Drinking Water Supply and Sanitation Government Departments Closing in 10 days TDR #58079311

Tender For providing Fixing Pvc Pipe, Construction Of Masonry Sluice Valves Chamber, Sewerage System, Rising Main, Construction Of Ugsr, Tubewell, Electrical Panel Etc At Govt I.T.I Buildings (G+5) At Nangal Distt Roopnagar (Public Health Services).

Issued by Government Departments · Rupnagar, Punjab
Tender Value
1.89 Crore
Estimated cost
Bid Submission
29 Oct 2026
10 days left
EMD
3.79 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Rupnagar → Punjab
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for providing Fixing Pvc Pipe, Construction Of Masonry Sluice Valves Chamber, Sewerage System, Rising Main, Construction Of Ugsr, Tubewell, Electrical Panel Etc At Govt I.T.I Buildings (G+5) At Nangal Distt Roopnagar (Public Health Services). (Under Head Eds-80 School Of Eminence

BOQ

Name of Work:- Prov. Fixing PVC pipe, Construction of masonry Sluice valves chamber, Sewerage System, rising main, Construction of UGSR, Tubewell, Electrical Panel etc at Govt I.T.I Buildings (G+5) at Nangal Distt Roopnagar (Public Health Services). (Under Head EDS-80 School of Eminence
Sl. No. Item Description
1Sub head-1 Estate Water Supply distribution system
2Excavation manually in trenches for pipe lines with straight or open cutting in streets and lanes in builtup area where width of street / Lane from wall to wall is less than 3 meter including trimming and dressing sides levelling of beds of trenches to correct grade, cutting joint holes, refilling consolidation, watering, including the cost of dewatering of rain water, diversion for traffic, night signals. Providing & fixing caution boards, watching, fencing, etc. and removalof surplus soil from the site upto 15 meter distance complete in all respects.
3Providing, Laying , fixing & jointing of P.V.C. Pipes as per iSi-4985 (iSi marked with the prior approval of Engineer-in-Charge) along the Trenches and laying the same in Trenches to correct alignment and gradients, cutting, jointing and testing complete as per specifications.
490mm o/d pipe of 6 Kgf. / sqcm
5Providing & fixing C.I/D.I Flanged end, stem of SS (AIS 1410) and Bronze(gunmetal) working parts Sluice Valves ISI marked 14846-2000, including jointing , testing & cost of Nut, Bolt & insertion sheet, all carriage complete (with the approval of Engineer incharge).
680mm i/d sluice valve flanged
7Construction of masonary Sluice Valve Chamber excluding Sluice valve cover as per standard design & drawings of public health department.
8Size 0.9 m. x 0.9 m.
9Sub head-2 Estate Sewerage System
10Excavation by mechanical means (JCB or Hydraulic excavator) in trenches for pipe lines with straight or open cutting in streets or open area including trimming and dressing sides levelling of beds of trenches to correct grade, cutting joint holes, refilling consolidation,watering, including the cost of dewatering of rain water, diversion for traffic, night signals. providing & fixing caution boards, crossing over trenches for access to the houses, watching, fencing, etc. and removal of surplus soil out side/inside the town involving lead upto 15 meter complete in all respect.
11Depth not exceeding 3 m. BGL
12For Ordinary Soil having gravel 40%
13160 mm pipe
14Providing and fixing in position singel socket SWR UPVC soil waste or antisyphonage pipes as per IS 13592 of E.D.C manufacture or of any other reputed firm including cutting, jointing, wastage, but excluding cost of jointing.
15Single socket type B
16160mm o/d single socket SWR UPVC pipe lines laid complete IC TO MH
17Sand filling under floor and in wells of bridge foundation including handling withing 100 metres
18Constructing brick masonry manhole in cement mortar 1:5 ( 1 cement : 5 coarse sand ) R.C.C. top slab 20cm thick using M-20 mix by using mixer and vibrator, TMT Fe500 @ 80.00 kg/per cum, foundation concrete 1:4:8 mix (1 cement: 4 coarse sand : 8 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement: 3 coarse sand) finished with floating coat of neat cement and making 40mm thick benching in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement, Orange coloured PVC steps including RCC cover with frame complete as per standard design complete in all respects.
19Inside size 90x150 cm and 120 cm deep
20Providing, laying in trenches to correct gradient and alignment and jointing of UPVC pipes having ISI specification IS:15328-2003 class-SN-8 marked make Supreme, Finolex, Kissan, Jain, Prince or equivalent good on them and laying the same in trenches to correct alignment and gradients, cutting and jointing, testing for water tightness and making good the leakages and defects including cost of specials (Specials and Solvent should be of same make as that of pipes) complete in all respects.
21200mm o/d pipe
22Sub head- 3 Strome sewer System with Recharge well
23Providing, Laying , fixing & jointing of P.V.C. Pipes as per ISI-4985 (ISI marked with the prior approval of Engineer-in-Charge) along the Trenches and laying the same in Trenches to correct alignment and gradients, cutting, jointing and testing complete as per specifications.
24200mm o/d PVC pipe of 4 Kgf. / sqcm
25Supplying, fixing and jointing PVC / H.D.P.E pipe's specials complete as desired by Engineer-in-Charge. For pipe lines laid inside habitation
26Top Khurra 0.6mx0.6m for rain water pipe in 25mm thick cement concrete 1:2:4 over 50.00 thick cement concrete 1:8:16
27Excavation in trenches with straight or open cutting in a street, lanes or in a open area with 3D/JCB or excavator including manually dressing bed, trimming sides & slide slope for sewer & manhole to full depth as shown in drawing, including, dressing to correct sections and dewatering, provision for diversion for traffic,protection of existing services i.e. telephone cables ,electric lines, water supply lines and gas lines etc. night signals, profiles, pegs, sight rails, boning rods, watching etc. fixing and maintenance of caution boards, fencing, refilling trenches, watering, ramming and restoration of surface to original level removal of surplus spoils from the site of works upto chain (15 m), complete in all respects.
28For depths not exceeding 3.0 metre B.G.L.For all classes of soil except rocky
29Storm water Line 200 mm i/d pipe
30Construction of Haudi internal size 0.90 mtr. x 0.90 mtr. & 0.90 mtr. depth in Brick masnory 1:5 bed 40mm thick cement 1:2:4, 150mm thick base lean concrete 1:8:16, RCC slab cover 75 mm thick inside plaster, cement rendering & RCC man hole cover 450x450mm clear inside opening rectangular RCC Manhole cover with frame light duty.
31Providing, Laying, Houdies prior approval of Engineer-in-Charge) Haudies (Size 0.45 Mtr x 0.45 Mtr.)
32Providing, Laying , fixing & jointing of P.V.C. Pipes as per ISI-4985 (ISI marked with the prior approval of Engineer-in-Charge) along the Trenches and laying the same in Trenches to correct alignment and gradients, cutting, jointing and testing complete as per specifications.
33110mm o/d PVC pipe of 4 Kgf. / sqcm
34160mm o/d PVC pipe of 4 Kgf. / sqcm
35Supplying, fixing and jointing PVC / H.D.P.E pipe's specials complete as desired by Engineer-in-Charge. For pipe lines laid inside habitation
36Sub head- 4 Recharge well
37Construction of Recharge well 4.5mtr dia up to 4 mtr depth 1 No. ,installation of 200mm i/d tubewell up to 50 mtr depth complete in all respects.
38Boring with casing pipe for tubewell in all soils except ordinary hard rocks requiring blasting including removing the casing pipe after the tube well is lowered & tested, equipment as requried such as hand boring machine and its accessory, transportation to site and vice versa etc. complete in all respect.
39From bottom of wellBoring with 300mm id Housing Pipe
40Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818-2010, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer – incharge. 200mm nominal size dia
41Bore well
42Collecting chamber to well
43200 mm nominal size dia.
44Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS:12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge.200mm nominal size dia
45Supplying & Fixing of M.S pipe bail plug suitable for 200 mm dia UPVC casing pipe having thickness of socket as 12 mm, length 100 mm & base plate of 8 mm thick complete in all respect.
46Supplying & fixing of M.S Clamp of size 150mm X 12mm made out of MS Flat 1.52m long, suitable to fit Housing pipe including the cost Nut & Bolts of Suitable size complete in all respect.
47Supplying, lowering & fixing of M.S Special socket to connect S.S Strainer to M.S Pipe duly welded with suitable grade welding electrode complete in all respect. 200mm internal dia
48Supplying at site Wooden Box of suitable size with Lid & locking arrangment for preserving strata sample collected from the bore.
49Supplying & Fixing of well cap having thread to fix on housing pipe complete in all respect.200mm internal dia
50Foot Rest for Manhole.Providing orange colour safety footrest of minimum 6mm thick plastic encapsulated as per IS:10910 on 12mm dia steel bar confirming to IS: 1786 having minimun cross section as 23mm x 25mm and over all minimum length 263mm and width as 165mm with minimum 112mm space between protruted legs having 2mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specification and having manufacturer's permanent identification mark to be visible even after fixing, including fixing in manholes with 230x150x75cm cement concrete block 1:2:4 (1 cement: 2 sand: 4 stone aggragate) complete as per design.
51Earth work in excavation in foundations trenches etc. in all kinds of soil where Pick-Jumper work is not involved and not exceeding 2.0 metres depth including dressing of bottom and sides of trenches, stacking the excavated soil clear from the edge of excavation and subsequent filling around masonry in 15 cm, layers with compaction including disposal of all surplus soil as directed within lead of 30 metres.
52Cement concrete 1:2:4 with stone ballast or shingle using concrete mixer volumetric type
53First class burnt brick work laid in cement sand mortar 1:5 in first storey upto 4 metres above plinth level.
54Extra for specially moulded brick work in circular work such as well shafts circular sumps, pump chambers etc. in which specially moulded or cut bricks have to be used but for which no centring or supports are required upto 4.5 metre internal diametre.
5512.5 mm thick cement plaster 1:2
56Providing and placing in horizontal layers filtering media screened, washed and cleaned as described below:- Bottom Layer :----- Broken stone, screened, cleaned and washed and graded from 50mm to 75mm (from Pathankot or approved equivalent quarry).
571st layer
58Bajri (Coarse) screened, cleaned and washed and graded from 20mm to 25mm (from Pathankot or approved equivalent quarry).
592nd Layer
60Third Layer :----- Bajri screened,cleaned and washed and graded from 6mm to 20mm (from Pathankot or approved equivalent quarry).
613rd Layer
62Second Layer :----- Coarse sand screened, cleaned and washed and graded from 3mm to 6mm (from Pathankot or approved equivalent quarry).
634th Layer
64Reinforced cement concrete M-20 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
65Deduct Man Hole
66Centering and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc.
67Outer Face Of Slab
68Man Hole Inner face
69Cold twisted detormed (Ribbed/ Tor steel) Bars (Fe 500 grade as per IS 1786-2008) , for R.C.C works, where not including in the complete rate of RCC including bending and binding placing in position complete
70Providing and fixing RCC manhole covers 560mm i/d heavy duty
71Wrought iron & Mild steel ladders, framed grills, gratings etc. with ends of bars riveted or molded forged framed window guards, barred iron doors stair case iron railing etc. including cost of bolts and nuts, screws, welding rod complete fixing in position
72Angle
733.5 kg/mtr
74Flats 30x5 strips 1 1/2\\" C/C
751.2kg./mtr
76Central angle for openable shutter
773.5 kg/mtr
78Total A+B+C:-
79Sub Head -5 Tubewell
80Drilling of 400mm dia bore with Direct Rotatry Rig in all kinds of soil including the cost of consumable stores, fuel oil and transportation of rig to the site. complete in all respect.a)Drilling of 400mm dia bore with Direct Rotatry Rig Upto 200 m depth BGL.
81Supplying & lowering MS Pipe as per IS 4270-2001 including MS sockets having dimensions as per IS code duly welded with MS electrode to have extra strenght to lower the pipe into tubewell bore.
82200mm nominal diameter (weight 33.6 kg per metre) 6.4mm thickness
83Supplying, fixing lowering of Stainless Steel Cage type wire wound screen as per IS:8110-2000 or latest ISI Marked,duly welded with suitable grade S.S welding electrode to lower the strainer into tubewell bore.
84200mm Steel Strainer (slot size 0.75mm) 6.30 mm thickness
85Supplying and fixing of bail plug of M.S. Pipe complete with inverted U-hook attached to the bottom plug complete in all respects.
86200mm internal diameter (Weight 33.6 kg per meter) 6.4 mm thickness.
87Supplying & fixing mild steel centering guides made out of 32mm x 6mm thick M.S. bar complete in all respects.
88Supplying and fixing of well cap having threads to fix on housing pipe complete in all respects.
89200mm internal diameter
90Supplying and fixing M.S. Clamps of size 150mm x 12mm made out of MS Flat 1.52m long, suitable to fit Housing Pipe including the cost Nut & Bolts of Suitable size complete in all respects.
91Supplying, fixing and lowering of stainless steel socket as per IS 8110: 2000 or latest, ISI marked duly welded with suitable grade SS welding electrode to lower the strainer into tubewell bore complete in all respects.
92200mm internal diameter
93Supplying at site wooden box of suitable size with Lid & lockign arrangement for preserving strata sample collected from the bore.
94Supplying at site of gravel of 1/16\\" to 1/8\\" sizes including pouring and packing in the annular space between the pipe assembly and the bore. The gravel should be free from, dust, dirt, or the vegetable manner as per IS 4097/1967 with latest amendments (to be paid as per actual length of pipe)
95Development and stabilizing of the tubewell with Air compressor or required capacity as directed by the engineer-in-charge including cost of tools, appliances & consumable to the satisfaction of Engineer-in-charge.
96Capacity of Air Compressor 300 cfm at 250 PSI
97Development and stabilizing of the tubewell with submersible pump of required capacity as directed by the engineer-in-charge including cost of tools, appliances & consumable to the satisfaction of Engineer-in-charge.
98Collection of water sample from different strata and testing of sample from approved laboratory (Physical & chemical Analysis)
99Testing of water sample for Heavy metal fromapproved laboratory (Toxic material such asArsenic, lead, mercury, pesticide uranium etc.)
100Making electric Logging of borehole with electronic well logger including cost of equipment at site etc.complete in all respect
101Supplying at site Tibba sand etc. including pouring and packing in the annular space between the pipes assembly and the bore above clay seal complete in all respect.
102Providing & Fixing Clay seal in graval pack minimum 3 Mtr.(As per BIS Code 2800:2019)
103Providing & Fixing Sanitery Seal (As per BIS Code 2800:2019)
104Sterilization of Well (As per BIS Code 2800:2019)
105Providing, installing, testing and commissioning of 1 no. Electrically driven pumping set of reputed make, capable of deleviring 131lpm against a head of 62mt . Complete in all respects. (5HP )
106Supplying lowering of 65 mm dia GI pipe as per IS 1239 (B - class) premim make such (as Jindal Hisar) including cost of specials such as tees, bends, sockets elbow etc, cutting, treading and testing in trenches in the ground. Complete in all respects
107Providing and fixing of submerssible of mm 2.5 mm² core cable, complete in all respect
108Providing installing, testing and commissioning of 1 no. control panel with closed transition star delta with enclosure consisting of electrical appliances such as contactor, furses, MCCB's over load relays, isolator switches wiring and connnections. Complete in all respect.
109C.I FITTING INSIDE PUMP CHAMBER
110Providing and installing 80mm dia delivery main (From Tube well to Duck Foot bend including cost of C.I/D.F Pipes, D/F Sluice valves, D/F NRV & Specials as C.I Bends, Tail Piece Tees etc.. inside the pump room as per standard design complete in all respects (Analysis attached)
111Construction of V- Notch Houdi (Size 1.80 x 0.90 m) including cost of v – notch as per standard design & drawings of Public health Department.
112Providing, installing, testing and commissioning of 1 no. Electrically driven centrifugal pumping set of reputed make, capable of deleviring 450 lpm against a head of 60 mt . Complete in all respects. (7.5 BHP) (One working +one standby)
113Providing and laying, jointing, fixing, testing ISI Marked G.I. Pipe (as per IS 1239) B- Class, including cost of Specials such as tees, bends, sockets elbow etc., cutting, threading and testing in trenches in the ground complete. 65mm i/d
114Providing and fixing of submerssible of mm 2.5 mm² core cable, complete in all respect
115Providing installing, testing and commissioning of 1 no. control panel with closed transition star delta with enclosure consisting of electrical appliances such as contactor, furses, MCCB's over load relays, isolator switches wiring and connnections. Complete in all respect.
116Providing and installing 80mm dia delivery main (From UGSR to Centrifugal pumps including cost of C.I/D.F Pipes, D/F Sluice valves, D/F NRV & Specials as C.I Bends, Tail Piece Tees etc.. inside the pump room as per standard design complete in all respects
117PUMPING MAIN (RISING MAIN)
118Providing, Laying , fixing & jointing of P.V.C. Pipes as per ISI-4985 (ISI marked with the prior approval of Engineer-in-Charge) along the Trenches and laying the same in Trenches to correct alignment and gradients, cutting, jointing and testing complete as per specifications including excavation. (Manually) (Analysis attached)
11975mm o/d pipe of 10 Kgf. / sqcm
120Sub head-6 Installation of Water coolers and RO System
121Providing & fixing in position Water Cooler without Stablizer of approved make (to the approval of Engineer-in-charge ) including carriage complete in all respect.
122Water Cooler Semi Steel Body 80/120 ltr Capacity without Stablizer
123Providing & fixing in position RO of approved make (to the approval of Engineer-in-charge ) including carriage complete in all respect.
124Sub Head-7 Installation of AC
125Providing and installing Hitachi/ O-General/ Carrier/ Mitsubishi/ Toshiba make 5-Star Inverter model (with installation kit i.e. 3 Mtr. Copper Pipe, copper cable from OD to ID etc) or any other equivalent make Split type Air Conditioner of 1.5 Ton capacity suitable for 230 Volts single phase supply with nature friendly refrigerant R32 or equivelant capable of performing the following functions :- (i) Cooling (ii) Dehumidifying (iii) Air Circulation (iv) Filtering including installation charges. Cooling capacity minium 600 W
126Providing and installing Hitachi/ O-General/ Carrier/ Mitsubishi/ Toshiba make 5-Star Inverter model (with installation kit i.e. 3 Mtr. Copper Pipe, copper cable from OD to ID etc) or any other equivalent make Split type Air Conditioner of 2.0 Ton capacity suitable for 230 Volts single phase supply with nature friendly refrigerant R32 or equivelant capable of performing the following functions :- (i) Cooling (ii) Dehumidifying (iii) Air Circulation (iv) Filtering including installation charges.
127AUTOMATIC VOLTAGE STABLIZER:
128Supply and erection of Single phase copper wound Automatic voltage stablizer of suitable capacity electronically controlled circuit with input voltage 140-260 volts single phase AC supply and output voltage 220 ± 5% volts single phase AC supply having main silicon core copper wound step up transformer with suitable nos. of turns on primary side and secondary side the transformer should be fully insulated inside the MS sheet box of suitable size. There should be power control relay and single pole MCB (C-curve, 10kA) of suitable capacity complete with internal copper wiring along with amp. meter and volt meter, high voltage cut off 280 volt input (240 volt output) and 90 volt maximum boost and overloading protection to be provided
129Automatic Voltage Stablizer 4 KVA
130Automatic Voltage Stablizer 5 KVA
131Providing and fixing angle iron stands for placing outdoor units.
132Drain Water piping Providing, laying, jointing, fixing and testing ISI Marked uPVC Pipe with G.I. specials as per ISI-4985, including cost of G.I. specials such as tees, bends, sockets, elbows etc. testing inside building complete. (25 mm nom. Dia)- for Split Ac 25mm = 3 mtr. each(94 No. x 3 mtr. = 282 Mtr.)
133uPVC Pipe 10 Kgf/cm2
13425mm i/d
135Providing & fixing Copper Refrigerant pipe (in addition to the default 3 mtr. Length already provided with each AC) = 4 meter each 94 x 4 = 376 meter
136Sub head-8 Construction of UGSR 70,000 ltr capacity for Fire Fighting system and Drinking water
137Earth work in excavation of foundations of bridges culverts, buildings including handling of material with a combined lead of 15 metres dressing of bed and sides stacking the excavated soil from the edge of excavation and subsequent filling
138For ordinary gravel soil involving pick work
139Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
140Centering and shuttering for faces of walls, partitions, retaining walls and the like (vertical or battering including attached pilasters buttresses etc.
141Cement concrete 1:4:8 With stone aggregate 40mm gauge mixing by mechanical means using concrete mixer volumetric type
142(carrage material drive rate)
143Reinforced cement concrete M-25 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centering and shuttering in foundation and plinth
144First class burnt brick work laid in cement sand mortar 1:6 in first storey upto 4 metres above plinth level.
145Door area for motor room
146(carrage material drive rate)
147Providing & laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry cost of neat cement using 2.75 kg/Sqm. of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer- in- charge over the RCC slab including adjoining walls upto 300mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/ brick bats 25mm to 115mm size with 50% of cement mortar 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS: 2645 and approved by Engineer-in-charge over 20mm thick layer of cement mortar of mix 1:5 ( 1 cement L5 coarse sand) admixed with water proofing compound conforming to IS :2645 and approved by Engineer.
148Providing and fixing 1st quality ceramic glazed wall tiles Matt/Semi Matt/Glossy/Highly Gloss finish/Highlighter/emboss conforming to IS : 15622 (thickness to be specified by the manufacture of approved make in all colours, shades except burgundy, bottle green, black of size 200 x 300 mm, 100x200mm, 200x200mm as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:4 (1 cement: 4 fine sand) and jointing with grey cement slurry @ 3.3kg per Sqm including pointing in white cement mixed with pigment of matching shade complete.
14912.5 mm thick cement plaster 1:5 Walls
150Preparation of plastered or concrete surface for painting (including sand papering the surface) using Acryllic Wall Putty by applying two or more coats to get required finish including priming coat to make an even surface before applying Acrylic wall putty on new plastered surface. Complete as per specifications
151Supplying and fixing of Japani sheet frames (Chowkat) consisting of 18 gauge (1.25mm) thick steel sheet of the specified section (standard design latest), including iron lugs (hold fasts) iron hinges conforming to PWD specifications including bolts for fixing steps, lock notch provision for receiving tower bolts and finished, fixed in position including the cost of cement concrete 1:3:6 for filling in the frame and cement concrete 1:2:4 for lugs complete to the satisfaction of Engineer-in-charge.
152Doors and windows frame of size 151mm x 60mm with 35 mm wide double rebate weighing 3.95 kg per meter.
153Factory manufactured solid flush door fixed in position iron hinges, etc (excluding the cost of any fittings other than specified above but including labour for fixing the same in position (Code: IS 2202-1 (1999)
15435mm thick
155Wire gauge Hollock wood door shutter without springs housed in chowkhat 35mm thick
156Providing and fixing aluminum sliding door bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS :1868) transparent or dyed to required colour or shade with nuts and screws etc. complete :250mm x 16mm
157Providing & Fixing glass panes with nails and putty or wooden strip complete in all respect 4mm thick or 10.78 Kg/ sqm
158Wrought iron & Mild steel ladders, framed grills, gratings etc. with ends of bars riveted or molded forged framed window guards, barred iron doors stair case iron railing etc. including cost of bolts and nuts, screws, welding rod complete fixing in position
159Cold twisted deformed (Ribbed/ Tor steel) Bars (Fe 500 grade as per IS 1786-2008) , for R.C.C works, where not including in the complete rate of RCC including bending and binding placing in position complete
160Providing & fixing 560 mm, 500 mm and 450 mm internal diametre circular or 450 mm x 600 mm clear inside opening rectangular RCC manhole cover and frame ISI marked as per IS:12592-2002 including carriage from the stores of the Engineer-in-charge to site of work, loading, unloading including stacking and setting the same to correct lines over manholes including cement concrete copping (M:20) around the frame etc. Dia of steel for lifting hook is 16mm. (for EHD and HD).560mm i/d RCC man hole cover with frame as per ISI
161Supplying, fixing and testing at site Automatic electronic type water level indication system with gun metal float sensor and electrical cable suitable for three phase pump submersible / monoblock to be fixed on existing panel for OHSRs complete in all respects.
162Sub head-9 Internal and External Fire Fighting Arrangment including Hydrant,Fire Extinguishers & UGSR Main Pumps as per NBC Norms
163MAIN PUMPSET FOR HYDRANT SYSTEM
164Supplying, installation, testing & commissioning of approved make horizontally mounted coupled motor (Eff-1) 60hp, 2900 RPM, 3 Ph 415 V with mechanical seal pump delivery of 2280 litres per minute against total head of 70 meter so as to ensure a minimum pressure of 3.5 Kg/Cm2 at the highest. The impeller shall be closed type and accurately balanced dynamically. The pump shall be of cast iron, impeller shall be of bronze and shaft shall be of stainless steel, automatic air release valve, pressure gauges (combination suction gauge, 3½” dial type with ¼” cock and lever handle - 1 no, discharge gauge, 3½” dial type with ¼” cock and lever handle - 1 no.) i/c coupling, coupling guard, base channel foundation &matching flanges etc. as required as per specifications. The fire pump set as per NFPA –20 specifications.
165Common bed plate of fabricated mild steel channel or cast iron type.
166Suitable reinforced cement concrete pump foundation including cushy foot mounting, foundation bolts, washers as required.
167The pump shall be of the following specifications:
168Discharge - 2280 lpm
169Head - 70 m
170No. of stage preferred - Single / Double
171Speed RPM - 2900
172Material of construction
173a) Impeller - Bronze
174b) Casing - C.I.
175c) Shaft & Shaft Sleeve - SS-410
176d) Bearing - Grease Lubicated
177Type of pump - End suction
178JOCKEY PUMPSET
179Supplying, installation, testing & commissioning of approved make jockey pump horizontally mounted coupled motor (Eff-2) 5.5hp, 2900 RPM, 3 Ph 415 V with mechanical seal pump, delivery of 180 litres per minute against total head of 70 / 88 meter so as to ensure a minimum pressure of 3.5 Kg/Cm2 at the highest. The impeller shall be closed type and accurately balanced dynamically. The pump shall be of cast iron, impeller shall be of bronze and shaft shall be of stainless steel. i/c coupling, coupling guard, base channel foundation & matching flanges etc. as required as per specifications
180Common bed plate of fabricated mild steel channel or cast iron type.
181Suitable reinforced cement concrete pump foundation including cushy foot mounting, foundation bolts, washers as required.
182The pump shall be of the following specifications:
183Discharge - 180 lpm
184Head - 70 m
185No. of stage preferred - Multistage
186Speed RPM - 2900
187Mover - Electric Motor Driven
188Material of construction
189a) Impeller - Bronze
190b) Casing - C.I.
191c) Shaft & Shaft Sleeve - SS-410
192d) Bearing - Grease Lubicated
193Type of pump - End suction
194DIESEL ENGINE
195Supplying & installation of approved make diesel engine driven firefighting pump water cooled 65 BHP 2150 RPM engine, fuel tank 200 Ltr (empty), accessories, matching flanges, base frame, ARV , fuel gauge, exide12 Volt battery & charger, lugs & cable between battery & charger. The pump capacity of 2280 litres per minute at total head 70 meters, automatic air release valve, pressure gauges (combination suction gauge, 3½” dial type with ¼” cock and lever handle - 1 no, discharge gauge, 3½” dial type with ¼” cock and lever handle - 1 no.) as required. All above equipment's are mounted on common base plate. The fire pump set as per NFPA –20 specifications.
196Horizontal end suction centrifugal pump complete with mechanical seal and including necessary arrangement for testing of pump.
197Flexible coupling and coupling guard with the Pump,
198Common bed plate of fabricated mild steel channel or cast iron type.
199Suitable reinforced cement concrete pump foundation including cushy foot mounting, foundation bolts, washers as required.
200Engine panel
201Sealed maintenance free batteries of 24 V, 88 AH
202Exhaust pipe of required length with asbestos lagging, muffler
203Day oil tank of 400 lts with first charge and manual oil pump set.
204The pump shall be of the following specifications:
205Discharge - 2280 lpm
206Head - 70 Mtr
207No. of stage preferred - Single / Double
208Speed RPM - 2150 RPM
209Mover - Diesel engine driven
210Material of construction
211a) Impeller - Bronze
212b) Casing - C.I.
213c) Shaft & Shaft Sleeve - SS-410
214d) Bearing - Grease Lubicated
215e) Type of pump - End Suction
216AIR CUSHION TANK
217Supplying & fixing air vessel made out of 250mm. Dia, 8 mm thick MS sheet, 1200mm height with air release valves on top and flanged connection to risers, drain arrangements with 25 mm dia gunmetal wheel valves, with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required
218ELECTRICAL PANEL
219DSupplying, installation, testing & commissioning of cubical type floor mounted electrical control panel of 2.0 mm thick CRCA sheet suitable for 380-415 Volt, 50 Hz, 3 Ph supply, NEMA type 2 (IP 31) drip proof metal free standing enclosure for firefighting pumps with suitable star-delta starter including indicating lamps, ammeter, voltmeter, selector switches for each, incoming and outgoing feeder, auxiliary switches, dry suction cut off, single phase preventer, alu. bus bar etc. The panel shall be provided with interlocking arrangement between electric motor driven and dieselengine driven pumps so that only one pump can operate at one time and in case of any failure in electric motor driven pump the diesel engine driven pump shall operate automatically. The installation shall include all control wring, accommodation for battery charger etc. and connections as required
220Incoming :1. No. 250 Amp 4 Pole MCCB, 35 KA 1 Set 300 Amp, 500V capacity 4 Nos. aluminium bus bar with epoxy insulator, heat shrink sleeve, required hole, nut bolt etc. 1 No. 96x 96 mm 0 to 500 Volt voltmeter selector switch and HRC fuse with base. 1 No. 96x 96 mm 0 to 300 Amp ammeter, selector switch and CT 1Set –3 nos. indicating lamp with HRC fuse and base Out goings :2 Nos. 200 Amp 4 Pole MCCB,25 KA2 Nos. 63 Amp 4 pole MCCB,10 KA.1 No. fully automatic star delta startersuitable for main pump motor I/C CT, ammeter with selector switch & control with pressure switch, pump ON indicating lamp.1 No. DOL starter suitable for jockey pump motor I/C CT, ammeter with selector switch. & control with pressure switch complete
221Necessary cable alleys space for switches, internal wiring and copper earthing of all equipment willll also be included. All switch gears/control gears will be motor duty rating.
222CABLES
223S/E of LT Cast Resin type/ Heat Shrinkable Termination Kit for Outdoor/ Indoor supply of 1.1 KV grade PVC/XLPE cable as desired by the Engineer incharge of the site:-
224Heat Shrinkable Outdoor/ Indoor End Termination Kit for Cable Size 3½/4 Core 25-50sq.mm
225Heat Shrinkable Outdoor/ Indoor End Termination Kit for Cable Size 3½/4 Core10-16sq.mm
226PVC INSULATED PVC SHEATHED FR ROUND FLEXIBLE COPPERCONDUCTOR CABLE: Supply and erection of PVC insulated PVC sheathed FR (2Core) round flexible wire with copper conductor cable (ISI marked) confirm to IS:694/1990 left bare in pipe or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:- Overall size 2.5sq.mm (50/0.25mm), 2Core
227PVC INSULATED PVC SHEATHED FR ROUND FLEXIBLE COPPERCONDUCTOR CABLE: Supply and erection of PVC insulated PVC sheathed FR (2Core) round flexible wire with copper conductor cable (ISI marked) confirm to IS:694/1990 left bare in pipe or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:- Overall size 1.5sq.mm (48/0.20mm), 2Core
228PRESSURE SWITCH
229Providing and fixing of Pressure switch of approved make in MS pipe line suitable for line presure up 15kg/cm2 & including connection with main panel etc. as required complete in all restect
230MS PIPE
231Providing, laying, fixing, testing and commissioning of 'C' Class Medium duty MS Pipe conforming to Indian Standard IS : 1239/3589 including fittings like tees, bends, sockets, elbows, flanges, tapers, nuts bolts, gaskets etc. fixing the pipe on the wall / ceiling with suitable clamps and painting with two or more coats of synthetic enamel paint of required shade complete in all respects.
232100 mm dia
23380 mm dia
234ANGLE SUPPORTS
235Providing and fixing of MS Angle on wall with suitable fastner of 12mm thick x 100mm long as required for pipe support.
236CABLE TRAY
237Supply and erection of hot dip G.I. cable tray perforation not more than 17.5% for specific dimensions along with tees, bends. The cable tray shall be hang from ceiling/ fixed to wall with necessary angle/flat iron/hanging rod, for ceiling suspensions, clamp, anchor fastener, nuts, bolts, washers, not more than 1.0 mtr. apart complete as per specification to complete the job. The tray shall be as follows :-
238100 x 50 x 1.6mm thick
239150 x 50 x 1.6mm thick
240PRESSURE GAUGE
241Providing and fixing Pressure Gauge complete as required complete in all respect.
242Dial diameter 100mm calibration 0-16 Kg
243BUTTERFLY VALVES
244Supplying, Laying, Testing and Commissioning of ISI marked BUTTERFLY VALVE PN 1.6, with Gun metal seal duly ISI marked complete with rubber insertion, nuts, bolts and washers, matching flanges of required thickness, etc. complete as per specifications.
245150 mm dia
246NON RETURN VALVE
247Proving & fixing ISI Marked Dual Type Non-return valves flanged end class PN-1.6 as per IS:5312/2004 in pipe lines including jointing & cost of Nut Bolt , rubber insertion etc complete
248150mm dia(Dual Type NRV)
249STRAINER
250Supplying, Installation, Testing and Commissioning of cast iron flanged Y type strainer with stainless steel mesh in PN-1.6 including cost of Nut Bolt , rubber insertion complete in all respects.
251For 200 mm dia
252ALARM GONG BELL
253Providing & Fixing of installation control valve with turbine type automatic Alarm Gong to be connected with control valve, drain & test valve as per manufacturer's specifications complete.
254150mm dia
255FIRE ALARM SYSTEM
256PVC CONDUIT
257PVC, HDPE PIPES & PVC FLEXIBLEPIPES: Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD GeneralSpecifications:- Medium Gauge PVC Conduit Pipe 25mmdia. (On Surface)
258FIRE ALARM CONTROL PANEL
259Fire panel : Providing, fixing, testing & commissioning microprocessor based main fire alarm panel and indicating panel solid state modular card type pulsar, timer for dual stage alarm facility with indicators, standby battery, complies to IS 2189:1999.2 x 16 character backlit LCD display lamp test features. Complete with integral power supply and battery charger for SMF battery. NO/NC contacts for both fireand fault. Switches to enable on board operation. LCD and LED Indication for open, short circuit, Isolate, fire in each zone. reset, lamp test, silence, isolate, short, open, fire continuous buzzer for fault and intermittent buzzer for fire battery charger box, operating voltage 220 Volt mains A.C. input/24V D.C. output etc. complete in all respect. 8 zone
260Internal Fire Fighting Arrangment including Hydrant,Fire Extinguishers as per NBC Norms
261MS PIPE
262Providing, laying, fixing, testing and commissioning of 'B' Class Medium duty MS Pipe conforming to Indian Standard IS : 1239/3589 including fittings like tees, bends, sockets, elbows, flanges, tapers, nuts bolts, gaskets etc. fixing the pipe on the wall / ceiling and painting with two or more coats of synthetic enamel paint of required shade complete in all respects.
263100MM
264UNDERGROUND MS PIPE
265Providing, laying, fixing, testing and commissioning of 'C' Class Heavy duty MS Pipe (For External) conforming to Indian Standard IS : 1239/3589 including fittings like tees, bends, sockets, elbows, flanges, tapers, nuts bolts, gaskets etc. in ground with anti corrosive treatment with wrapping coating tape (4mm pypkote tape) as per IS : 10221 including cost of primer etc. excluding cost of excavation and refilling complete in all resepcts.
266100 mm dia
267ANGLE SUPPORTS
268Providing and fixing of Tie Rod on ceiling with suitable fastner of as required for pipe support.
269HYDRANT VALVE
270Supplying, Installation, Testing and Commissioning of Stainless Steel Single headed hydrant valve with instantaneous SS coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 with blank Cap and chain complete in all respects.
271Single Hydrant Valve
272HOSE PIPE
273Supplying, Installation, Testing and Commissioning of RRL FIRE hose Type A, IS:636, 63mm dia x 15m long with Stainless Steel male & female couplings (ISI marked) bound & riveted to hose pipes with GI rivets and GI wire as required.
274BRANCH PIPE
275Supplying, Installation, Testing and Commissioning 63 mm dia Stainless Steel Branch Pipe (ISI marked) with 20mm (nominal internal dia) size Stainless Steel nozzle confirming to IS 903, suitable for instantaneous connection to interconnect hose pipe coupling as required.
276FIRST AID HOSE REEL DRUM
277Providing and fixing first aid hose reel full swinging type including cabinet with 30 m length x 20 mm dia rubber lined pipe with ABS plastic shut off nozzle of 6 mm dia. The hose reel will conform to IS requirements. Rate will 25 mm dia pipe connection from riser to hose reel including flexible pipe, sockets, nipples, elbows .
278HOSE CABINET
279Supplying, Installation, Testing and Commissioning of weather proof cabinet for hose fabricated out of 1.6mm thickness M.S. sheet with front glass door having locking arrangement, suitable to accommodate all the necessary pipes, accessories, fittings etc including painting the metal portion with one coat of ready mixed primer paint and two coats of synthetic enamel paint of approved shade and quality, sign writing etc. 450 mm wide x 450 mm high x 250 mm deep Size.
280BUTTERFLY VALVES
281Supplying, Laying, Testing and Commissioning of ISI marked BUTTERFLY VALVE PN 1.6, with Stainless Steel seal duly ISI marked complete with rubber insertion, nuts, bolts and washers, matching flanges of required thickness, etc. complete as per specifications.
282150MM
283100MM
284NON RETURN VALVE
285Proving & fixing ISI Marked Non-return valves flanged end class PN-1.6 as per IS:5312/2004 in pipe lines including jointing & cost of Nut Bolt , rubber insertion etc. complete.
286150 mm dia
287FIRE BRIGADE INLET
288Providing and fixing fire brigade inlet connection of cast iron body with Stainless Steel 63mm dia instantaneous type male coupling with built in check valves and 150mm dia flanged outlet complete with bolts, nuts and rubber insertions as per IS:904.
289Three Way Inlet Connection
290AIR RELEASE VALVE
291Supplying & fixing of Air release valves on top .
292PRESSURE GAUGE
293Providing and fixing Pressure Gauge complete as required complete in all respect. Dial dia 100 mm calibration 0-16Kg/cm2
294ABC STORED PRESSURE FIRE EXTINGUISHER
295Providing and fixing of FIRE EXTINGUISHER, ABC Powder type (stored pressure) as per IS: 15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect.
296Capacity 4.0 kg. I.S.I. Marked.
297CO2 GAS TYPE FIRE EXTINGUISHER
298Providing and fixing of FIRE EXTINGUISHER, CO2 type as per IS: 15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect.
299Capacity 4.5 kg. I.S.I. Marked.
300BUCKET STAND
3014 buckets set with sand, self-supported M.S. stand i/cshed duly painted with red colour as per IS.
302Providing & placing in position on terrace (at all floor levels) HDPE water storage tanks of approved make (to the approval of Engineer - in-charge) with cover with suitable locking arrangement and making necessary holes for inlet, outlet and over flo pipes but without fittings and base support for tank.
303Triple Layer Tanks
3045000 Ltr x5 nos.
305Construction of Plateform complete as per specification & as desired by Enginer-in-charge
306For 5000 ltr Water Tank
307Proving & fixing ISI Marked Non-return valves flanged end class PN-1.0 as per IS:5312/2004 in pipe lines including jointing & cost of Nut Bolt , rubber insertion etc. complete.Note: If Non-return valves class PN-1.6 is used instead of class PN-1.0 , than 5% will be paid extra.
308Class PN-1.0 as per ISI with gun metal flap
309100mm i/d Non-return valve
310CONCEALED IN WALL: Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes as per IS 15778 (ISI marked with the prior approval of Engineer-in- Charge), having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing including jointing of pipes & fittings, with one step CPVC solvent cement and testing of pipes complete as per direction of Engineer-in-Charge.
311CPVC SDR 11 Pipe & fitting 32mm o/d
312Providing, fixing and jointing CPVC Ball valves screwed with CPVC ball & spindle & Teflon seats, on CPVC Pipe lines including all carriages complete.
31332mm i/d Brass Ball valves
314Providing and fixing in position automatic brass Ball Cock in tanks.Brass Ball Cock with rod and Plastic Ball
315Brass Ball Cock with rod and Plastic Ball 32mm i/d
316Providing and fixing fire brigade inlet connection of cast iron body with Gun metal 63mm dia instantaneous type male coupling with built in check valves and 150mm dia flanged outlet complete with bolts, nuts and rubber insertions as per IS:904. (to beconnected to static tank).
317Two Way inlet connection
318Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)
319Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520
320Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325
321M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.
322Suitable cement concrete foundation duly plastered and with anti vibration pads
323900 LPM AT 35 M HEAD Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58079311
AUTHORITY Government Departments
TENDER VALUE 1.89 Crore
LAST DATE 29-10-2026
Authority
Authority Name Water Supply And Sanitation Department
Work Description Tender for providing Fixing Pvc Pipe, Construction Of Masonry Sluice Valves Chamber, Sewerage System, Rising Main, Construction Of Ugsr, Tubewell, Electrical Panel Etc At Govt I.T.I Buildings (G+5) At Nangal Distt Roopnagar (Public Health Services). (Under Head Eds-80 School Of Eminence
Basic Detail
Tender No 6323/ITI Nangal
Bidding Type Tender
Location
City Rupnagar
State Punjab
Key Dates
Publish Date 16 Oct 2026
Submission Date 29 Oct 2026
Open Date 29 Oct 2026
Finance
Tender Value 1.89 Crore
Tender Fee 1000
EMD 3.79 Lakhs
Exemption Available
Document List
12d162ad-47f3-4e49-8dd5-828c889a5d33.html
BOQ_362498.xls
DNIT.pdf
TDNIT.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 16, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 29, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 10 days
Oct 29, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 10 days

Tender Documents

Download All (ZIP) ↓
html

12d162ad-47f3-4e49-8dd5-828c889a5d33.html

xls

BOQ_362498.xls

pdf

DNIT.pdf

pdf

TDNIT.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender