Tender For Replacement Of Old Non-Functional 30 Kva Ups At Hdu And Ot Complex Of Murshidabad Medical College & Hospital (Electrical Work)
Tender Value
Ref. Documents
Estimated cost
Bid Submission
24 Oct 2026
6 days left
EMD
10249
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Murshidabad → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Replacement Of Old Non-Functional 30 Kva Ups At Hdu And Ot Complex Of Murshidabad Medical College & Hospital (Electrical Work)
BOQ
| Sl. No. | Item Description |
| 1 | Technical Specification for 30 KVA UPS 3phase input & 3 phase out put on line UPS systems [Make: POWER ONE, NUMERIC, Switching AVO,POWER ONE, ] |
| 2 | Topology, IGBT BASED DSP CONTROLED |
| 3 | Rating of UPS(KVA/KW): 20 KVA / 16 KW |
| 4 | Input Voltage: 310----400----415 VAC 165-288 Volt /Phase(selectble) |
| 5 | Input Frequency: 45 to 65 Hz |
| 6 | Isolation Transformer: Inbuilt Isolation Transformer with 1:1 ratio at UPS Input to be provided at output |
| 7 | Back feed Protection: UPS should have back feed protection |
| 8 | Charging: Autometic float cum Boots Charging Capability with setteble flote & boost charging voltages and current levels and boots charger timer |
| 9 | Output Voltage: 230 VAC |
| 10 | Output Voltage Regulation: Static Variation +/_ 1% and Dynamic variation +/-3% |
| 11 | Output Frequency: 50 Hz +/- 0.1% |
| 12 | Output Power Factor: 0.8 |
| 13 | Crest Factor: 3:1 |
| 14 | THDu: < 2% (linear load), < 5%(non linear load) |
| 15 | Waveform: Pure Sine Wave |
| 16 | Birdge: Microprocessor based and IGBT Technology |
| 17 | Overload: 110% for 60 minutes, 125% for 10 minutes, 150% for 30 sec |
| 18 | Static By Pass: 100 % rated static switches with fuse protection overload on Bypass: 100% for 10 ms |
| 19 | Overall Efficiency: 92% |
| 20 | Battary Rack: With power coated MS angle with suiteble dimention and gadge.Useing Nyvin cable with proper rating for interlink cables and battery input and necessary acessiress. |
| 21 | Battery : 12 V, Mono Block batteries. SMF VRLA |
| 22 | Protection: Multi Protection-Over Temperature Protection with 8 Sensors, Overload, Battery Under Voltage, Fan Failures ,Short Circuit. Four Circuit Breakers, Providing Full Protection When Fault, Strong Overload Capability. Surge Protector at Panel Input & EB Input. PV Reverse Polarity, Input Low & High Voltage, Output Low & High Voltage cut off. Glass cartridge Fuse on Control Circuits MCB at Input Panel, |
| 23 | Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip |
| 24 | Metering: Graphical LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current |
| 25 | Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current |
| 26 | Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch |
| 27 | Termination: Input, Battery, Output & Bypass |
| 28 | Enclosure: IP 20 |
| 29 | Operating Temp: 0 to 40 Deg C |
| 30 | Humidity: Upto 95% Rh (non-condensing) |
| 31 | Cooling: Forced Air |
| 32 | Noise: < 55 dB |
| 33 | Cold Start : Provided |
| 34 | CE Certification:IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture) |
| 35 | ISO 9001: 2015, ISO 14001: 2015, ISO 45001:2018,ISO 50001;2018 , ISO:20000-1:2011,ISO:27001:2013, ROHS |
| 36 | Warranty: Two Years on UPS on site against any Manufacturing defects[ Battery already installed, only old UPS will be replaced with new one] Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 16, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 24, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysOct 26, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender