Tender for Electro-Mechanical Works To Be Executed At Water Supply Scheme Kachipora Bagathpora (Stage 1St And Stage 2Nd) Under Nabard.
BOQ
| Sl. No. | Item Description |
| 1 | WSS Kachipora Bagathpora (Part-A) |
| 2 | Supply, Installation, Testing & Commissioning of Openwell Horizontal Submersible Pumping Unit as per IS 14220 with latest amendments having the specification as under:- PUMP: Discharge = 1045 LPM Head = 56 m Efficiency = Not less than 50% Speed = 2900 RpmType of pump : Mixed flow. Type of fluid to be handled = Clear Water MATERIAL OF CONSTRUCTION: Impeller = Stainless Steel / Bronze/ chrome steelPump Shaft = Stainless Steel SS 410. Pump Casing = Cast Iron/Stainless steelIMPELLER: Impeller is of the enclosed or semi – enclosed type and properly balanced. Enclosed Impellers equipped with seal rings on their hubs. COUPLING: A suitable coupling arrangement provided with pump set.Non Return Valve: Non Return Valve of the suitable size provided above the pump discharge case.MOTOR:- Method of starting = Star – Delta Speed = 2900 (Sync).Frequency = 50 ± 3 % Hz Working Voltage = 380 -415 ± 15% V, 03 phaseEfficiency = As per IS 9283 (2013) with latest amendments.Rating = Not less than 20HP Class of insulation = F/ BSubmersible motor should be water filled, water lubricated squirrel cage type, working on 3 phase; AC supply ranging from 380 to 415 volts, 50Hz. The motor should be sealed by radial rings to avoid mixing of well water with motor b) The job includes providing and fitting of appropriate size MS nipple 2 feet long threaded on one end and welded to same size MS flange of thickness (as per Table-17) at other end for column pipe as per site requirement. The threaded portion should be as per size of pumping out let for proper fixing.The job includes providing and fitting of R. I. cloth joints/rubber washers with nuts, bolts and washers for all joints of column pipe. The job also includes lowering of pumping unit in the dugwell then proper testing and commissioning of pumping unit on full load at site.Note: Providing of test certificate & Characteristic Curve of pumping equipment is compulsory . |
| 3 | Supply, Installation, Testing & Commissioning of Submersible Pumping Unit as per IS 8034 with latest amendments having the specification as under:- PUMP: Discharge = 900 LPM Head = 74 m Efficiency = Not less than 50% Speed = 2900 RpmType of pump : Mixed flow. Type of fluid to be handled = Clear Water MATERIAL OF CONSTRUCTION: Impeller = Stainless Steel / Bronze/ chrome steelPump Shaft = Stainless Steel SS 410. Pump Casing = Cast Iron/Stainless steelIMPELLER: Impeller is of the enclosed or semi – enclosed type and properly balanced. Enclosed Impellers equipped with seal rings on their hubs. COUPLING: A suitable coupling arrangement provided with pump set.Non Return Valve: Non Return Valve of the suitable size provided above the pump discharge case.MOTOR:- Method of starting = Star – Delta Speed = 2900 (Sync).Frequency = 50 ± 3 % Hz Working Voltage =380 -415 ± 15% V, 03 phaseEfficiency = As per IS 9283 (2013) with latest amendments.Rating = Not less than 20HP Class of insulation = F/ BSubmersible motor should be water filled, water lubricated squirrel cage type, working on 3 phase; AC supply ranging from 380 to 415 volts, 50Hz. The motor should be sealed by radial rings to avoid mixing of well water with motor b) The job includes providing and fitting of appropriate size MS nipple 2 feet long threaded on one end and welded to same size MS flange of thickness (as per Table-17) at other end for column pipe as per site requirement. The threaded portion should be as per size of pumping out let for proper fixing.The job includes providing and fitting of R. I. cloth joints/rubber washers with nuts, bolts and washers for all joints of column pipe. The job also includes lowering of pumping unit in the dugwell then proper testing and commissioning of pumping unit on full load at site.Note: Providing of test certificate & Characteristic Curve of pumping equipment is compulsory . |
| 4 | Fabrication, providing, fitting and lowering of 'B' class column pipe conforming to IS: 1239 of length 10 Rft into the Production Well up to the desired depth; The job includes Providing and welding of flanges conforming to IS: 6392, Table-17 and PN 16 to these pipes and welding of flanges in two layers to make the flanged joint strong and leak proof. The pipe of 10 ft length is to be weld on both sides with flanges using welding rod of reputed make. The job includes all types of skilled labors, arrangement of power supply/ diesel Generator set etc required for the job including P/F of suitable size nuts bolts and R.I Gasket in the flanged joints of column pipes. The job further includes cutting of 2 No. rectangular cable slots in each flange. Any modification to the column pipes /flanges required during lowering is included in the job.Size : DN 100 mm |
| 5 | Carriage, laying & fitting of Departmental Pipe (rising main), excluding cost of pipe & earth work with following description:a) Providing, fitting and welding of M.S Flanges (DN:125mm) conforming to BIS 6392/1997 Table 17 (Rating PN16). The job includes cutting of threaded portion of the pipe from both sides and welding flanges to the newly formed plane ends. The flange welding shall be carried out in double layers using reputed make electrodes to form strong welding joint. DC Arc Welding using welding electrode having diameter not less than 4mm.b) Providing and fitting of galvanized nuts and bolts as per IS:1363 Part 1st, RI Gaskets as per IS: (638/79). c) Carriage of 125 mm dia. B-class G.I. Departmental pipe from Qazigund divisional store to dumping site and then to work site. Job includes cost on account of transportation, loading, unloading, stacking etc.d) Laying & fitting of flanged pipe. Flanged joints are required to be made leak proof by using R.I gaskets of suitable thickness between the joints to make them leak proof. Job also includes all necessary labour work, tools and tackles for completing the job in all manners. Size: DN 125 mm |
| 6 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge. |
| 7 | Earth work in excavation by hydralic means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge. |
| 8 | Filling available excavated earth in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by reaming and watering, lead upto 50 m and lift upto 1.5m. |
| 9 | Fabrication, providing and fitting of split type MS clamps 10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts. |
| 10 | Fabrication, Providing and fitting of 90-120 degree bend/elbow to be fabricated out of Class C GI pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with welded jointson three ends. The job includes nuts, bolts, gaskets etc complete.Size : DN 100 mm |
| 11 | Fabrication, Providing and fitting of 90-120 degree bend/elbow to be fabricated out of Class C GI pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with welded jointson three ends. The job includes nuts, bolts, gaskets etc complete.Size : DN 125 mm |
| 12 | Fabrication, providing and fitting of washout Tee with arm length 1 feet each (Approx). The Tee shall be fabricated out of G.I C-class pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with weld joints on three ends. The size of the Tee is given Below:Size : 125 mm |
| 13 | Fabrication, Providing and fitting of Y- junction having 1m length (Approx.) of each arm to be fabricated out of hot dip galvanized G.I, pipe. The job also includes Providing and welding of M.S flanges to the ends of each arm. The Thickness of flange shall conform to IS 6392 Part 1st Table-17. The flange welding shall be carried out in double layers using reputed make electrodes to form strong welding joint by dint of DC arc welding. The job further includes Providing and Fitting of nuts and bolts (conforming to IS:1363 Part 1st) and Rubber Insertion Gaskets (conforming to IS: 638/79) to be used between flanged joints. The size of the Y- junction is given below:Size : DN 125 mm |
| 14 | Providing, fitting, testing and commissioning of ARV (Air Release valve) as per IS 14845 to be fitted to G.I rising Main. The ARV Shall have the following specifications: - i. Valve type - single chamber, single/double orifice. ii. End connection - flanged ends to IS 1538 iii.Working temperature - 45oc to -150 c iv. Test pressure - body / seat 2.5 x PN v. Sealing ring - EPDM vi. Construction -ductile iron with stainless steel floats vii. Coating - epoxy with corrosion resistance Besides the above works, The job also cost on account of P/F R.I gasket, GI Pipe, nuts and bolts required for installation of ARV and arrangement of gas cutter/ welding set at site.Size : DN 50 mm |
| 15 | Supply, Installation, Testing and Commissioning of Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS 14846 (PN16) in accordance with BS 5163 part 1 and part 2 / EN 1074 Part 1 & 2 for regulating the water supply outside the pumping units. The body and bonnet of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber (Approved for drinking water) and NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions. It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve. The valve shall be supplied along with hand wheel.Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.The job includes providing and fitting of 02 nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job.Size: DN 125 mm Rating: PN 16 |
| 16 | Supply, Installation, Testing and Commissioning of Ductile Iron double flanged, Slanted seat swing check valve (NRV) (PN16) 5312. The body shall be of ductile cast iron with fully encapsulated vulcanized EPDM rubber (Approved for drinking water). The valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions.It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve.Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.The job includes providing and fitting of 02 nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with Rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job.Size: DN 65 mm Rating: PN 16 |
| 17 | Fabrication of gantry mechanism by way of providing Structural steel in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete welded. |
| 18 | Providing, installation and testing of manual type triple spur gear chain pulley block having following features. The main specifications of C.P Block are given below : Capacity = 2 ton (P) No. of load chain falls = 2 or above Min. Height of lift = 6 M |
| 19 | Earth work in excavation required for installation of gantry by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge. |
| 20 | Centering and shuttering including strutting, propping etc. and removal of form work for Foundation, footings, bases for columns. |
| 21 | Providing and laying of stone soling including manual compaction. |
| 22 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size). |
| 23 | Painting of the gantry and plate form of well using one coat of red oxide metal primer and two coats of enamel paint of different shades. |
| 24 | Supply, Installation, Testing and Commissioning of outdoor type Electric Sub Station as per the technical specifications given here under -Specifications conforming to IS: 1180 (Part 1) 2014 with latest amendments.Type: HT/LT Transformer (Level-2)Capacity:- 100 KVAType of cooling: ONAN.Operating conditions:Input =11000 voltsOutput = 433 volts AC supply in 3- phase.Terminals:Input=3 No. HT Brass bush rods with insulators, washer, nuts etc.Output=4 No. LT Brass bush rods switch insulators, washers, nuts etc.Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge. The job includes providing of LT concealed box, cable glands, etc.Transformer Coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved.The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica jel crystals, conservator with oil level indicator, explosion vent and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS: 1180 (Part 1) 2014 with latest amendments. NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment. |
| 25 | Providing and fitting G.I Channel /Angle/ Flat/ V crosses/ F- tops of sizes including clamps. The job includes fitting of Channels on two poles for the installation of insulators and safety devices, GO Set, Lighting Arrestor etc. It also includes the channels for fitting of LT Meter and LT Distribution Box. The job includes P/F of GI channels at Tapping point for installation of GO Link Set, Pin Insulators Etc as per site requirement.Size of Channel= ISMC 75X40MM & ISMC 100x50mm |
| 26 | Supply, Installation, Testing and commissioning of 01 No. Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT pole double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings, operating handle and 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs. The 11 KV AB switches shall conform to IS: 9920 (Part-I to IV).01 No. GO Set is to be fitted at tapping point and 01 No at HT Transformer (Substation). |
| 27 | Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation. |
| 28 | Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type. |
| 29 | Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative, creepage distance 320 mm. |
| 30 | Supply, installation, erection of 9 mtrs long H.T pole of specifications ST- 410 (sp-33) . The job further includes drilling of holes for installation of various accessories, wherever required the job further includes G.I wire earthing of pole as per IEC standard. |
| 31 | P/F of Galvanized nuts bolts of various sizes as per site requirement. |
| 32 | Earth work in excavation required for installation of HT poles by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge. |
| 33 | Centering and shuttering including strutting, propping etc. and removal of form work for Foundation, footings, bases for columns. |
| 34 | Providing and laying of stone soling including manual compaction. |
| 35 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size). |
| 36 | Painting of poles with red oxide. |
| 37 | Painting of poles with Aluminum Paint. |
| 38 | P/F Danger Plate with clamps on every HT pole. |
| 39 | Providing and fixing G.I Barbed wire for anti-climbing/ anti-climbing devices. The barbed wire shall be tightly close wrapped around the pole for 10-12 turns, commencing at 2.50m above the datum line. |
| 40 | Providing and Fitting of PG Clamps. |
| 41 | Supply, Installation, Testing and Commissioning of Galvanized stay set with 50 X 8 mm Stay Clamp, Guy insulator (2 No.), Anchor plate (200X200X6mm), nuts and bolts, 2 No.- turn buckle, 1.8 m long, 16 mm diameter solid G.I stay rod & 7/3.15 mm dia. G.I stranded wire complete. |
| 42 | Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 50sq.mm ACSR (Galvanized steel reinforced) for fitment of various accessories. |
| 43 | Supply, Installation, Testing and Commissioning of LT Distribution box for H.T transformer with 200A MCCB for incomer and 100A SFU for outgoing circuits. The LT distribution Box is to be fitted on GI Channels.Capacity of transformer: 100 kVA |
| 44 | Supply, Installation, Testing and Commissioning of PRODIGY LT Meter of following specification complete with all fixtures required for fitment at site Type: 3 Phase, 4 wire Measurements offered: KWh, KVARh, KVAh, KVAVoltage : 3x240V (415v), 50HZIb : 40A Imax: 200A Battery: LithiumThe Prodigy Meter must be fitted inside the Box, that is to be fitted on GI Channels near LT Distribution Box. Both the enclosures must be symmetrical Sealing /Inspection report of Prodigy meter from JKPDCL (Concerned) is to be submitted by the firm at the time of charging of SUBSTATION. |
| 45 | Fabrication, Providing and fitting of Modular motor control panel of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protectionClass : IP-55 & fitted with accessories as under: a) Bus bar Chamber: The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 200 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between bus bar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards. b) Main Circuit Breaker (Incomer MCCB): Qty. = 02 No.No. of poles = 4 Pole Rated operational voltage = 415 V + 15 % Rated frequency = 50+/-3%Hz Ambient temperature = 40C˚ Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) =50 KA,Type of release = Thermal-MagneticThermal Release Range = 160-200AOverload protection = 0.8 – 1×ln adjustable Short-circuit protection = 6-10×ln adjustable. c) Change over Switch: Qty. = 01 No. Rating = 200 Amp, Type = Front operated, on load, 4 pole, 400 +15%V, 50 + 3%Hzd) Motor Back-up Protection MCCB: Qnty = 2 No. No.of poles = 4 Pole, Current Rating = 84-125 Amp,Rated operational voltage = 415 V +15 % Rated frequency = 50 + 3% Hz Ambient temperature = 40C˚ Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36KA. e) Submersible starters = Fully automatic star delta. Capacity = MU-G 40, Power Specs = 3 Ф, 415 + 15% V, 50 + 3 % Hz. Relay range = 30-50 Amp, Protection = Under voltage/ over Voltage relays (01 No. for each starter)Qty. = 2 No’s f) Auxiliary MCCB for Heating/Lighting: Circuit Breaker = MCCB (Outgoing) Qty. = 1 No. No. of poles = 4P, Current Rating = 63Amp. Rated operational voltage = 415 V + 15 % Ultimate S.C Breaking Cap. at (240V AC, 50 Hz) = 25 KA g) Motor Protection Relay: Digital Motor Protection Relay with LCD Display (MM10) for 3-phase supply with following protections suitable for the Modular Control Panel.Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, over current, Prolong starting, Locked Rotor, Under voltage, over voltage & Earth fault. Qty: 02 No,s 01 for each starter The panel shall be provided with phase indicators (03 No,s) and digital ammeter of range 0-60 A, digital voltmeter of range 0-500 V, and digital frequency meter 01 No for each. The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements.Preferably Make of constituent parts: ABB/Schinider/L&TT/C&S |
| 46 | Supply, Installation, Testing and Commissioning of 40 KVA voltage stabilizer as per specifications below: Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.Type of Regulator : Double plate type with electrolytic copper contacts.Input voltage :170-400 volts.(3 phase)Output voltage : 415 ± 10% volts.Frequency : 50 ±3 C/S.Windings : Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.Insulation : Fiber glass insulations to tested parameters.Cooling : Naturally, Oil cooled (ONAN)Temp. Rise (Max) : 30°C above ambientMounting : On Uni-directional wheels.Correction rate : 40 volts per stepWave form distortion : virtually nilDuty cycle : 100% continuous.Enclosure : MS sheet enclosure in pressed CGR Sheet powder coated with radiators.Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations.Load : Three phase induction motor load.Load Amperes (continuous)Overload in 24-hours operation: 10% above continuous Ampere rating.The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) along with 4-way selector switch and set of neon indicators for incoming and outgoing phases (06 No’s).Insulating media (T. Oil) of 11 KVA grade to be provided and filled up to top level, with dielectric strength of 5 KV at 4m air gap. The T-Oil of specific grade should be provided in separate barrels and filled at site up to top level. |
| 47 | Supply, Installation, Testing and Commissioning of, 3.5-Core, XLPE, 1.1KV and 11KV grade Armoured Aluminium Cable conforming to IS: 7098 part 1st as service line from the HT transformer to control panel including necessary thimbling, crimping, taping etc. (Service line from HT Transformer and D.G Set).i) 50 sqmm, 3.5 core, LT cable |
| 48 | Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipment. The cable connections terminal shall be fitted with copper thimbles of required size. The main specification of the cable is given below:Size :- 16 sqmm |
| 49 | Supply, Installation, Testing and Commissioning of earthing station for electric substation, LT panel and stabilizer comprising of company fabricated GI earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip (25x3mm) as per relevant standards.Safe earthing electrode size : 80 mm dia,Length : 2000 mmBack fill compound : 30 kg |
| 50 | Illumination of Premises:Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 150mm, top 75mm wide, thickness 3mm with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items.1) 3 Way Terminal Connector 20 Amp.2) 3 No MCB 8 Amp.The job includes fabrication, providing and fitting of three arm GI structures at the top having 120˚ angle between arms and each arm having 15˚ inclination with respect to horizontal plane. Each arm should be of 2’ length and size and shape appropriate as per requirement of the luminary.The job also includes providing and fitting of required length of flexible multi strand 2 mm copper wire from each terminal connector to each holding arm.The pole is mounted on 1:2:4 Cement concreting of size not less than 2’x2’x6” (cost of concreting not included in the job) using 04 No anchor bolts of required size not less than 7” in length. The complete job includes earthing in GI Electrode as per relevant IS Code. |
| 51 | Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole. Having following specs:Input: 90-240 V 50 HzPower Factor: >0.9Colour Temperature: 4K - 6.5KBeam Angle: 120˚ - 170˚Lumens: >12000Operating Temperature: -20˚C to 60˚CThe LED is pressure die cast aluminum housing with power coated finish and having Ingress Protection up to IP-68.The LED is properly fitted on the arm of the pole and connected to the copper wire as provided in the high mast pole. |
| 52 | Supply, Installation, Testing and Commissioning of L.T, 1 core, capable to work up to 1.1 KV, with latest amendments to be fitted from modular control panel to stabilizer etc. (interconnecting cable). The job includes providing and fitting of suitable rating copper thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The job includes earth work in excavation wherever required for laying of cable underground. Size: 16 sq mm |
| 53 | Providing and fitting of 02 core, XLPE, 1.1 KV and 11 KV grade Armoured Aluminum Cable of Various sizes confirming to IS:7089 part 1st as service line from HT transformer to Control panel including necessary thimbles, crimping, taping etc.Size: 10 sq mm |
| 54 | Supply, installation, Testing & commissioning of 1050VA Full Sine wave power inverter including Providing / Installation of 12V, 150AH Tubular inverter Battery with trolley and cover with 2-core 4 mm2 Cu (25 m) wiring as per site requirement along with other accessories like SS-Combine (02 No’s), 3-pin plugs etc of reputed make for proper fitment and installation of the item. |
| 55 | Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -Composition: Rubber (synthetic mats for electrical purpose)Thickness: - 2.5mm Size: - 1M wide. |
| 56 | Supply, installation, testing and commissioning of 40 kVA, 3 Phase, 415V AC, Silent DG Set comprising of Engine, with minimum 50 BHP, at 1500 RPM, coupled with alternator and mounted on a common base frame complete with • Fuel tank • Battery & leads • Silencer – Residential • AVM(Anti-Vibration Mounting) pads• Standard control panel• First Fill of lube oil • Acoustic enclosure • Aluminium Power cable ( upto 60 mtr) •Transportation upto Site•CommissioningTECHNICAL REQUIREMENT DIESEL ENGINE Type : The Diesel Engine shall be suitable for generating set application• Developing specified BHP at 1500 RPM under NTP conditions of BS: 5514 or equivalent in IS, Liquid cooled, Turbocharged Inter-cooled, powered by four (4) strokes, multi cylinder with engine performance requirement as specified below. Diesel engines shall be as per MOEF (MINISTRY OF ENVIRONMENT, FOREST AND CLIMATE CHANGE) notification dtd. 3rd November 2022. Only Indian origin Engine is acceptable as per PPP (Public Procurements P-45021/2/2017-PP(BEII)) policy Nominal Output : To match with, alternator 40 kVA at 0.8 pf (lagging) i.e., 32 kW.• Revolution : 1500 rpm• Starting System: 12 V battery operated electric motor starting.• Fuel : High speed diesel oil• Governing Class: G3• Aspiration System : Turbocharged Inter-cooled• Cooling System : Liquid cooled • Lubrication System: As per engine OEM StandardEngine shall meet the following parameters: - The Engine shall be enclosed in an enclosure to make it work silently (as per CPCB IV+ norms) without any degradation in its performance. - The fuel shall be used: High Speed Diesel (HSD) as per IS: 1460. - Filter shall be dry type air filter with replaceable elements. - The Engine shall have closed loop lubricating system. No moving parts shall require lubrication by hand prior to the start of engine or while it is in operation. - The Engine shall be electric starting (by 12 V DC starter motor system for 40 kVA DG Set). - The engine shall be fitted with Governor Class G3Instrument Control Panel shall be furnished for the engine, which shall comprise the following:● Push Button ● Water temp. gauge ● Hour meter with rpm indicator ● Lube oil pressure gauge ● Other item as considered necessary by manufacturer The Instrument Control Panel shall preferably be mounted on the Diesel Generator skid. Otherwise it may be of separately pedestal / floor mounted type.GENERATOR / ALTERNATOR:Alternator with rated output of 40 kVA at STP suitable for continuous operation at 1500 RPM developing 415 volts at 0.8 p. f. (lag) suitable for 50 Hz, three phase, 4 wire system. The alternator shall be brushless type, drip proof, screen protected as per IP-23, self excited & self regulated. The alternator shall conform to IS: 4722. The salient features of the alternator are: +/- 1% voltage regulation in static conditions. IP 23 protection with class ‘H’ insulation Permissible overload of 10% for one hour in 12 hours of operation●Type : Self excited ● kVA : 40 kVA 3 Voltage : 415V, solidly grounded● Phase : 3 phase ● Frequency : 50 Hz ● Power Factor : 0.8 (lagging) ● Excitation System : Brushless exciter ● Insulation Class : Class “H” insulation with temperature limitations for Class-H ● Connection : Star, with neutral terminal wired up to external bushing ●Voltage Regulator : Solid State Electronic typeSTANDARD CONTROL PANEL:The Control Panel shall be fabricated out of steel sheet 1.5 mm thick duly pre-treated and aesthetically finished. It shall be totally enclosed, dust, vermin proof with IP-53 degree of protection as per IS 2147-62. The panel shall consist of following instruments:a) 0 – 600 V, AC Voltmeter of class 1.5 accuracy with phase selector switchb) A.C. Ammeter of Class 1.5 accuracy.c) HRC Fuses of required rating.d) One No MCCB of required rating.e) Frequency Meter.f) Power factor meter.g) Pilot Lampsh) Energy Metrei) Push Button Switch for ON-OFF operation.All the above components shall be properly mounted duly wired and shall be of reputed make.Engine Instrument Panel:The Engine Instrument Panel shall be fitted with starting switch with keys, Lube Oil Gauge, Temperature & Pressure Gauge, Speedometer, Kilowatt Hour Meter etc and all other accessories as required.Safety Control:The D. G. Set shall be provided & fitted with all the safety controls i.e. for Low lube oil Pressure indication switch, High water temperature indication, RPM indication, water temperature indication, battery charging indication etc.Metering ● 3 phase current ● 3 phase voltage ● 3 phase Kilo-watt ● 3 phase KVA ● Kilo-watt hour ● Power factor ● System frequencyStarting BatteryStarting battery shall be furnished along with the set, as per following particulars:i) Type : Lead acid ii) Nominal voltage: 12 V D.C.iii) Capacity : Minimum 1 Nos. of 150 AH battery iv) Mounting: Inside the Acoustic Enclosure. v) Battery: The Battery should be same brand as engine to avail single window service.BASE FRAME (i) The DG set complete with its accessories shall be mounted on a common base frame. (ii) In case the manufacturer recommends vibration isolators for the installation of the equipment, the same shall be included in their scope, in required quantities (iii) AVM Pads as per engine manufacturer standard shall be provided with DG Set.The Acoustic enclosure consisting of the following:- a) Acoustic Insulation: Insulated and noise reduction type, properly clamped shall be provided on all doors, roof and sides to absorb noise. b) Door Locks and Door Hinges: Special designed Stainless steel Door Locks and doors hinges ensuring for smooth operation and long life. c) Residential Silencer: Absorption type non-resistance Residential Silencer insulated from inside with glass wool shall be provided to suppress exhaust noise from the enginePERFORMANCE REQUIREMENT Performance Requirement ● Nominal output of the set : 40 kVA● Rated speed : 1500 rpm ● Rated voltage : 415 volts ● No of phases : 3 ● Rated frequency : 50 Hz ● Overload capacity : 10% for 1 hour ● Over speed withstand capacity : 110% of rated speed for 1 min ● Voltage Regulation : Within +/- 1% of rated voltage from no load to Full load ● Frequency Regulation : Within +/- 4% from no load to full loadTESTS AT SITE DG SET shall be tested at site and diesel (100 Litres) for testing is to be provided by the firm.PACKING ● The materials shall be property packed before dispatch to avoid damage during transport, storage and handling. ● Proper arrangement shall be provided to handle the equipment.INSTALLATION, ERECTION, TESTING AND COMMISSIONING● The generator set, control panel, as well as the neutral of the generator shall be effectively earthed. ● Power cabling upto 60 mtrs shall be done by the contractor. Necessary aluminum power cable, cable glands, cable end lugs, PVC numbering ferrules, tapes etc. shall be supplied and installed by the contractor. In case Power cable beyond 60 mtr is required, then the same will be provided by the department. ● Residential Silencer and The exhaust pipe upto Silencer shall be provided with each DG Set ● The Supplier shall follow occupational health and safety norms, |
| 57 | Supply, Installation, Testing and Commissioning of earthing station for D.G SET comprising of company fabricated GI earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip (25x3mm) as per relevant standards.Safe earthing electrode size : 80 mm dia ,Length : 2000 mmBack fill compound : 30 kg |
| 58 | Fabrication of foundation for DG set of dimensions 4m*3m*1m by providing and laying in position cement concrete with boulders of specified grade including curing but excluding the cost of centring and shuttering all work up to plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size). The job includes necessary earthwork, shuttering soling stones etc. |
| 59 | TOOL KIT For Maintenance: -The Tool Kit for maintenance shall comprise of the following and all the items as mentioned below shall be of Providing of tool kit consists of following items: i. Double ended Spanner (Chrome plated) 01 set complete (6-32) sizesii. Double ended Ring spanners chrome plated 01 set complete (6-32) sizes iii. Cutting plier 9 inch -------1 No.iv. Long nose plier; size in mm 205 – 01 No.v. Insulated screw Drivers 12 inch, 9 inch, 6 inch---------------01 No. eachvi. Hammer 1 kg--------------------01 No. vii. Heavy duty pipe wrench 24 inch -----------------– 01 No. viii. Providing of chain pipe wrench as per IS 4123-1998 (80mm)The job also includes providing of canvas bag/tool box for carrying/storing of tools. 01 No. |
| 60 | Providing of good quality bedding for night stay/Shift consisting of: a) i) Mattress with warm cover size 6'x3' (6Kg)- 02 No’s ii) Quilt with warm cover size 5'x8' (6Kg)- 02 No’s iii) Pillows with covers - 02 No’siv) Single bed warm blankets with one sided Fur- 02 No’s The filling material for mattress, quilt and pillow shall be of good quality cotton b) The job also includes providing of pressure cooker 5 ltr 01 No, Rice cooker 3 ltr 01 No, Steel patella(utensil) 5ltrs 02 No’s, cooking heater 01 No., room heater 01 No., steel buckets 10 litre capacity 01 No., Plastic bucket 10 litre capacity with Mug 02 No’s each, steel glasses 06 No’s, steel Plates with large spoons and bowls 03 No’s each, Cup and Saucer set (01 No. Set) and, 16 kg Gas cylinder with burner/ stove. The job also includes providing of thermo-cool 15’x12’ along with excel matting of 15’x12’ size. The job also includes providing of unbreakable Plastic Chair table set consisting of chairs 04 No’s, extra heavy Table 01 No. c) The job also includes providing of good quality safety Door locks (03 No’s) locks, Providing of solar/electrical lantern (Andslite) chargeable on both solar & electrical 220v supply, |
| 61 | WSS Kachipora Bagathpora (Part-B) |
| 62 | Supply, Installation, Testing & Commissioning of Horizontal Openwell Submersible Pumping Unit as per IS 14220 with latest amendments having the specification as under:- PUMP: Discharge = 730 LPM Head = 30 m Efficiency = Not less than 50% Speed = 2900 RpmType of pump : Mixed flow. Type of fluid to be handled = Clear water MATERIAL OF CONSTRUCTION: Impeller = Stainless Steel / Bronze/ chrome steelPump Shaft = Stainless Steel SS 410. Pump Casing = Cast Iron/Stainless steelIMPELLER: Impeller is of the enclosed or semi – enclosed type and properly balanced. Enclosed Impellers equipped with seal rings on their hubs. COUPLING: A suitable coupling arrangement provided with pump set.Non Return Valve: Non Return Valve of the suitable size provided above the pump discharge case.MOTOR:- Method of starting = Star – Delta Speed = 2900 (Sync).Frequency = 50 ± 3 % Hz Working Voltage =380 -415 ± 15% V, 03 phaseEfficiency = As per IS 9283 (2013) with latest amendments.Rating = Not less than 7.5 HP Class of insulation = F/ BSubmersible motor should be water filled, water lubricated squirrel cage type, working on 3 phase; AC supply ranging from 380 to 415 volts, 50Hz. The motor should be sealed by radial rings to avoid mixing of well water with motor The job includes providing and fitting of R. I. cloth joints/rubber washers with nuts, bolts and washers for all joints of column pipe. The job also includes lowering of pumping unit in the sump then proper testing and commissioning of pumping unit on full load at site.Note: Providing of test certificate & Characteristic Curve of pumping equipment is compulsory . |
| 63 | Fabrication, providing, fitting and lowering of 'B' class column pipe conforming to IS: 1239 of length 10 Rft; The job includes Providing and welding of flanges conforming to IS: 6392, Table-17 and PN 16 to these pipes and welding of flanges in two layers to make the flanged joint strong and leak proof. The pipe of 10 ft length is to be weld on both sides with flanges using welding rod of reputed make. The job includes all types of skilled labors, arrangement of power supply/ diesel Generator set etc required for the job including P/F of suitable size nuts bolts and R.I Gasket in the flanged joints of column pipes. The job further includes cutting of 2 No. rectangular cable slots in each flange. Any modification to the column pipes /flanges required during lowering is included in the job.Size : DN 100 mm |
| 64 | Providing/supplying and fitting of G.I flanged Rising Main–The Pipe shall be hot dip Galvanized pipe confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16). The flanges shall be double welded both from inside and outside of the pipe using standard electrode of reputed make.Flanges (as per IS 6392/1997 Table:17)Thickness shall conform to IS 6392 Part 1st Table-17. The flange welding shall be carried out in double layers using reputed make electrodes to form strong welding joint.Welding ElectrodeDC Arc Welding using welding electrode having diameter not less than 4mm.Nuts and BoltsNuts and Bolts (conforming to IS:1363 Part 1st)Rubber Insertion GasketsRubber Insertion Gaskets (conforming to IS: 638/79) to be used between flanged joints. The main technical specifications of the pipe are given here under:Size: DN 100 mm Class \\"B\\" Medium |
| 65 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge. |
| 66 | Filling available excavated earth in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by reaming and watering, lead upto 50 m and lift upto 1.5m. |
| 67 | Fabrication, providing and fitting of split type MS clamps 10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts.Size : 100 mm |
| 68 | Fabrication, Providing and fitting of 90-120 degree bend/elbow to be fabricated out of Class C GI pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with welded jointson three ends. The job includes nuts, bolts, gaskets etc complete.Size : DN 100 mm |
| 69 | Fabrication, providing and fitting of washout Tee with arm length 1 feet each (Approx). The Tee shall be fabricated out of G.I C-class pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with weld joints on three ends. The size of the Tee is given Below:Size : 100 mm |
| 70 | Supply, Installation, Testing and Commissioning of Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS 14846 (PN16) in accordance with BS 5163 part 1 and part 2 / EN 1074 Part 1 & 2 for regulating the water supply outside the pumping units. The body and bonnet of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber (Approved for drinking water) and NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions. It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve. The valve shall be supplied along with hand wheel.Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.The job includes providing and fitting of 02 nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job.Size: DN 100 mm |
| 71 | Supply, Installation, Testing and Commissioning of Ductile Iron double flanged, Slanted seat swing check valve (NRV) (PN16) 5312. The body shall be of ductile cast iron with fully encapsulated vulcanized EPDM rubber (Approved for drinking water). The valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions.It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve.Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.The job includes providing and fitting of 02 nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with Rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job.Size: DN 100 mm |
| 72 | Fabrication of gantry mechanism by way of providing Structural steel in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete welded. |
| 73 | Providing, installation and testing of manual type triple spur gear chain pulley block having following features. The main specifications of C.P Block are given below: Capacity = 1 ton (P) No. of load chain falls = 2 or above Min. Height of lift = 6 M |
| 74 | Earth work in excavation required for installation of gantry by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge. |
| 75 | Centering and shuttering including strutting, propping etc. and removal of form work for Foundation, footings, bases for columns. |
| 76 | Providing and laying of stone soling including manual compaction. |
| 77 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size). |
| 78 | Painting of the gantry and plate form of well using one coat of red oxide metal primer and two coats of enamel paint of different shades. |
| 79 | Supply, Installation, Testing and Commissioning of outdoor type Electric Sub Station as per the technical specifications given here under -Specifications conforming to IS: 1180 (Part 1) 2014 with latest amendments.Type: HT/LT Transformer (Level-2)Capacity:- 25 kVAType of cooling: ONAN.Operating conditions:Input =11000 voltsOutput = 433 volts AC supply in 3- phase.Terminals:Input=3 No. HT Brass bush rods with insulators, washer, nuts etc.Output=4 No. LT Brass bush rods switch insulators, washers, nuts etc.Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge.The job includes providing of LT concealed box, cable galnds, etc.Transformer Coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved.The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica jel crystals, conservator with oil level indicator, explosion vent and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS: 1180 (Part 1) 2014 with latest amendments. NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment. |
| 80 | Providing and fitting G.I Channel /Angle/ Flat/ V crosses/ F- tops of sizes including clamps. The job includes fitting of Channels on two poles for the installation of insulators and safety devices, GO Set, Lighting Arrestor etc. It also includes the channels for fitting of LT Meter and LT Distribution Box. The job includes P/F of GI channels at Tapping point for installation of GO Link Set, Pin Insulators Etc as per site requirement.Size of Channel= ISMC 75X40MM & ISMC 100x50mm |
| 81 | Supply, Installation, Testing and commissioning of 01 No. Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT pole double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings, operating handle and 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs. The 11 KV AB switches shall conform to IS: 9920 (Part-I to IV).01 No. GO Set is to be fitted at tapping point and 01 No at HT Transformer (Substation). |
| 82 | Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation. |
| 83 | Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type. |
| 84 | Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative, creepage distance 320 mm. |
| 85 | Supply, installation, erection of 9 mtrs long H.T pole of specifications ST- 410 (sp-33) . The job further includes drilling of holes for installation of various accessories, wherever required the job further includes G.I wire earthing of pole as per IEC standard. |
| 86 | P/F of Galvanized nuts bolts of various sizes as per site requirement. |
| 87 | Earth work in excavation required for installation of HT poles by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge. |
| 88 | Centering and shuttering including strutting, propping etc. and removal of form work for Foundation, footings, bases for columns. |
| 89 | Providing and laying of stone soling including manual compaction. |
| 90 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size). |
| 91 | Painting of poles with red oxide. |
| 92 | Painting of poles with Aluminum Paint. |
| 93 | P/F Danger Plate with clamps on every HT pole. |
| 94 | Providing and fixing G.I Barbed wire for anti-climbing/ anti-climbing devices. The barbed wire shall be tightly close wrapped around the pole for 10-12 turns, commencing at 2.50m above the datum line. |
| 95 | Providing and Fitting of PG Clamps. |
| 96 | Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 50 sq.mm ACSR (Galvanized steel reinforced) for fitment of various accessories. |
| 97 | Providing and fitting of anchoring clamps comprising clamp body, plastic wedge, steel bill bracket, straps and buckles or nuts and bolts required for holding (35sqmm). |
| 98 | Supply, Installation and testing of 35 Sq.mm XLPE HT cable (ABC) type of 11 kV grade with cross sectional area of 35 sq,mm i.e. 3 X35, phases red, yellow and blue. |
| 99 | P/F of 11 KV cable termination kit for connecting 35 Sq mm XLPE cable (ABC type) with the existing HT line near tapping point and HT transformer. |
| 100 | Supply, Installation, Testing and Commissioning of LT Distribution box for H.T transformer with 200A MCCB for incomer and 100A SFU for outgoing circuits. The LT distribution Box is to be fitted on GI Channels.Capacity of transformer: 25 kVA |
| 101 | Supply, Installation, Testing and Commissioning of PRODIGY LT Meter of following specification complete with all fixtures required for fitment at site Type: 3 Phase, 4 wire Measurements offered: KWh, KVARh, KVAh, KVAVoltage : 3x240V (415v), 50HZIb : 40A Imax: 200A Battery: LithiumThe Prodigy Meter must be fitted inside the Box, that is to be fitted on GI Channels near LT Distribution Box. Both the enclosures must be symmetrical Sealing /Inspection report of Prodigy meter from JKPDCL (Concerned) is to be submitted by the firm at the time of charging of SUBSTATION. |
| 102 | Fabrication, Providing and fitting of Modular motor control panel of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories as undera)Bus bar Chamber:The busbar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar with a minimum cross-sectional size of each busbar as 25x4 mm2. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 160 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between busbar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards b) Main Circuit Breaker (Incomer MCCB):Qty = 02 No.No. of poles = 4 Pole Rated operational voltage = 415 V + 15 % Rated frequency = 50+/-3%Hz Ambient temperature = 40C˚ Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 50 KA Type of release = Thermal-MagneticThermal Release Range = 108-160AOverload protection = 0.8 – 1×ln adjustableShort-circuit protection = 6-10×ln adjustable.c) Change over Switch:Qty. = 01 No.Rating = 100 AmpereType = Front operated, on load, 4 pole, 400 +15%V, 50 + 3%Hz.d) Motor Back-up Protection MCCB:Qnty = 2 No’sNo. of poles = 4PThermal Release Range = 84-100 ARated operational voltage = 415 V +15 %Rated frequency = 50 + 3% HzAmbient temperature = 40C˚Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36KAe) Submersible Motor starter:Fully automatic submersible motor starters.Rating = MU-G20Power Specs = 3 Ф, 415 + 15% V, 50 + 3 % Hz.Relay range = 9-14 A.Protection = Under voltage/ over Voltage relays (01 No. for each starter)Qty = 02 No’s)f) Auxiliary MCCB for Heating/Lighting:Circuit Breaker = MCCB (Outgoing)Qty. = 1 No.No. of poles = 4PCurrent Rating = 63 Amp.Rated operational voltage = 415 V + 15 %Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 25 kAg) Motor Protection Relay:Digital Motor Protection Relay with LCD Display (MM10 ) for 3-phase supply with following protections suitable for the Modular Control Panel:-Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, Prolong starting, Locked Rotor & Earth fault and over currentQty. = 02 No (01 No. for each starters)The panel shall be provided with phase indicators (03 Nos) and digital ammeter of range 0-60 A, digital voltmeter of range 0-500 V, and digital frequency meter (01 No each). The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements.Preferably make of constituent parts: ABB/Schinider/L&T/C&S |
| 103 | Supply, Installation, Testing and Commissioning of 25 KVA voltage stabilizer as per specifications below: Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.Type of Regulator : Double plate type with electrolytic copper contacts.Input voltage :190-400 volts.(3 phase)Output voltage : 415 ± 10% volts.Frequency : 50 ±3 C/S.Windings : Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.Insulation : Fiber glass insulations to tested parameters.Cooling : Naturally, Oil cooled (ONAN)Temp. Rise (Max) : 30°C above ambientMounting : On Uni-directional wheels.Correction rate : 40 volts per stepWave form distortion : virtually nilDuty cycle : 100% continuous.Enclosure : MS sheet enclosure in pressed CGR Sheet powder coated with radiators.Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations.Load : Three phase induction motor load.Load Amperes (continuous)Overload in 24-hours operation: 10% above continuous Ampere rating.The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) along with 4-way selector switch and set of neon indicators for incoming and outgoing phases (06 No’s).Insulating media (T. Oil) of 11 KVA grade to be provided and filled up to top level, with dielectric strength of 5 KV at 4m air gap. The T-Oil of specific grade should be provided in separate barrels and filled at site up to top level.The voltage Stabilizer shall be accepted with manufacturers dully stamped test certificate and shall have name plate with specifications. |
| 104 | Supply, Installation, Testing and Commissioning of 3.5-Core, XLPE, 1.1KV and 11KV grade Armoured Aluminium Cable conforming to IS: 7098 part 1st as service line from the HT transformer to control panel including necessary thimbling, crimping, taping etc. i) 35 sqmm, |
| 105 | Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipment. The cable connections terminal shall be fitted with copper thimbles of required size. The main specification of the cable is given below:Size :- 10 sqmm |
| 106 | Supply, Installation, Testing and Commissioning of earthing station for electric substation, LT panel and stabilizer comprising of company fabricated GI earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip (25x3mm) as per relevant standards.Safe earthing electrode size : 80 mm dia,Length : 2000 mmBack fill compound : 30 kg |
| 107 | Illumination of Premises:Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 150mm, top 75mm wide, thickness 3mm with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items.1) 3 Way Terminal Connector 20 Amp.2) 3 No MCB 8 Amp.The job includes fabrication, providing and fitting of three arm GI structures at the top having 120˚ angle between arms and each arm having 15˚ inclination with respect to horizontal plane. Each arm should be of 2’ length and size and shape appropriate as per requirement of the luminary.The job also includes providing and fitting of required length of flexible multi strand 2 mm copper wire from each terminal connector to each holding arm.The pole is mounted on 1:2:4 Cement concreting of size not less than 2’x2’x6” (cost of concreting not included in the job) using 04 No anchor bolts of required size not less than 7” in length. The complete job includes earthing in GI Electrode as per relevant IS Code. |
| 108 | Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole. Having following specs:Input: 90-240 V 50 HzPower Factor: >0.9Colour Temperature: 4K - 6.5KBeam Angle: 120˚ - 170˚Lumens: >12000Operating Temperature: -20˚C to 60˚CThe LED is pressure die cast aluminum housing with power coated finish and having Ingress Protection up to IP-68.The LED is properly fitted on the arm of the pole and connected to the copper wire as provided in the high mast pole. |
| 109 | Supply, Installation, Testing and Commissioning of L.T, 1 core, capable to work up to 1.1 KV, with latest amendments to be fitted from modular control panel to stabilizer etc. (interconnecting cable). The job includes providing and fitting of suitable rating copper thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The job includes earth work in excavation wherever required for laying of cable underground. Size: 16 sq mm |
| 110 | Providing and fitting of 02 core, XLPE, 1.1 KV and 11 KV grade Armoured Aluminum Cable of Various sizes confirming to IS:7089 part 1st as service line from HT transformer to Control panel including necessary thimbles, crimping, taping etc.Size: 10 sq mm |
| 111 | Supply, installation, Testing & commissioning of 1050VA Full Sine wave power inverter including Providing / Installation of 12V, 150AH Tubular inverter Battery with trolley and cover. with 2-core 4 mm2 Cu (25 m) wiring as per site requirement along with other accessories like SS-Combine (02 No’s), 3-pin plugs etc of reputed make for proper fitment and installation of the item. |
| 112 | Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -Composition: Rubber (synthetic mats for electrical purpose)Thickness: - 2.5mm Size: - 1M wide. |
| 113 | Providing of good quality bedding for night stay/Shift consisting of: a) i) Mattress with warm cover size 6'x3' (6Kg)- 02 No’s ii) Quilt with warm cover size 5'x8' (6Kg)- 02 No’s iii) Pillows with covers - 02 No’s iv) Single bed warm blankets with one sided Fur- 02 No’s The filling material for mattress, quilt and pillow shall be of good quality cotton b) The job also includes providing of pressure cooker 5 ltr 01 No, Rice cooker 3 ltr 01 No, Steel patella(utensil) 5ltrs 02 No’s, cooking heater 01 No., room heater 01 No., steel buckets 10 litre capacity 01 No., Plastic bucket 10 litre capacity with Mug 02 No’s each, steel glasses 06 No’s, steel Plates with large spoons and bowls 03 No’s each, Cup and Saucer set (01 No. Set) and, 16 kg Gas cylinder with burner/ stove. The job also includes providing of thermo-cool 15’x12’ along with excel matting of 15’x12’ size. The job also includes providing of unbreakable Plastic Chair table set consisting of chairs 04 No’s, extra heavy Table 01 No. c) The job also includes providing of good quality safety Door locks (03 No’s) locks, Providing of solar/electrical lantern (Andslite) chargeable on both solar & electrical 220v supply. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 16, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 30, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysOct 31, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender