Tender For Special Repair For Conversion Of Lt Over Head Electric Lines To Ug Cable And Connected Items In Cwe Office And Colony Area At Af Station Bhuj
Tender Value
49.40 Lakhs
Estimated cost
Bid Submission
06 Nov 2026
8 days left
EMD
98800
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kachchh → Gujarat
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Special Repair For Conversion Of Lt Over Head Electric Lines To Ug Cable And Connected Items In Cwe Office And Colony Area At Af Station Bhuj
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling ACSR or ACC Conductor with steel work all as Specified & directed by EIC. |
| 2 | Dismantling insulators any type, any size all as directed by Engineer-in-Charge |
| 3 | Dismantling cross arm any type, any size all as directed by Engineer-in-Charge |
| 4 | Dismantling stay assembly any type, any size all as directed by Engineer-in-Charge |
| 5 | Taking down existing street/security light fittings of any type and any wattage and refixing the same/new on existing pole including necessary clamps ,brackets including connections all as directed. |
| 6 | Supply & Fix in replacement FRP juction box of size outside dimensions 350 x 270 x 200 mm WITH 4 nos copper busbar of capacity 100 Amps , length 250 mm , 01 Nos MCB SPN C series of capacity 06 Amps as approved by the GE including connector and fixing on pole with and including MS clamps made out of 25 x 3mm MS flat iron, nut, bolts etc. complete. Note:- The cost of sintex box installation includes making hole of suitable size for entry and exit of cable any size, making new lugs of cables of entry and exit. |
| 7 | M & L for Wiring for Circuit from Sintex box to Street light with 2 x 2.5 sqmm sizes FRLSH PVC insulated copper conductor including 2.5 sqmm FRLSH copper conductor PVC insulated as earth wire in suraces/recessed as required in flexible casing if reqd/inside of steel tubular pole.Note : Two runs of the conductor with one run of wearth wire with one run of flexible casing reqd, will be measured as one unit |
| 8 | Supply & Fixing ,connecting,testing and commissioning and jointing,LT under ground cable 1100 volts grade,XLPE insulated,armoured with galvanized round steel wire or steel strip, electric power cables heavy duty, with multi stranded aluminum conductor, laid in trenches,ducts,fixed on poles/walls with proper size saddles and clamp laid under roads /path /drain /culverts or encased in GI pipe fixed/after taking proper shut down/connection using appropriate size lugs, crimped by crimper/gland in panel ,clearing of shut down after connection of LT cable and charging the LT cable & testing and commissioning complete all as specified and as directed by the Engineer-in-Charge of following Sizes:- Note:- (i) Sand cushioning, Cable protection cover, GI pipes, excavation and earth work shall be measured and paid for separately under respective items of Schedule \\"A\\" . |
| 9 | 6 sq mm 4 core. |
| 10 | 10 sq mm 4 core. |
| 11 | 10 sq mm 2 core. |
| 12 | 16 sq mm 4 core. |
| 13 | 25 sq mm 4 core. |
| 14 | 70 sq mm 3.5 core. |
| 15 | 95 sq mm 3.5 core. |
| 16 | 120 sq mm 3.5 core. |
| 17 | 150 sq mm 3.5 core. |
| 18 | 240 sq mm 3.5 core. |
| 19 | Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and not exc 1.5m in depth and getting out in hard/dense soil ,For laying of pipe/cable/finding out LT cable faults complete all as specified and directed by Engineer-in-Charge. |
| 20 | Returning filling in soil and including spreading leveling watering and well ramming in layers n.exc. 25 cm thick complete ,For laying of pipe/cable/finding out LT cable faults all as specified and directed. |
| 21 | Removing excavated soil to a distance n.exc. 50 mtr and depositing where directed at a level n.exc. 1.5m above the starting points complete all specified and directed. |
| 22 | M&L for sand cushioning for UG cables using dry river sand; gently punning down all as directed and specified. ( Note : For measurement purpose punned thickness shall be considered) |
| 23 | M & L unreinforced precast concrete cable covers CLASS LV type II, flat size 300 x 180 x 40 mm laid transverse to cable.all as specified and as directed by Engr-in-Charge. |
| 24 | M&L for road cutting for laying cables in GI pipe in trench size 0.45x0.60 Mtr and making disturbed surface good by using appropriate ratio of PCC all as specified and directed.(Note Laying of cables and GI pipe will me measured separately under respective items) |
| 25 | S&F GI tubing light grade for encasing cables for mechanical protection, laid under plinth/floors/ roads/ path /culverts or fixed on walls/on poles by means of MS FI clamps with necessary bolts, nuts and washers all as specified of sizes 50mm bore. |
| 26 | S&F GI tubing light grade for encasing cables for mechanical protection, laid under plinth/floors/ roads/ path /culverts or fixed on walls/on poles by means of MS FI clamps with necessary bolts, nuts and washers all as specified of sizes 80mm bore |
| 27 | M&L for heat shrinkable straight through joint for LT 1100 Volts grade, aluminum conductor including jointing kits, aluminium ferrules and labour complete for making joints and testing |
| 28 | Cable size 70 to 95 Sqmm, 3.5 core |
| 29 | Cable size upto 50 Sqmm, 4 core |
| 30 | M&L for heat shrinkable indoor/ outdoor LT end terminations for LT 1100 Volts grade, aluminum conductor including jointing kits, aluminium ferrules and labour complete for making joints and testing complete for size Cable size upto 150 to 240 Sqmm, 4.0 core |
| 31 | Supply, fabricate, test and commissioning of LT electrical out door distribution panel board floor mounted cubical type dust proof, weather proof,Both side openable, vermin proof, astehically desiggned, having at least IP-54 degree of ingress protection, fabricated from 3.15 mm thick CRCA sheet with front and rear opening including bus bar chamber, continuous GI strip earth bus bar 4 strips of Copper bus bar size 50x15 mm capacity, insulated color sleeves, procelain/epoxy insulators, rail channels cable alloy, danger notice board including over angle iron frame of size 40 x 40 x 6mm, 30 cm grouted in ground floor and 60 cm above GL including necessary excavation, foundation, PCC etc complete with locking arrangement duly powder coated painted of approved color connecting incoming & outgoing cable connection with suitable lugs, nuts, bolts, washers and cable joints, prewired complete with PVC insulated fire retardant copper conductor cable complete including:- ( Main Panel SS-24)Note-All cables whether existing or new,will be connected from bottom of the panel to ACB/MCCB/Bus bar by means of appropriate size gland and lugs.All MCCBs/ACBs to be interconnected by means of copper bus bar and open extended copper bus bar should also be provided at output side of all MCCBs to connecte LT cables. |
| 32 | (a)Phase indicator lamps,modular,LED type (R-Y-B)-03 Nos (b) Voltmeter digital type , flush type, with selector switch-01 No.(c ) Digital type ammeter, flush type, with CT's 100/5 A and selector switch-01 No.(d) ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 630 Amps(Incomer)(e) MCCB,250 Amp 36 KA,4 pole with adjustable thermal setting-01 No.(O/G) (f) MCCB,200 Amp 36 KA,4 pole with adjustable thermal setting-01 No.(O/G) (g) MCCB,100 Amp 25 KA,4 pole -02 Nos.(O/G)(h) MCCB,63 Amp 16 KA,4 pole -02 Nos.(O/G)(i) MCCB,40 Amp 16 KA,4 pole -02 Nos.(O/G) |
| 33 | Supply, fabricate, test and commissioning of LT electrical out door distribution panel board floor mounted cubical type dust proof, weather proof,Both side openable, vermin proof, astehically desiggned, having at least IP-54 degree of ingress protection, fabricated from 3.15 mm thick CRCA sheet with front and rear opening including bus bar chamber, continuous GI strip earth bus bar 4 strips of Copper bus bar size 40x10 mm capacity, insulated color sleeves, procelain/epoxy insulators, rail channels cable alloy, danger notice board including over angle iron frame of size 40 x 40 x 6mm, 30 cm grouted in ground floor and 60 cm above GL including necessary excavation, foundation, PCC etc complete with locking arrangement duly powder coated painted of approved color connecting incoming & outgoing cable connection with suitable lugs, nuts, bolts, washers and cable joints, prewired complete with PVC insulated fire retardant copper conductor cable complete including:- ( P-1026,SS-24)Note-All cables whether existing or new,will be connected from bottom of the panel to ACB/MCCB/Bus bar by means of appropriate size gland and lugs.All MCCBs/ACBs to be interconnected by means of copper bus bar and open extended copper bus bar should also be provided at output side of all MCCBs to connecte LT cables. |
| 34 | (a)Phase indicator lamps,modular,LED type (R-Y-B)-03 Nos (b) Voltmeter digital type , flush type, with selector switch-01 No.(c ) Digital type ammeter, flush type, with CT's 100/5 A and selector switch-01 No.(d) MCCB,200 Amp 36 KA,4 pole with adjustable thermal setting-01 No.(I/C) (e) MCCB,40 Amp 16 KA,4 pole -07 Nos.(O/G)+01 (Spare) |
| 35 | Supply, fabricate, test and commissioning of LT electrical out door distribution panel board floor mounted cubical type dust proof, weather proof,Both side openable, vermin proof, astehically designed, having at least IP-54 degree of ingress protection, fabricated from 3.15 mm thick CRCA sheet with front and rear opening including bus bar chamber, continuous GI strip earth bus bar 4 strips of Copper bus bar size 40x10 mm capacity, insulated color sleeves, procelain/epoxy insulators, rail channels cable alloy, danger notice board including over angle iron frame of size 40 x 40 x 6mm, 30 cm grouted in ground floor and 60 cm above GL including necessary excavation, foundation, PCC etc complete with locking arrangement duly powder coated painted of approved color connecting incoming & outgoing cable connection with suitable lugs, nuts, bolts, washers and cable joints, prewired complete with PVC insulated fire retardant copper conductor cable complete including:- ( Near P-733,&P-1030)Note-All cables whether existing or new,will be connected from bottom of the panel to ACB/MCCB/Bus bar by means of appropriate size gland and lugs.All MCCBs/ACBs to be interconnected by means of copper bus bar and open extended copper bus bar should also be provided at output side of all MCCBs to connecte LT cables |
| 36 | (a)Phase indicator lamps,modular,LED type (R-Y-B)-03 Nos (b) Voltmeter digital type , flush type, with selector switch-01 No.(c ) Digital type ammeter, flush type, with CT's 100/5 A and selector switch-01 No.(d) MCCB,100 Amp 25 KA,4 pole with adjustable thermal setting-01 No.(I/C) (e) MCCB 40 Amp 16 KA,4 pole -02 No.(O/G) +1 Spare |
| 37 | Supply, fabricate, test and commissioning of LT electrical out door distribution panel board floor mounted cubical type dust proof, weather proof,Both side openable, vermin proof, astehically designed, having at least IP-54 degree of ingress protection, fabricated from 3.15 mm thick CRCA sheet with front and rear opening including bus bar chamber, continuous GI strip earth bus bar 4 strips of Copper bus bar size 40x10 mm capacity, insulated color sleeves, procelain/epoxy insulators, rail channels cable alloy, danger notice board including over angle iron frame of size 40 x 40 x 6mm, 30 cm grouted in ground floor and 60 cm above GL including necessary excavation, foundation, PCC etc complete with locking arrangement duly powder coated painted of approved color connecting incoming & outgoing cable connection with suitable lugs, nuts, bolts, washers and cable joints, prewired complete with PVC insulated fire retardant copper conductor cable complete including:- ( P-1032)Note-All cables whether existing or new,will be connected from bottom of the panel to ACB/MCCB/Bus bar by means of appropriate size gland and lugs.All MCCBs/ACBs to be interconnected by means of copper bus bar and open extended copper bus bar should also be provided at output side of all MCCBs to connecte LT cables |
| 38 | (a)Phase indicator lamps,modular,LED type (R-Y-B)-03 Nos (b) Voltmeter digital type , flush type, with selector switch-01 No.(c ) Digital type ammeter, flush type, with CT's 100/5 A and selector switch-01 No.(d) MCCB,160 Amp 36 KA,4 pole with adjustable thermal setting-01 No.(I/C) (e) MCCB 40 Amp 16 KA,4 pole -06 No.(O/G) |
| 39 | Supply, fabricate, test and commissioning in replacement of LT electrical out door distribution panel board floor mounted cubical type dust proof, weather proof,Both side openable, vermin proof, astehically desiggned, having at least IP-54 degree of ingress protection, fabricated from 3.15 mm thick CRCA sheet with front and rear opening including bus bar chamber, continuous GI strip earth bus bar 4 strips of Copper bus bar size 40x10 mm capacity, insulated color sleeves, procelain/epoxy insulators, rail channels cable alloy, danger notice board including over angle iron frame of size 40 x 40 x 6mm, 30 cm grouted in ground floor and 60 cm above GL including necessary excavation, foundation, PCC etc complete with locking arrangement duly powder coated painted of approved color connecting incoming & outgoing cable connection with suitable lugs, nuts, bolts, washers and cable joints, prewired complete with PVC insulated fire retardant copper conductor cable complete including:- (main Panel SS-25)Note-All cables whether existing or new,will be connected from bottom of the panel to ACB/MCCB/Bus bar by means of appropriate size gland and lugs.All MCCBs/ACBs to be interconnected by means of copper bus bar and open extended copper bus bar should also be provided at output side of all MCCBs to connecte LT cables |
| 40 | (a)Phase indicator lamps,modular,LED type (R-Y-B)-03 Nos (b) Voltmeter digital type , flush type, with selector switch-01 No.(c ) Digital type ammeter, flush type, with CT's 100/5 A and selector switch-01 No.(d) MCCB,200 Amp 36 KA,4 pole with adjustable thermal setting-01 No.(I/C) (e) MCCB,100 Amp 25 KA,4 pole with adjustable thermal setting-02 No.(I/C) (f) MCCB 63 Amp 16 KA,4 pole -04 No.(O/G) (g) MCCB 40 Amp 16 KA,4 pole -02 No.(O/G) |
| 41 | Supply, fabricate, test and commissioning of LT electrical out door distribution panel board floor mounted cubical type dust proof, weather proof,Both side openable, vermin proof, astehically designed, having at least IP-54 degree of ingress protection, fabricated from 3.15 mm thick CRCA sheet with front and rear opening including bus bar chamber, continuous GI strip earth bus bar 4 strips of Copper bus bar size 00x10 mm capacity, insulated color sleeves, procelain/epoxy insulators, rail channels cable alloy, danger notice board including over angle iron frame of size 40 x 40 x 6mm, 30 cm grouted in ground floor and 60 cm above GL including necessary excavation, foundation, PCC etc complete with locking arrangement duly powder coated painted of approved color connecting incoming & outgoing cable connection with suitable lugs, nuts, bolts, washers and cable joints, prewired complete with PVC insulated fire retardant copper conductor cable complete including:- (Near main office)Note-All cables whether existing or new,will be connected from bottom of the panel to ACB/MCCB/Bus bar by means of appropriate size gland and lugs.All MCCBs/ACBs to be interconnected by means of copper bus bar and open extended copper bus bar should also be provided at output side of all MCCBs to connecte LT cables |
| 42 | (a)Phase indicator lamps,modular,LED type (R-Y-B)-03 Nos (b) Voltmeter digital type , flush type, with selector switch-01 No.(c) Digital type ammeter, flush type, with CT's 100/5 A and selector switch-01 No.(d) MCCB,100 Amp 25 KA,4 pole with adjustable thermal setting-01 No.(I/C) (e) MCCB 63 Amp 16 KA,4 pole -02 No.(O/G) (f) MCCB 40 Amp 16 KA,4 pole -02 No.(O/G) |
| 43 | M & L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure. |
| 44 | M&L for earthing complete with GI earth plate electrode 60cmx60cm x 6 mm thick buried directly in ground vertically to depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level connected to and including GI strip of 32X6mm as earth lead up to 7.5 mtr long fixed by means of bolts, nuts, check nuts and washers etc. of galvanised iron or steel including provn of GI protection pipe light grade of 32/40mm bore and connected to earth strip earthing test point all as shown in electrical plate No.5 of SSR Part-I 2009 and as specified or indicated and testing on completion including necessary excavation & earthwork in any type of soil, PCC (1:3:6) type C1 chamber, precast slab 50mm thick in cement concrete (1:2:4)type B1 (reinforced with welded steel wire fabric (XPM) of weight not less than 4kg/sqm) with frame, funnel with watering pipe of 15mm bore Sch.40, wire mesh and lugs, test point etc. complete.Note: GI strip exceeding 7.5m long shall be measured & paid seperately. |
| 45 | M & L for Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 4 mm dia by means of nut, bolts, check nuts and washers of galvanised iron or steel as shown in electrical plate No.3 of SSR Part-I (2009) complete all as specified and directed including testing on completion including the material and labour of the following : -(a) Excavation and earth work for electrode in any type of Soil.(b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter.(c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed(d) 15 mm nominal bore uPVC protection pipe 5 meter long for protection of earthing lead complete all as specified and directed.(e) Requisite quantity of common salt and charcoal.(f) Testing of earthing. |
| 46 | Supply and fixing LED street light fitting 100 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete,flexible copper wire upto 30 cm for connection with IP 65/66 protection complete. |
| 47 | Supply and fix in replacement of Steel tubular swaged poles ,swan neck complete with cast iron base plate, final taper plug, bolts, nuts and screws as specified type 410 SP-31 (9.00 metres long) complete including PCC foundation(1:3:6) and coping(2:4:8) incl of two coat of synthetic enamel silver paint after applying one coat of red oxide primer on outer surface of the pole,one coat of black bituminous paint on inner surface of the pole,connecting of Earthing wherever catered all as specified and as directed by Engr-in charge. |
| 48 | Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) TPN 40 to 100 Amp capacity in the existing DB complete with connection testing and commissioning.all as specified and as directed by engr-in-charge. |
| 49 | M & L for transporting transformer From one Sub Stn to another witout any damage to body or any component as directed within 8 Km distance by disconnecting HT/LT cables earthings etc as directed and reconnectuing HT/LT cables,earthings etc.all as specified and as directed by EIC,In case of any damage to the body/component of Transformer during transportation, contractor will pay estimated cost for the same.Note:-All T& P required for transportation shall be included in item rate quoted. |
| 50 | Supply & Fix of FRP juction box of size outside dimensions 400 x 300 x 190 mm of WITH 4 nos copper busbar of capacity 200 Amps , including internal wiring and 01 Nos MCCB of capacity 100 Amps,16 KA,4 pole with adjustable type as outgoing, as approved by the EIC including connector and fixing on pole with and including MS clamps made out of 25 x 3mm MS flat iron, nut, bolts etc. complete all as directed by Engineer-in-chargeNote:- The cost of sintex box installation includes making hole of suitable size for entry and exist of cable any size, making new lugs of cables of entry and exit. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 17, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 06, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysNov 09, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender