Tender For special Repair Replacement Of O/H Ht Abc Cable Into Ht Xlpe Ug Cable And Connected Items From 14 Mech Inf Four Ppole To Bundela C Area Under Ge Babina
Tender Overview
Project Description
Tender for special Repair Replacement Of O/H Ht Abc Cable Into Ht Xlpe Ug Cable And Connected Items From 14 Mech Inf Four Ppole To Bundela C Area Under Ge Babina
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 06-Nov-2026 | Corrigendum No I | Date | 19-Nov-2026 |
| 2 | 19-Nov-2026 | Corrigendum No II | Date | 28-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply, laying testing and commissioning in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 11000 Volt grade with multistranded aluminium conductor of size 120 Sqmm 3 core including taking out old u/s existing HT cable including suitable size of aluminium lugs/thimble and taking down old unserviceable existing HT cable complete all as specified and directed. |
| 2 | M & L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to galvanised earth lead 32X6mm by means of bolts, nuts, check nuts and washers of galvd iron or steel surronded by charcoal of coke and salt and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 5 of MES schedule Pt I of 2009 and also including making test point for testing of earthing made out of gun metal or phosphorous bronge size 75x75x25 mm complete |
| 3 | Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover.2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item. |
| 4 | Supply, laying testing and commissioning in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 11000 Volt grade with multistranded aluminium conductor of size 95 Sqmm 3 core including taking out old u/s existing HT cable including suitable size of aluminium lugs/thimble and taking down old unserviceable existing HT cable complete all as specified and directed. |
| 5 | Material and labour for cross arms, bracings, supports clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coat of aluminium paint over a coat of red oxide primer including preparing the surface all as specified and as directed. |
| 6 | Excavating in trenches soft/loose soil, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying of cable, laying of pipes . n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed. |
| 7 | Excavating in trenches Hard Rock soil , n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying of cable, laying of pipes . n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed. |
| 8 | Excavating in trenches soft/loose soil, Exc 1.5 m wide and n exc 3.0 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying of cable, laying of pipes . n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed. |
| 9 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm soft/loose soil complete all as specified and directed. |
| 10 | Removing excavated material(soil) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 11 | M&L for sand cushioning in cable trenches over & under the cables, with river washed coarse sand, as per standard practice with proper compaction complete all as specified and directed. Note : Punned thickness 18 cm shall be considered for payment as per para 19.75 of SSR Part-I. |
| 12 | Supply & laying in trenches unreinforced precast concrete cable cover, class HV type-I flat, size 300x180x40mm for cable protection complete all as specified and as directed. |
| 13 | M&L for PCC 1:4:8 type D2 (using 40 mm graded stone aggregates) for foundation filling and bed concrete all as specified. |
| 14 | M&L for P.C.C. 1:3:6 (Type C-2,40mm graded aggregate) as in foundation filling or for mass concrete of poles,stays,struts or any other indicated work including form work (if required) complete all as specified and directed. |
| 15 | M&L for P.C.C. 1:2:4 (Type B-1,20mm graded aggregate) for coping of poles / platform of feeder pillar box or any other indicated work including form work(if required) duly 20mm thick cement plaster (1:4) and making the surface smooth and even by using extra cement complete all as specified and directed. |
| 16 | M&L for GI tubing (light grade) with all necessary fittings laid in trenches under road crossing fixed on poles, wall under floor etc. of 80 mm dia bore complete all as specified and directed. |
| 17 | M&L in repair Cable jointing kit for 11 KV (Earthed ) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm all as specified and as directed |
| 18 | M&L in repair Cable jointing kit for 11 KV (Earthed ) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm all as specified and as directed |
| 19 | M&L in repair Cable jointing kit for 11 KV (Earthed ) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm all as specified and as directed |
| 20 | M&L in repair Cable jointing kit for 11 KV (Earthed ) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm all as specified and as directed |
| 21 | S & F in repair heat shrink straight through type Cable jointing kit for 11KV HT XLPE cable of size 95 Sqmm 3 core complete with jointing material and accessories complete all as specified and directed. |
| 22 | S & F in repair heat shrink straight through type Cable jointing kit for 11KV HT XLPE cable of size 120 Sqmm to 185 sqmm 3 core complete with jointing material and accessories complete all as specified and directed. |
| 23 | M&L steel tubular swaged poles complete with cast iron base plate, final taper plug, bolts, nuts & screws as specified , type 410 SP 55 (11 meter long) and shall be in confimity with IS 2713 ( Part 1 to 3) including protection against corrosion as per Para 19.3.6 of SSR Part-I complete as specified and directed. Note :- Earth work and PCC shall be measured and paid seperately. |
| 24 | Supply and fix in repair Polymer type air break switch, gang operated, triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 400 Amps and working pressure 11000 Volts with drop out type fuses set 12 insulators (three numbers of 40 Amp capacity) complete including dismentling air break gang operated switches vertical/horizontal mounted including insulator hand operating mechanism for replacement of broken/worn out components and insulators etc all as specified and directed. Please Enable Macros to View BoQ information |
| 25 | Supply and fix in repair Polymer type air break switch, gang operated, triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 400 Amps and working pressure 11000 Volts with drop out type fuses set 12 insulators (three numbers of 40 Amp capacity) complete including dismentling air break gang operated switches vertical/horizontal mounted including insulator hand operating mechanism for replacement of broken/worn out components and insulators etc all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 6 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender