall, making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
3490.11.1.15Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall, making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/RCCB/RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
3590.14.1.1Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
3690.14.2.1Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
3790.14.3.2Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
3890.14.5Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
3990.14.6Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
4090.14.7Supply and providing copper earth bus in the panel board
4190.14.10.10Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 16A-100A, 35/36 kA (Ics=100% Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
4290.16.1.4Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor (8 SWG)
4390.12.5.31Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME/STONE WARE/GI/DWC pipe as required.3.5 core 95 sq mm
4490.12.7.31Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages, colour washing etc. as required.3.5 core 95 sq mm
4590.6.6.4Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.6 sq mm
46OD256732/2025-2026Dismantling the existing cable of size up to 35 Sq.mm and reconnecting to the newly installed DB
47OD256754/2025-2026Providing and fixing 20 mm X 3 mm copper strip on surface or in recess for connections etc. as required
48OD258076/2025-2026Supplying and providing following size of electrical grade rubber mat to site location, 1000 mm X 2000 mm X 12 mm. etc completed
491.17.12Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
501.17.21Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
511.17.3Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
52OD263863/2025-2026Cost for dismantle the existing Panel board and related AUG cable, And returned to the electrical store etc.
53OD263864/2025-2026Dismantling Damaged MCCBs (250A-400A) in the existing panel board and fabricate the panel for fixing new one.Dismantled item should be return to the electrical room.
54OD263865/2025-2026Dismantling the damaged wiring installations and its accessories and the dismantled materials should be returned to the Electrical store.
55OD263866/2025-2026Labour charges for dismantling the old DB / Main switch and to connect the cable to newly installed DB. And return the dismantled material to the electrical store
56OD263873/2025-2026Dismantling of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size from wall surface as required. Up to 150 sq. mm.(Dismantling two no's end termination also)
57OD263874/2025-2026Labour cost for laying and joining/connecting AUG cable appropriate size (departmental supply) including transportation
58OD275724/2025-2026Providing and fixing following rating 4 Pole On - Load change over switch and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 400 A
59OD276145/2025-2026Supplying and fixing FP sheet steel enclosure on surface/ recess along with 40/63 amps 415 volts FP isolator. Complete with connections, testing and commissioning etc. as required.
60OD277177/2025-2026Providing and fixing approved quality self-adhesive vinyl sticker for panel board, DB etc. (Rate/Sq.cm) Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58112993
AUTHORITY Boards / Undertakings / PSU
TENDER VALUE 5.76 Lakhs
LAST DATE 28-10-2026
Authority
Authority Name University Of Calicut
Work Description Tender for Replacement Of The Existing Damaged Panel Board At Administration Block
Basic Detail
Tender No D3/154770/E-Tender No.22/2026-27
Bidding Type Tender
Location
City Malappuram
State Kerala
Key Dates
Publish Date 17 Oct 2026
Submission Date 28 Oct 2026
Open Date 31 Oct 2026
Finance
Tender Value 5.76 Lakhs
Tender Fee 1416
EMD 14409
Exemption Not Available
Document List
84d19c4a-d1bd-4595-9d85-d8d27bbc68e0.html
BOQ_1497901.xls
Tendernotice_1.pdf
Tender_AdBlock.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 17, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 28, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 8 days
Oct 31, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 11 days

Tender Documents

Download All (ZIP) ↓
html

84d19c4a-d1bd-4595-9d85-d8d27bbc68e0.html

xls

BOQ_1497901.xls

pdf

Tendernotice_1.pdf

pdf

Tender_AdBlock.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender