Tender For special Repairs To Roof And Rewiring Of Bldg No P-133 Of 91 Inf Bde Signal Coy At Pms Under Ge (Army) Trivandrum
Tender Value
46.98 Lakhs
Estimated cost
Bid Submission
04 Nov 2026
17 days left
EMD
94000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Thiruvananthapuram → Kerala
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for special Repairs To Roof And Rewiring Of Bldg No P-133 Of 91 Inf Bde Signal Coy At Pms Under Ge (Army) Trivandrum
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling of Plain or corrugated steel sheeting, any gauge, thickness, including Nainital or similar pattern roof coverings complete all as specified and directed. |
| 2 | S&F Pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self-tapping screws/ J-hooks complete all as specified and directed. |
| 3 | S&F Pre-painted galvalume aluminium zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self-tapping screws/ J-hooks complete all as specified and directed. |
| 4 | Dismantling timber scantlings 40 sq. cm and over in section, unframed work, in any position complete all as specified and directed. |
| 5 | M&L for second class hardwood in scantlings, clean sawn complete all as specified and directed. |
| 6 | All as per Sl No. 5.00 here-in-before, but except scantlings complete all as specified and directed.Note: Serviceable scantlings obtained from item No. 4.00 here-in-before will be reused under this item. |
| 7 | Dismantling wooden fillets for roof tiles battens, rails, posts, rafters, purlins etc. under 40 sq.cm in section (unframed work) complete all as specified and directed. |
| 8 | M&L for second class hardwood plain fillets (sectional area exceeding 13 sq.cm and not exceeding 25 sq.cm), square, rectangular or triangular in section, clean sawn, secured with nails or brads complete all as specified and directed. |
| 9 | All as per Sl No. 8 here-in-before, but except fillets complete all as specified and directed.Note: Serviceable fillets obtained from item No. 7.00 here-in-before will be reused under this item. |
| 10 | M&L preparation of new or old wooden surfaces of any description or girth not otherwise described and applying Creosote oil complete all as specified and directed. |
| 11 | S&F Rolled mild steel sections as in main and cross beams, hip and jack rafters; purlins where connected to common rafters and running rails and guides for sliding doors; fixed with angle cleats or other connecting plates confirming to Fe 410-W (Gde E- 250) quality A complete all as specified and directed by Engineer-in-Charge. |
| 12 | S&F rolled mild steel plates (plain or chequered), as in base plates etc., square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment confirming to Fe 410-W (Gde-E- 250) quality-A complete all as specified and directed. |
| 13 | M&L for preparation of new or previously un-treated surfaces of steel and iron of any description, over 10cm in width or girth, not otherwise described and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer all as specified and directed. |
| 14 | Dismantling of wall and ceiling wooden / AC boarding or insulation boards any thickness including cover fillets etc complete as as specified and directed |
| 15 | M&L 4 mm thickness non-asbestos fibre cement building boards (decorative type) including cover fillets fixed or laid/ inserted to timber/ GI/ Aluminium framework with screws fixed in ceiling flat or sloping complete all as specified and directed. |
| 16 | S&F anodised aluminium snap grid frame work (size of grid 605x605 mm) with 35x25x1.5 mm main tee and 25x25x1.4 mm cross tee and wall angle for false ceiling complete all as specified and directed. |
| 17 | S&F hangers 6 mm dia. G.I. (upto 1200mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of G.I. flat 40 x 3 mm size 60mm long and expansion hold fasteners 12.5mm dia. 40mm long complete all as specified and directed. |
| 18 | M&L preparation of old steel surfaces of any description over 10 cm width or girth not otherwise described and applying one coat of synthetic enamel paint complete all as specified and directed. |
| 19 | Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for complete all as specified and directed. |
| 20 | M&L for PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in bed blocks for grouting hold fasts, coping, filling in pressed steel chowkat or similar work including necessary form work as required complete all as specified and directed. |
| 21 | Taking down chowkats or frames with shutters (without taking off shutters from frames) area exceeding 1.5 Sqm and not exceeding 4 sqm each, including cutting holes for taking out hold fasts or dismantling brick work and making good in PCC 1:2:4 type B1 (using 12.5mm graded stone aggregate) or with cement mortar in CM 1:4 to match the existing surface identical complete all as specified and as directed. |
| 22 | S&F Powder coated aluminium (minimum thickness of powder coating 50 micron) frame for doors, windows ventilators & partitions with one or more rebates, grills including joining cleat for fixing etc., including powder coated complete all as specified and dierected by Engr-in-Charge. |
| 23 | S&F Powder coated aluminium (minimum thickness of powder coating 50 micron) for shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/neoprene gasket required (Fittings shall be paid for separately) with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing/ paneling, C.P. brass/ stainless steel screws all complete as per architectural drawings and the directions of Engineer-in-charge. |
| 24 | S&F Anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer in-charge |
| 25 | S&F 5.5 mm thick sheet glass ordinary quality and glazing with oil putty in square exc 0.50 sqm in each pane complete all as specified and directed. |
| 26 | S&F 12 mm thick Prelaminated particle board, exterior grade, prelaminated one side with decorative choice lamination & other side balancing white lamination, fixed with screws to timber/aluminium frame work complte all as specified and directed |
| 27 | S&F Aluminium alloy wire cloth, 0.45mm nominal dia of wire and average width of aperture 1.40mm and fixed with aluminium wire staples complte all as specified and directed |
| 28 | S&F door closer hydralulically regulated designation No 3 universal type, suitable for door shutters of 851 to 1000 mm width and weight between 61 to 80 Kg and fixed using aluminium extruded section complte all as specified and directed |
| 29 | S&F 4-lever, mortice lock, mild steel, vertical type, size as required and fixed complte all as specified and directed |
| 30 | S&F mild steel framed work such as grills, grating etc with end of bars shouldered and/ or riveted or forged into spikes, framed guard bars,barred iron doors, ladders, framed balusters, walk ways, railings and similar work confirming to Fe-410-0 or Fe 310-0 complete all as specified and directed. |
| 31 | M&L complete removal of existing treatment and applying 3mm thick layer of wall care putty and then applying two coats of oil bound distemper over a coat of chalk whiting after preparation of wall surfaces complete all as specified and directed. |
| 32 | Taking down cement plaster on brick or stone masonry surfaces of walls etc including raking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed. |
| 33 | M&L for rendering 10 mm thick in cement mortar 1:4 on fair faces of brick work or concrete surfaces finished even and smooth (without using extra cement) complete all as specified and directed. |
| 34 | M&L for two coats of old bound distemper over a coat of chalk whiting on newly prepared wall surfaces all as specified and directed. |
| 35 | Taking down copper/aluminium point wiring (light, ceiling fan,exhaust fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials and making good disturbed surfaces of walls, floors, etc.complete all as specified and directed. |
| 36 | M&L for taking down old unsv aluminium/copper submain wiring of any size as specified and directed. |
| 37 | M&L for point wiring complete for one light point controlled by one switch with complete with 1.5 sqmm PVC insulated FRLSH unsheathed cable1100 volts grade multistranded copper conductor single core conforming to IS-694 1990 with ISI marked (for phase, neutral and earth) in and including PVC casing and caping with ISI mark of minimum 20/25 mm size and all casing and caping accessories and including factory made branded make embossed galvanised steel pressed terminal boxes alongwith suitable size modular cover plates with frames for fixing modular switches and sockets , fan regulators etc of suitable sizes modules and the earth wire connected to common earth dolly complete all as specified and directed. |
| 38 | All as per item No. 37.00 here in before but for one fan point controlled by one way switch and regulator complete all as specified and directed. |
| 39 | All as per item No. 37.00 here in before but for exhaust fan controlled by one switch complete all as specified and directed. |
| 40 | All as per item No. 37.00 here in before but for One 3 Pin, 5 Amps socket outlet on same board with other switches/ sockets complete all as specified and directed. |
| 41 | All as per item No. 37.00 here in before but for One 3 Pin, 5 Amps socket outlet on independent board complete all as specified and directed. |
| 42 | M & L for Point wiring complete with all specified with 1100 Volts grade 2.5 sqmm single core PVC insulated FRLSH unsheathed cable1100 volts grade multistranded copper conductor single core conforming to IS-694 1990 with ISI marked (for phase, neutral and earth) in and including PVC casing and caping with ISI mark of minimum 20/25 mm size and all casing and caping accessories and including factory made branded make embossed galvanised steel pressed terminal boxes alongwith suitable size modular cover plates with frames for fixing modular switches and sockets , fan regulators etc of suitable sizes modules and the earth wire connected to common earth dolly complete all as specified and directed for one 3 pin modular switch socket outlet 16 Amps on independent board. |
| 43 | All as per ser item No. 42 here in above but point wiring with 4.0 Sqmm FRLSH cable and 4.0 sqmm cable earth continuity wire for one 3 pin socket outlet,15 Amps on independent board. |
| 44 | S&F modular switch 1 way 6A, 240 volts, 1 module complete all as specified and directed |
| 45 | S&F modular switch 1 way 16A, 240 volts, 1 module complete all as specified and directed |
| 46 | S&F modular fan step regulator, 120 W - 2 module, 240 Volts, 50 Hz, suitable for ceiling fan any sweep complete all as specified and directed |
| 47 | S&F modular socket, 6A, 240 volts, 2/3 pin combined 2 module, flush type complete all as specified and directed |
| 48 | S&F modular socket, 6A/16A, 240 volts, 2/3 pin combined 2 module flush type complete all as specified and directed |
| 49 | S&F ceiling rose surface PVC/Polycarbonate, isolated body with face Bakelite three terminal complete all as specified and directed |
| 50 | Supply and fixing of Remote control operated Smart LED batten 20 Watts with Remote including battery, with tunable colors and dimming, working in normal light and emergency light with colours (Cool white /Normal white/Warm white), CCT 6500K-3000K adjustable, rated voltage 220 V, AC, 50 HZ Lithium Ion battery 2600 mAH with charging time 7 hours, over charge protection and back up time upto 4 hours, Luminous efficency greater than 100 Lm/watt @ 6500K, Dimming efficiency 100% to 20% including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.Make: Jaquar cat No. SSB-WHT-LSRA01S020DM or equivalent make of Philips/Bajaj/Wipro/Crompton/Havells/Goldmedal |
| 51 | Supply and fixing of Inverter LED batten (2 feet) Cool White 10 Watts LED 6500 K, 220V, IP rating 20, AC Decorative box type with driver, Lithium Ion battery 2200 mAH with charging time 9hours, over charge protection and back up time upto 2 hours including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.Make: Jaquar cat No. HEL-WHT-LKRZ01BAT10C or equivalent make of Philips/Bajaj/Wipro/Crompton/Havells/Goldmedal |
| 52 | Supply and fixing of Recessed/Surface mounting 1x36 Watts LED luminaire 140 Lm/Watt (2'x2') 6500 K, prewired with white powder coated CRCA housing with LEDs and full mounted acrylic diffuser, suitable for 600x600mm E-grid/POP/ false ceiling complete with all accessories making connection using 3 core, 0.50 Sqmm PVC insulated and overall sheathed flexible copper conductor cable from ceiling rose/ PVC connector to light fitting and testing etc complete all as specified and directed.Make: Jaquar cat No. IPN-WHT-LULPU2SL36XC or equivalent make of Philips/Bajaj/Wipro/Crompton/Havells/Goldmedal |
| 53 | S&F LED light fitting 1x9 watt/10 watts bulk headfitting including LED light , driver holder and connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 54 | S&F sheet steel metal enclosure single pole & neutral with a 2 pin and earth plug and socket complete with one single pole MCB SP 20 Amp, 240 volts complete all as specified and directed. |
| 55 | S&F in of distribution board, vertical, made out of sheet metal enclosure (CRCA sheet) dust and vermin proof, double door, VTPN 4 way, 415 volts grade with insulated rated bus bar with nickel plated brass, isolated neutral bar and door earthing, earth bar IP- 43 protection with poly urithene (PU) gasketing, IK-08 Mechanical impact resistance, door earthing flush to wall, including testing suitable for fixing MCCB, MCB TP/SPN/SP etc, including taking down existing unserviceable one and removing from site complete all as specified and directed. |
| 56 | S&F in replacement of MCCB, triple pole and neutral (four pole), 125 Amp, 415 volts, 50 Hz, having thermal setting range 70% to 100% and adjustable magnetic setting and breaking capacity 16 KA including making incoming and outgoing connections complete all as specified and directed. |
| 57 | M&L for TPN DB 4 way , made out of sheet metal enclosure (CRCA sheet) dust and vermin proof, double door, 415 volts grade with insulated rated bus bar with nickel plated brass, isolated neutral bar and door earthing, earth bar IP- 43 protection with poly urithene (PU) gasketing, IK-08 Mechanical impact resistance, door earthing flush to wall, including testing suitable for fixing MCB TP/SPN/SP etc, including taking down existing unserviceable one and removing from site complete. |
| 58 | S&F RCBOs 4-Pole RCBO capacity 40 Amps, 300mA 415 Volts for earth leakage, overload and short circuit protection complete all as specified and directed. |
| 59 | Supply and fix sheet metal enclosure double door powder painted for MCB DB SPN 8 way with din rail and bus bar including grouting the DB to wall and making good to the disturbed surface matching with the existing complete all as specified and directed |
| 60 | Supply and fixing amp rating 240V, 10 KA 'C' curve miniature circuit breaker MCB of single pole 6 to 32 Amps current carrying capacity, in the MCB DB including connection testing and commissioning complete all as specified and directed |
| 61 | All as per ser item No. 60 above but for MCB TP 63 Amps 415V complete all as specified and directed. |
| 62 | Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 40 Amps, SP in the MCB DB complete with connection testing and commissioning all as specified and directed |
| 63 | S&F RCBOs double pole RCBO capacity 32 Amps, 30mA 230 Volts for earth leakage, overload and short circuit protection complete all as specified and directed. |
| 64 | Supply and fixing sub-main wiring with 4 runs of 10 sqmm single core PVC insulated, FRLSH, unsheathed cable with stranded copper conductor, 1100 Volts grade drawn through and including PVC conduit 20/25mm bore with all fitting such as Tees, Bends, Elbows, etc., fixed surface on wall/ceiling including 1 run of 10 Sqmm multistranded PVC insulated, FRLSH, copper conductor cable as earth continuity conductor and connecting to common earth dolly complete all as specified and directed. NOTE: 4 runs of 10.0 sqmm copper cables and one run of 10.0 sq mm copper cable along with white colour PVC conduit/ conduit accessories will be measured as one unit length. |
| 65 | Supply and fixing sub-main wiring with 2 runs of 6 sqmm single core PVC insulated, FRLSH, unsheathed cable with stranded copper conductor, 1100 Volts grade drawn through and including PVC conduit 20/25mm bore with all fitting such as Tees, Bends, Elbows, etc., fixed surface on wall/ceiling including 1 run of 6 Sqmm multistranded PVC insulated, FRLSH, copper conductor cable as earth continuity conductor and connecting to common earth dolly complete all as specified and directed. NOTE: 2 runs of 6.0 sqmm copper cables and one run of 6.0 sq mm copper cable along with white colour PVC conduit/ conduit accessories will be measured as one unit length. |
| 66 | Taking down carefully existing serviceable Ceiling fan, ceiling cable end, etc., removing the fan for keeping in safe custody, painting of ceiling fans complete in situ with synthetic enamel paint by spraying including filling cavitie with filler one coat after cleaning all dust etc, hanging the ceiling fan with required length of down rod after rewiring including clamps, hooks, hold fasteners etc and connecting up, including making electric connection from ceiling rose or connector to fan complete all as directed |
| 67 | Supply and fixing of ceiling fans complete with blades, down rods, electronic regulators and accessories 230V, 1200mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) remote control fan with remote complete all as specified and directed. |
| 68 | Supply and fix exhaust fans, steel body AC single phase, 230 Volts of size 300mm sweep with, blades and frames and louvers complete all as specified and directed. |
| 69 | M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below normal ground level, connected to galvanised earth lead wire of size 4mm dia by means of GI Bolts, Nuts, check nuts and washers of the earth and thimbles and other end of the earth GI wire connected to earthing test point and protected by galvanised iron pipe light grade 15mm dia from earth plate to Panel/DBs and water pipe 20mm dia GI medium grade raised up to a level of 50cm above ground level with plug at top, earthing pit in PCC (1:3:6) type C-1 RCC pre-cast (1:2:4 type B-1) cover slab of 50 mm thick using 8.00mm dia CTD bars reinforcement both ways at 140 mm centre to centre with handle, 20 mm dia GI pipe medium grade for watering pipe, wire mesh, funnel and providing charcoal or coke and salt in alternative layers of 15 cm including necessary earth work in soft/ loose soil, returning, refilling and removing of surplus soil to a distance not exceeding 50 mtr testing complete all as shown in electrical plate No-3 of MES Schedule Part-I of SSR-2009 complete all as specified and directed, including taking down existing unserviceable earthing complete all as specified and directed. Please Enable Macros to View BoQ information |
| 70 | M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below normal ground level, connected to galvanised earth lead wire of size 4mm dia by means of GI Bolts, Nuts, check nuts and washers of the earth and thimbles and other end of the earth GI wire connected to earthing test point and protected by galvanised iron pipe light grade 15mm dia from earth plate to Panel/DBs and water pipe 20mm dia GI medium grade raised up to a level of 50cm above ground level with plug at top, earthing pit in PCC (1:3:6) type C-1 RCC pre-cast (1:2:4 type B-1) cover slab of 50 mm thick using 8.00mm dia CTD bars reinforcement both ways at 140 mm centre to centre with handle, 20 mm dia GI pipe medium grade for watering pipe, wire mesh, funnel and providing charcoal or coke and salt in alternative layers of 15 cm including necessary earth work in soft/ loose soil, returning, refilling and removing of surplus soil to a distance not exceeding 50 mtr testing complete all as shown in electrical plate No-3 of MES Schedule Part-I of SSR-2009 complete all as specified and directed, including taking down existing unserviceable earthing complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 17, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 04, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysNov 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender