Tender For Supply Installation Testing and Commissioning of Split Ac For Computer Lab And Fundamental Lab And Allied electrical installation Works Of Nts, Sarat Chandra Chattopadhyay Govt. Medical College And Hospital, Uluberia, Howrah,
Tender Overview
Project Description
Tender for Supply Installation Testing and Commissioning of Split Ac For Computer Lab And Fundamental Lab And Allied electrical installation Works Of Nts, Sarat Chandra Chattopadhyay Govt. Medical College And Hospital, Uluberia, Howrah,
BOQ
| Sl. No. | Item Description |
| 1 | SUB-HEAD 1 - SITC OF AC MACHINE |
| 2 | Supply and Delivery of Non Inverter Split Air Conditioner machine having cooling capacity not less than 6900 W, ISSER 3.8 to 4.39, BEE rating not less than 3 star, noise level not more than 50 db. This Split Air Conditioning machine fitted with rotary compressors, LCD Remote and all other accessories suitable for Refrigerant-R32/ R410A. (Make: O-General/ Daikin/ Hitachi/Mitsubishi Electric/Mitsubishi Heavy Industries as per approved by EIC/ Authority) |
| 3 | Installation, testing & commissioning of the above said split AC machine incl supply & Fixing required angle iron structure on wall for placing outdoor unit & mending good the damages as per Direction of EIC |
| 4 | Supply & Installation of Extra Add-on items -HVAC graded 5/8''( for suction) & 1/4'' ( For Discharge) copper refrigerant pipe with 9 mm thick nitrile rubber isulation including sgaddle, Screw, isulation tape, Fastner etc for above AC machine as per direction of EIC |
| 5 | Supply & laying 1.1 kv grade,3 Core, 4 sqmm flexible copper cable with screw, Saddle,nut bolt etc all necessary items needed for connection. (From starter to AC outdoor connection) ( Make- Havells/ KEI/Polycab/Finolex as per approved by EIC) |
| 6 | Supply & laying 20 mm dia, PVC Pipe (heavy type) incl. Fitting accessories for water drainage. |
| 7 | Supply & Filling of R-32/ R-410A Refrigerant where needed. |
| 8 | S&F of 32A timer controlled DB for 1no single phase AC in SS double door 12-way DB enclosure (Make:L&T/ Legrand/ABB(E)) with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish.All connections should be made by copper wire of 4mm² & 1.5 mm² and finishing with dowells solderless socket by crimping method incl necessary connection & provision for earthing attachment incl Ferruling & marking with S&F following Electrical accessories as per direction of EIC [for 2 / 1.5 TR AC]i. 240V, 32A DPMCB C curve breaking capacity 10kA (Make:L&T) - 1 no.ii. 240V, 22A, 2P Contactor - 1 nos. [MNX 22, L&T]iii.10A,250V AC ON-OFF-ON SPDT toggle switch with marking (Make-Kaycee Model No:KT1032BY) --1 no.(for Auto/Manual option).iv. 24Hr x 7days programmable Digital timer (Make:L&T Cat no 67DDT0) -- 1 no.v. On & Off Indicator with marking-2 nos. vi.Din rail mounted Terminal Block for Outgoing & Incoming(Make:Elmax Model:KUT4) -- 4 nos vii.6A SP MCB c curve breaking Capacity 10kA-- 1 no(Make:L&T) [NS] |
| 9 | SUB-HEAD 2--DISTRIBUTION WIRING: |
| 10 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene pipe as per GS.[ As per approved list of Material ] (Polycab/Havells/KEI/Mescab) |
| 11 | 2x(4 sqmm)+1x (2.5 sqmm) |
| 12 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc including supplying sockets, tapes. |
| 13 | 2.5 Sq.mm |
| 14 | 4 Sq.mm |
| 15 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works. |
| 16 | 20 mm size |
| 17 | Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles(i)19 mm dia 3 mm thick polythene pipe without earth continuity wire . |
| 18 | SUB-HEAD 3-- PLUGS & SOCKETS: |
| 19 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy.connections with PVC Cu wire and earth continuity wire etc. |
| 20 | Supply & Fixing 240 V, 3 Pin 25 A, modular type plug top with indicator (Brand approved by EIC) & necy connections. |
| 21 | ADD GST @18% |
| 22 | ADD LWC @1% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender