Tender for Fire Compliance Works At Various Buildings In Kem Hospital, Parel.
BOQ
| Sl. No. | Item Description |
| 1 | 415V Main Distribution Panel 1 short circuit reating 50kA for 1Sec. 630A (Thermal magnetic overload, short circuit release & earth leakage module) MCCB with rotary operating mechanism as incomer with digital ammeter, voltmeter with selector switches, phase indicating lamp with required accessories,1Nos. 63A, 3Noss. Of 100A, 2Noss. 160A & 200A (total 8Noss.) MCCB of short circuit rating 25kA for 1 sec. as outgoings. |
| 2 | Supplying and installing, testing, perfect aligning and proper leveling and commissioning of fire service main pump, of 2820 LPM (Litres/min.) at 88m centrifugal type pump |
| 3 | SITC of Jockey Pump of 240 LPM at 88m head, |
| 4 | SITC of Booster Pump of 450 LPM at 35 m head |
| 5 | Providing and fixing in position G.I. Heavy grade 'C' class pipes 200 mm |
| 6 | Providing and fixing in position G.I. Heavy grade 'C' class pipes150 mm |
| 7 | Providing and fixing in position G.I. Heavy grade 'C' class pipes100 mm |
| 8 | Providing and fixing in position G.I. Heavy grade 'C' class pipes 80 mm |
| 9 | Providing and fixing in position G.I. Heavy grade 'C' class pipes 65 mm |
| 10 | Providing and fixing in position G.I. Heavy grade 'C' class pipes 50 mm |
| 11 | Providing and fixing in position G.I. Heavy grade 'C' class pipes 40 mm |
| 12 | Providing and fixing in position G.I. Heavy grade 'C' class pipes 32 mm |
| 13 | Providing and fixing in position G.I. Heavy grade 'C' class pipes 25 mm |
| 14 | Painting of MS Pipe 3\\" dia. |
| 15 | Painting of MS Pipe 2\\" dia. |
| 16 | Painting of MS Pipe 1\\" dia. |
| 17 | Supplying & Installing cast iron double flange butterfly valve 200 mm |
| 18 | WAFER TYPE BUTTERFLY VALVES: -150 mm dia. |
| 19 | WAFER TYPE BUTTERFLY VALVES: -100 mm dia. |
| 20 | WAFER TYPE BUTTERFLY VALVES: -80 mm dia. |
| 21 | WAFER TYPE BUTTERFLY VALVES: -50 mm dia. |
| 22 | Supplying and installing double flange NRV 200 mm |
| 23 | Supplying and installing double flange NRV 150 mm |
| 24 | Supplying and installing double flange NRV 100 mm |
| 25 | Supplying and installing double flange NRV 80 mm |
| 26 | End line strainer 150 mm |
| 27 | End line strainer 100 mm |
| 28 | End line strainer 80 mm |
| 29 | FIXING OF C.I. GATE VALVE COMPLETE WITH FLANGE, NUT, BOLTS ETC. -100 mm dia |
| 30 | FIXING OF C.I. GATE VALVE COMPLETE WITH FLANGE, NUT, BOLTS ETC. -150 mm dia. |
| 31 | Foot valve 150mm |
| 32 | Foot valve 100mm |
| 33 | Ball valves 50 mm diameter |
| 34 | Ball valves 25 mm diameter |
| 35 | Supplying and installing pressure gauge of 100 mm Ø., 0-300 PSI or 0- 14 kg per cm square fitted with 12/15 mm Ø. pad cock valve, and G.I. pipe, elbow etc |
| 36 | Supplying and installing pressure switch with 12/15 mm Ø isolation valve, G.I. nipple, elbow etc. in an approved manner as per specification. |
| 37 | 1st category Cu armoured cables FRLS outer sheathed- 3.5C x 95 Sq.mm |
| 38 | 1st category Cu armoured cables FRLS outer sheathed- 4C x 16 Sq.mm |
| 39 | Cable End Termination For Aluminium Cables – 3.5C x 95 Sq.mm |
| 40 | Cable End Termination For Aluminium Cables – 4C x 16 Sq.mm |
| 41 | Earthing Continuity Conductors -50 x 6mm GI |
| 42 | 2nd category Cu armoured cables FRLSZ outer sheathed- 2C x 1.5 Sq.mm |
| 43 | Supplying and fabrication of MS Support with accessories. 50 x 50 x 6 mm of M.S.angle. |
| 44 | Supplying and installing fire brigade Header of150 mm Ø, for supplying water in fire tank as per specification |
| 45 | Supplying & installing moulded HDP / Fibre water tank. for -ve suction only, having capacity 1000 ltrs.fitted with necessary accessories complete as per specification |
| 46 | Supplying and erecting 20/25mm Ø G.M.air release cock, with necessary G.I. coupling to be fitted on top of Air vessel or on wet riser as per specification |
| 47 | Supplying and installing Air Vessel of 300 mm Ø 1.5m in height M.S. tank installed inside pump house as per specification |
| 48 | Supplying and installing gun metal single outlet hydrant valve fitted with necessary accessories |
| 49 | Supplying Stainless Steel branch Pipe 63 mm Ø fitted with 20 mm dia detachable hexagonal nozzle as per specifications |
| 50 | Providing and fixing in position 2 lengths of 15 M long flexible canvas rubber lined hose reels 63 dia with adapter, branch pipe and nozzle and storing them in metal cabinets with lockable glass shutters and fixing the metal cabinet at ground level in a location where it can be easily spotted including painting etc |
| 51 | Supplying and erecting M.S./CRCA cabinet for housing single hydrant valve (size 400 x 400 x 400mm.) made from 16 SWG sheet and angle iron 25 mm. x 25 mm. x 4 mm. having front doors with viewing glass (8\\"x6\\") and locking arrangement with necessary fixing material such as rubber bidding etc. dulypainted in post box red colour |
| 52 | Supplying and installing fire brigade Header (Siamese Connection) of 150 mm Ø for supplying water to wet riser system as per specification |
| 53 | Providing coating of Bitumen Paint & 4mm thick Wrapping as per IS 10221 for underground 100 mm Ring Main of Fire Fighting System. |
| 54 | Excavating the trenches and refilling,reinstatement of the same after the cable is laid in approved manner (750 mm deep, 600 mm wide),in all types of soils 1 Cu. Mtr. = 2.2 RMT. |
| 55 | Supplying and installing wall mounting swinging Hose reel drum fitted with 19 mm dia. 30m high pressure polypropylene (Polyhose) long fitted with necessary accessories complete as per specification |
| 56 | Cement concrete foundation using M-20 cement concrete mix with J shaped foundation bolts where required. |
| 57 | Supply & Laying of double wall corrugated ( DWC) pipe 120 mm OD / 103.5 mm I.D. |
| 58 | Excavating the trenches and refilling the same after the cable is laid in approved manner (Size of trench: 750 mm deep, 600 mm wide) in concrete/ masonary /asphalt. 1 Cu. Mtr. = 2.2 RMT. And reinstatement. |
| 59 | Providing, detailing, composite fabricating members like Trusses, Nsteel members fabricated using M.S. hollow tubular steel sections (circular & rectangular pipes), of TATA Structura Make or equivalent conforming to IS 1239 part 1 and 2 and of grade Fe 250 as per specifications and approved fabrication drawings (which are to be prepared by Contractor and got approved from Engineer), including transportion of the same to site, erection of structural steel members for all heights & at all levels, provision of necessary erection bolts, fixing bolts, nuts, washers, cleats, stiffeners, gussets, base plate, and all necessary operations like preheating as per specifications, straightening, bending, cutting, drilling, grinding, machining if specified, welding, grinding, removing the welding burr and preparing surface for painting with wire brush cleaning and applying two coats of epoxy red oxide zinc phosphate primer of 30 microns each and two coats of Epoxy Corrosion Resistant Enamel paint of 30 microns after fabrication including touching up with spray painting after erection etc complete as directed by Engineer |
| 60 | Bare Galvalume/zincalume sheets for roofing |
| 61 | Rubber mat 2mm thick size 3x5 feet |
| 62 | 600 X 600 X 3.15 mm Copper Plate, 3000mm dip with suitable size cu strip earth pit as per IS 3043. The earth pit shall be provided with watering pipe (Class B) with wire messed funnel, 25X3 cu strip / 2X8SWG Cu.wire up to chamber, disconnecting links with 600 x 600 mm (clear) RCC chamber & 3mm thick heavy duty CI chequered plate cover with hinge. Bentonite shall be provided for earth pits. Excavation, back filling, removal of excess soil is included in the scope |
| 63 | Earthing Continuity Conductors -25 x 6mm Tinned copper |
| 64 | Earthing Continuity Conductors – Bare Copper Conductor size12 SWG |
| 65 | Supplying & erecting vane type water flow detector suitable for detecting flow of water in wet sprinkler pipe of main line or branch lines of 100 mm dia having following features 1) Visual Switch Activation 2) Rugged Switch Assembly 3) Heavy Duty Alluminium pipe Saddles 4) Durable Metal Encloser 5) Steel U Bolts For Secure Mounting 6) Two SPDT ( Single Pole Double Track ) Synchronised Switches 7) Serviceable Without Draining Pipes |
| 66 | Supplying and erecting 15 mm (½\\") dia. NBCM Body chrome finished quartzoid bulb sprinkler having 68º C fixed temperature rating with deflector disc of conventional construction and quality conforming to international standards and listed by LPC (formally FOC U.K.) U.L.F.M. of USA or approved and listed by Tariff Advisory Committee (TAC) OF India |
| 67 | Providng and fixing in position sprinkler guards to protect open sprinkler in basement from mechanical damage. |
| 68 | SITC of Hydraulic flexible pipe of one meter length with size |
| 69 | Work Supply & laying of 25 mm dia C class GI pipe, flow control valves from makeup water tank. To. If necessary suitable capacity boosters pump shall be provided for makeup water line. |
| 70 | Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver Paint. |
| 71 | Supply, Installation, testing & commissioning of addressable 2 loop main fire alarm electronic control panel, expendable up to 4 loop & having maximum 250 devices (any combination detectors plus devices) per loop & Audio/ Visual alarm complete as per IS: 2189 specification - modular type front operated with interlocking door arrangement totally encloseddust and vermin proof for indoor type applications. |
| 72 | Supply, Installation, testing & commissioning of Active Repeater panel with all accessories, which shall be replica of main fire alarm panel with control keys I,e. Mute, silent & sounder alarm. |
| 73 | Supply, Installation, testing & commissioning of expandable Loop card for main fire alarm electronic control panel, shall support 254 devices both detectors and modules and shall support both class 'A' & class 'B' wiring. |
| 74 | Supply, Installation, testing & commissioning of conventional optical type smoke detector complete on box as per Specification |
| 75 | Supply, Installation, testing & commissioning of conventional Manual Call Point (Pill box) with break glass push button in metal enclosure complete with back mounting box. |
| 76 | Supply, Installation, testing & commissioning of conventional Hooters with CRCA enclosure complete with external power supply & junction boxes. |
| 77 | SITC of Addressable control Relay module with required accessories along with junction box, glands and terminators ( For AC trip off, Access trip off, PA system, sprinkler flow switch, lift interface, sounder, fire fighter & telephone jack) |
| 78 | Supply, Installation, testing & commissioning of Isolator Module along with mounting box & termination glands. |
| 79 | Supply, Installation, testing & commissioning of remoteresponse indicator |
| 80 | Cable End Termination For Copper Cables – 2C x 1.5 / 2.5 Sq.mm |
| 81 | Supplying and erecting FRLS armoured cable 4 core 1.5 sq.mm.copper complete erected on wall/ceiling/trusses as per specification |
| 82 | Supply and installation of Mixer amplifier 120W (4 channel input & 1 line level balanced output) |
| 83 | Supply and installation of Booster amplifier 500W with all accessories. |
| 84 | Chairman Unit Microphone |
| 85 | 6W/100V. PA Ceiling Speaker |
| 86 | Supply & installation of 6W/100V wall mounting box speakers. |
| 87 | Speaker wiring using 40/36 cable with PVC conduit |
| 88 | SITC of Auto glow signage for Emergency Fire Exit |
| 89 | SITC of Auto glow signage for Do not use lift in case of Fire etc |
| 90 | Clean Agent Fire Extinguisher |
| 91 | B form charges |
| 92 | Mock drill |
| 93 | Trolley Mounted water mist cum CAFS System |
| 94 | Providing and fixing fire doors with 2 hour fire rating conforming to IS: 3614 (Part 2), BS 476 (Parts 20 & 22), ISO 834 ; 45 mm thickfully flush, double skin door shell with lock seam joints at stileedges made from 1.25 mm thick galvanized steel sheet including door frames made from 1.6 mm thick galvanized steel sheet formedto double rebate profile of size 143 mm x 57mm as per manufacturer's instructions, door frames and shutter primed withZinc Phosphate stoving Primer and finished with PolyurethaneAliphatic grade or epoxy paint including ironmongery consisting of stainless steel ball bearing butt hinges 3 mm thick fixed flush to the frame and shutter, full width horizontal handles (panic bar),concealed flush bolts, door closers, other standards fixtures and fasteners, etc. complete for the following clear opening sizes: |
| 95 | CSMC 5% for 2nd year after completing 1 year DLP. |
| 96 | CSMC 5% for 3rd year |
| 97 | CSMC 5% for 4th year |
| 98 | CSMC 5% for 5th year Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 16, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 05, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysNov 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender