Tender For Repair/ Maintenance Of Lt Panel Boards, Switch Gears, Earthings And Connected Misc Works Etc At Electric Supply Installation At installation Dronacharya Under Ge Fort Kochi
Tender Value
13.75 Lakhs
Estimated cost
Bid Submission
06 Nov 2026
8 days left
EMD
27500
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ernakulam → Kerala
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/ Maintenance Of Lt Panel Boards, Switch Gears, Earthings And Connected Misc Works Etc At Electric Supply Installation At installation Dronacharya Under Ge Fort Kochi
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exc 1.5m wide and not exc 1.5m deep and making good bottom surface for laying /removing of cable, erection of poles in soft/ loose soil complete, all as specified and as directed. |
| 2 | Material and Labour for removing excavated soil to a distance not exceeding 50 m and not exceeding 1.5 m above the starting point, and depositing where directed complete all as specified and as directed. |
| 3 | Material and Labour for sand cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid) of 23 cm spread thickness (8 cm in depth before laying the cable and 15 cm in depth after laying the Cable) and consolidated (punned) up to 180mm thickness, complete all as specified and as directed. Note: For the purpose of payment, punned thickness of Sand Cushioning only will be measured. |
| 4 | Material and labour for burnt bricks subclass B laid in trenches for cable protection complete, all as specified and as directed. |
| 5 | Returning filling in excavated soil in trenches, watering and well ramming in layers not exc 25 cm complete all as specified and as directed. |
| 6 | Taking out unserviceable UG cables of any sizes from trenches/walls including all mounting accessories and GI tubing including making good to disturbed area complete all as specified and as directed |
| 7 | Material and Labour for XLPE insulated PVC sheathed armoured with multistranded aluminium conductor cable having cross sectional area 16 sqmm 4 core, 1100-volt grade, Earthed, Heavy grade conforming to IS :7098 (Part 1) laid in trenches/Ducts or passing through pipes or fixing on poles etc. with stranded aluminium conductor of size laid in trenches, ducts etc. complete all as specified and as directed. |
| 8 | Material and Labour for XLPE insulated PVC sheathed armoured with multistranded aluminium conductor cable having cross sectional area 25 sqmm 4 core, 1100-volt grade, Earthed, Heavy grade conforming to IS :7098 (Part 2) laid in trenches/Ducts or passing through pipes or fixing on poles etc complete all as specified and directed. with stranded aluminium conductor of size laid in trenches, ducts etc. complete all as specified and as directed. |
| 9 | Material and Labour for XLPE insulated PVC sheathed armoured with multistranded aluminium conductor cable having cross sectional area 50 sqmm 3.5 core, 1100-volt grade, Earthed, Heavy grade conforming to IS :7098 (Part 4) laid in trenches/Ducts or passing through pipes or fixing on poles etc complete all as specified and directed. with stranded aluminium conductor of size laid in trenches, ducts etc. complete all as specified and as directed. |
| 10 | Material and Labour for XLPE insulated PVC sheathed armoured with multistranded aluminium conductor cable having cross sectional area 70 sqmm 3.5 core, 1100-volt grade, Earthed, Heavy grade conforming to IS :7098 (Part 5) laid in trenches/Ducts or passing through pipes or fixing on poles etc complete all as specified and directed. with stranded aluminium conductor of size laid in trenches, ducts etc. complete all as specified and as directed. |
| 11 | Taking down unserviceable LT panel of any type from existing position after disconnection of electric connection of all any size UG cables & temporary restoration of normal electric supply till final installation of New LT panel including making good disturbed surfaces if floor/walls etc complete all as specified and as directed. |
| 12 | Supply, installation, commissioning and testing LT Panel Board of minimum size 2.0 Mtr (height) x 2.0 Mtr (breath) x 0.45m (depth) ,2.0 mm thick, factory made CPRI approved panel, weather, dust & vermin proof Indoor type, double door, front openable, and made LT panel through Stainless steel sheet compartmentalized design including stainless steel channel frame, and ISMC 75 at the base of panel only for grouted with PCC using 20 mm graded stone aggregate, duly providing rubber/ PVC gasket of suitable size all sides of door, with aluminium busbar 800 AMPs capacity wrapped with PVC tape/ sleeves with maintained the colour code and copper strip/ wire busbar of suitable size to MCCB input and MCCB output of suitable length including aluminium bus bar of suitable size for neutral for connection of cable from main busbar, made out of 2.0 mm thick stainless steel with suitable size angle iron supporting frame including applying two coats of Powder coated paint over a coat of red oxide zinc chrome primer over exposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade including complete internal wiring with 6 sqmm copper wire and connections of all outgoing/ incoming electrical cable connections with new lugs, glands to be provided at cable entries, including angle iron support 50x50x6 mm angering with 45 cm height from ground level at the base of panel. The panel shall be comprising of following accessories, complete all as specified and as directed. |
| 13 | INCOMMING: -(a) MCCB, 4 Pole 415 Volts, 50Hz 250 Amps, 36 kA, thermal magnetic release, Ics =100% Icu, front face isolation with positive break indication with double break contacts with spreader and phase barrier - 01 No, Make - L/T, Havells, Schneider.(b) Multi-function digital energy meter with Rs 485 communication port with CTs.(c) Phase Indicator lamp assy RYB - 01 Set.(d) CT Coils of suitable ratio-01 Set. OUTGOING: - (a) MCCB, 4 Pole 415 Volts, 50Hz, 160 Amps, 25 kA, thermal magnetic release, Ics =100% Icu, front face isolation with positive break indication with double break contacts with spreader and phase barrier - 03 Each.(b) MCCB, 4 Pole 415 Volts, 50Hz, 100 Amps, 25 kA, thermal magnetic release, Ics =100% Icu, front face isolation with positive break indication with double break contacts with spreader and phase barrier - 02 Each.(c) MCCB, 4 Pole 415 Volts, 50Hz, 63 Amps, 25 kA, thermal magnetic release, Ics =100% Icu, front face isolation with positive break indication with double break contacts with spreader and phase barrier - 02 Each.(d) MCB, single pole & neutral, up to 32 Amps, with DBs, 240 volts, ‘C’ curve, 10 KA all complete as specified and as directed -0 2 Nos.(e) Automatic single dial time switch panel mounted flush to panel door, 230V AC quartz time base, with one selector switch for auto/manual selection Part No 15336, Type IH24h Make- Schneider/L&T/Legrand – 01 No (Bldg Security light) |
| 14 | Supply, installation, commissioning and testing LT Panel Board of minimum size 1.0Mtr (height) x 1.0 Mtr (breath) x 0.45 m (depth) ,2.0 mm thick, factory made CPRI approved panel, weather, dust & vermin proof Indoor type, double door, front openable, and made LT panel through Stainless steel sheet compartmentalized design including stainless steel channel frame, and ISMC 75 at the base of panel only for grouted with PCC using 20 mm graded stone aggregate, duly providing rubber/ PVC gasket of suitable size all sides of door, with aluminium busbar 200 AMPs capacity wrapped with PVC tape/ sleeves with maintained the colour code and copper strip/ wire busbar of suitable size to MCCB input and MCCB output of suitable length including aluminium bus bar of suitable size for neutral for connection of cable from main busbar, made out of2.0mm thick stainless steel with suitable size angle iron supporting frame including applying two coats of Powder coated paint over a coat of red oxide zinc chrome primer over exposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade including complete internal wiring with 6 sqmm copper wire and connections of all outgoing / incoming electrical cable connections with new lugs, glands to be provided at cable entries, including angle iron support 50x50x6 mm angering with 45 CM height from ground level at the base of panel . The panel shall be comprising of following accessories, complete all as specified and as directed by Engineer-in-Charge. |
| 15 | 1. Two (02) Nos of 10 HP (7.5 KW) capacity star delta starter fixing with is a three-phase motor control device designed to reduce starting current by initially running the motor in a star configuration before automatically switching to a delta configuration for full load operation. 2. Power rating 10 HP (7.5 KW), operational voltage 415 V, AC, three phase, frequency 50 Hz.3. Over load relay range: Typically, 6 A - 10A or 9 A-14 A depending on motor full load current specifies.4. Control / coil voltage: 415 V AC.5. Utilization category: AC 3 duty for induction motors.6. Contactors: Three inter connected 3 pole contactors, main star and delta, engineered with mechanical and Electrical interlocking to prevent simultaneous star - delta closure.7. Timer: Integrated electric or pneumatic timer that automatically shifts the connection from star mode to delta mode after a preset duration.8. Thermal overload protection: Protects the motor against continuous current overload and burning.9. Single phasing protector: Trips the system instantly / imbalance protector: Prevents reverse rotation and unbalance voltage stress on motor windings. |
| 16 | INCOMMING: -(a) MCCB, 4 Pole 415 Volts, 50Hz, 63 Amps, 16 kA, thermal magnetic release, Ics =100% Icu, front face isolation with positive break indication with double break contacts with spreader and phase barrier - 01 Each.(b) Multi-function digital energy meter with Rs 485 communication port with CTs.(c) Phase Indicator lamp assy RYB - 01 Set.(d) CT Coils of suitable ratio-01 Set. OUTGOING: - (a) MCB, TP, 63 Amps, 240 volts, ‘C’ curve, 10 KA all complete as specified and as directed - 02 Nos |
| 17 | Earthing complete with galvanised iron earth plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level, earth plate connected with GI strip 32X 6 mm by means of lug, bolts, nuts, check nuts, washers of galvanised iron or steel, GI protection pipe 40 mm bore light grade all as shown in elect plate No 3 on serial page No 497 of SSR part I - 2009 and connected to earthing test point all as specified or indicated including excavation, earth work, salt and charcoal dust mixed and packed 150 mm thick around copper earth plate, GI pipe medium grade 20 mm nominal bore watering pipe, GI sheet funnel, wire mesh, PCC pit 1:2:4, (type B-1) RCC cover 50 mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 8 mm dia at the rate of 75 mm centre to centre both way with 12 mm dia lifting handle and pit/ chamber in PCC 1:2:4 (type B-1) including testing on completion complete all as specified and as directed. |
| 18 | Material and Labour for servicing of LT Panel boards outdoor/indoor of sizes up to 250 x 150 x 50 cm installed at various locations by disconnecting from mains taking out burnt cable ends and reconnecting using internal connection with copper cables, necessary lugs, cable glands, gland plate, gaskets etc and scrapping out of rusted uneven surfaces and applying by spray painting two coats of paint of desired shade over a coat of metallic primer complete all as specified and as directed. |
| 19 | Material and Labour for servicing of LT Feeder pillars outdoor/indoor of sizes up to 200 x 100 x 40 cm installed at various locations by disconnecting from mains taking out burnt cable ends and reconnecting internal connection with copper cables using necessary lugs, cable glands, gland plate, gaskets etc and scrapping out of rusted uneven surfaces and applying by spray painting two coats of paint of desired shade over a coat of metallic primer complete all as specified and as directed. |
| 20 | Supply and laying GI tubing light grade including all accessories for encasing cables for mechanical protection, laid under Plinth / Floors/ Paths Culverts or fixed on wall or concealed in wall/floor or along poles or as street light poles or as street light mounting bracket with complete accessories such as bends/sockets/reducers/saddles and necessary threading/drilling works complete including taking down old tubing all as specified and as directed of sizes: |
| 21 | 80 mm bore |
| 22 | 50 mm bore |
| 23 | 40 mm bore |
| 24 | Supply and fix in replacement MCCB 415V 160 Amps TPN 25 KA thermal magnetic release with spreader terminals and including making necessary connections, fixing to panel Boards and ensure compatibility with existing MCCB in fit and finish including taking down old unserviceable MCCB complete all as specified and as directed. |
| 25 | Supply and fix in replacement MCCB 415V 200 Amps TPN 36 KA thermal magnetic release with spreader terminals and including making necessary connections, fixing to panel Boards and ensure compatibility with existing MCCB in fit and finish including taking down old unserviceable MCCB complete all as specified and as directed. |
| 26 | Supply and fix in replacement MCCB 415V 250 Amps TPN 36 KA microprocessor-based release with spreader terminals and including making necessary connections, fixing to panel Boards and ensure compatibility with existing MCCB in fit and finish including taking down old unserviceable MCCB complete all as specified and as directed. |
| 27 | Supply and fix in replacement MCCB 415V 125 Amps TPN 25 KA microprocessor-based release with spreader terminals and including making necessary connections, fixing to panel Boards and ensure compatibility with existing MCCB in fit and finish including taking down old unserviceable MCCB complete all as specified and as directed. |
| 28 | Supply and fix in replacement MCCB 415V 63 Amps TPN 25 KA microprocessor-based release with spreader terminals and including making necessary connections, fixing to panel Boards and ensure compatibility with existing MCCB in fit and finish including taking down old unserviceable MCCB complete all as specified and as directed. |
| 29 | Supply and fix in replacement MCCB 415V 400 Amps TPN 26 KA microprocessor-based release with spreader terminals and including making necessary connections, fixing to panel Boards and ensure compatibility with existing MCCB in fit and finish including taking down old unserviceable MCCB complete all as specified and as directed. |
| 30 | Material and Labour for clearing of Grass Shrubs and other growing by uprooting around poles and feeder pillars up to 10 cm in girth in various locations complete all as specified and as directed |
| 31 | Material and Labour for GI Strip 32x6 mm with saddle and fixing screws etc from test terminal block to earth pit and including taking down old unserviceable materials complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 16, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 06, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysNov 13, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 15 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender