Public Administrative Department Local Bodies Closing in 17 days TDR #58075170

Tender For Fire Compliance Works At Various Buildings In Kem Hospital, Parel.

Issued by Local Bodies · Mumbai, Maharashtra
Tender Value
Ref. Documents
Estimated cost
Bid Submission
05 Nov 2026
17 days left
EMD
8.36 Lakhs
Bank guarantee accepted
Document Fee
23560
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Mumbai → Maharashtra
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Fire Compliance Works At Various Buildings In Kem Hospital, Parel.

BOQ

Name of Work:- Fire Compliance Works at Various Buildings in KEM Hospital, Parel.
Sl. No. Item Description
1415V Main Distribution Panel 1 short circuit reating 50kA for 1Sec. 630A (Thermal magnetic overload, short circuit release & earth leakage module) MCCB with rotary operating mechanism as incomer with digital ammeter, voltmeter with selector switches, phase indicating lamp with required accessories,1Nos. 63A, 3Noss. Of 100A, 2Noss. 160A & 200A (total 8Noss.) MCCB of short circuit rating 25kA for 1 sec. as outgoings.
2Supplying and installing, testing, perfect aligning and proper leveling and commissioning of fire service main pump, of 2820 LPM (Litres/min.) at 88m centrifugal type pump
3SITC of Jockey Pump of 240 LPM at 88m head,
4SITC of Booster Pump of 450 LPM at 35 m head
5Providing and fixing in position G.I. Heavy grade 'C' class pipes 200 mm
6Providing and fixing in position G.I. Heavy grade 'C' class pipes150 mm
7Providing and fixing in position G.I. Heavy grade 'C' class pipes100 mm
8Providing and fixing in position G.I. Heavy grade 'C' class pipes 80 mm
9Providing and fixing in position G.I. Heavy grade 'C' class pipes 65 mm
10Providing and fixing in position G.I. Heavy grade 'C' class pipes 50 mm
11Providing and fixing in position G.I. Heavy grade 'C' class pipes 40 mm
12Providing and fixing in position G.I. Heavy grade 'C' class pipes 32 mm
13Providing and fixing in position G.I. Heavy grade 'C' class pipes 25 mm
14Painting of MS Pipe 3\\" dia.
15Painting of MS Pipe 2\\" dia.
16Painting of MS Pipe 1\\" dia.
17Supplying & Installing cast iron double flange butterfly valve 200 mm
18WAFER TYPE BUTTERFLY VALVES: -150 mm dia.
19WAFER TYPE BUTTERFLY VALVES: -100 mm dia.
20WAFER TYPE BUTTERFLY VALVES: -80 mm dia.
21WAFER TYPE BUTTERFLY VALVES: -50 mm dia.
22Supplying and installing double flange NRV 200 mm
23Supplying and installing double flange NRV 150 mm
24Supplying and installing double flange NRV 100 mm
25Supplying and installing double flange NRV 80 mm
26End line strainer 150 mm
27End line strainer 100 mm
28End line strainer 80 mm
29FIXING OF C.I. GATE VALVE COMPLETE WITH FLANGE, NUT, BOLTS ETC. -100 mm dia
30FIXING OF C.I. GATE VALVE COMPLETE WITH FLANGE, NUT, BOLTS ETC. -150 mm dia.
31Foot valve 150mm
32Foot valve 100mm
33Ball valves 50 mm diameter
34Ball valves 25 mm diameter
35Supplying and installing pressure gauge of 100 mm Ø., 0-300 PSI or 0- 14 kg per cm square fitted with 12/15 mm Ø. pad cock valve, and G.I. pipe, elbow etc
36Supplying and installing pressure switch with 12/15 mm Ø isolation valve, G.I. nipple, elbow etc. in an approved manner as per specification.
371st category Cu armoured cables FRLS outer sheathed- 3.5C x 95 Sq.mm
381st category Cu armoured cables FRLS outer sheathed- 4C x 16 Sq.mm
39Cable End Termination For Aluminium Cables – 3.5C x 95 Sq.mm
40Cable End Termination For Aluminium Cables – 4C x 16 Sq.mm
41Earthing Continuity Conductors -50 x 6mm GI
422nd category Cu armoured cables FRLSZ outer sheathed- 2C x 1.5 Sq.mm
43Supplying and fabrication of MS Support with accessories. 50 x 50 x 6 mm of M.S.angle.
44Supplying and installing fire brigade Header of150 mm Ø, for supplying water in fire tank as per specification
45Supplying & installing moulded HDP / Fibre water tank. for -ve suction only, having capacity 1000 ltrs.fitted with necessary accessories complete as per specification
46Supplying and erecting 20/25mm Ø G.M.air release cock, with necessary G.I. coupling to be fitted on top of Air vessel or on wet riser as per specification
47Supplying and installing Air Vessel of 300 mm Ø 1.5m in height M.S. tank installed inside pump house as per specification
48Supplying and installing gun metal single outlet hydrant valve fitted with necessary accessories
49Supplying Stainless Steel branch Pipe 63 mm Ø fitted with 20 mm dia detachable hexagonal nozzle as per specifications
50Providing and fixing in position 2 lengths of 15 M long flexible canvas rubber lined hose reels 63 dia with adapter, branch pipe and nozzle and storing them in metal cabinets with lockable glass shutters and fixing the metal cabinet at ground level in a location where it can be easily spotted including painting etc
51Supplying and erecting M.S./CRCA cabinet for housing single hydrant valve (size 400 x 400 x 400mm.) made from 16 SWG sheet and angle iron 25 mm. x 25 mm. x 4 mm. having front doors with viewing glass (8\\"x6\\") and locking arrangement with necessary fixing material such as rubber bidding etc. dulypainted in post box red colour
52Supplying and installing fire brigade Header (Siamese Connection) of 150 mm Ø for supplying water to wet riser system as per specification
53Providing coating of Bitumen Paint & 4mm thick Wrapping as per IS 10221 for underground 100 mm Ring Main of Fire Fighting System.
54Excavating the trenches and refilling,reinstatement of the same after the cable is laid in approved manner (750 mm deep, 600 mm wide),in all types of soils 1 Cu. Mtr. = 2.2 RMT.
55Supplying and installing wall mounting swinging Hose reel drum fitted with 19 mm dia. 30m high pressure polypropylene (Polyhose) long fitted with necessary accessories complete as per specification
56Cement concrete foundation using M-20 cement concrete mix with J shaped foundation bolts where required.
57Supply & Laying of double wall corrugated ( DWC) pipe 120 mm OD / 103.5 mm I.D.
58Excavating the trenches and refilling the same after the cable is laid in approved manner (Size of trench: 750 mm deep, 600 mm wide) in concrete/ masonary /asphalt. 1 Cu. Mtr. = 2.2 RMT. And reinstatement.
59Providing, detailing, composite fabricating members like Trusses, Nsteel members fabricated using M.S. hollow tubular steel sections (circular & rectangular pipes), of TATA Structura Make or equivalent conforming to IS 1239 part 1 and 2 and of grade Fe 250 as per specifications and approved fabrication drawings (which are to be prepared by Contractor and got approved from Engineer), including transportion of the same to site, erection of structural steel members for all heights & at all levels, provision of necessary erection bolts, fixing bolts, nuts, washers, cleats, stiffeners, gussets, base plate, and all necessary operations like preheating as per specifications, straightening, bending, cutting, drilling, grinding, machining if specified, welding, grinding, removing the welding burr and preparing surface for painting with wire brush cleaning and applying two coats of epoxy red oxide zinc phosphate primer of 30 microns each and two coats of Epoxy Corrosion Resistant Enamel paint of 30 microns after fabrication including touching up with spray painting after erection etc complete as directed by Engineer
60Bare Galvalume/zincalume sheets for roofing
61Rubber mat 2mm thick size 3x5 feet
62600 X 600 X 3.15 mm Copper Plate, 3000mm dip with suitable size cu strip earth pit as per IS 3043. The earth pit shall be provided with watering pipe (Class B) with wire messed funnel, 25X3 cu strip / 2X8SWG Cu.wire up to chamber, disconnecting links with 600 x 600 mm (clear) RCC chamber & 3mm thick heavy duty CI chequered plate cover with hinge. Bentonite shall be provided for earth pits. Excavation, back filling, removal of excess soil is included in the scope
63Earthing Continuity Conductors -25 x 6mm Tinned copper
64Earthing Continuity Conductors – Bare Copper Conductor size12 SWG
65Supplying & erecting vane type water flow detector suitable for detecting flow of water in wet sprinkler pipe of main line or branch lines of 100 mm dia having following features 1) Visual Switch Activation 2) Rugged Switch Assembly 3) Heavy Duty Alluminium pipe Saddles 4) Durable Metal Encloser 5) Steel U Bolts For Secure Mounting 6) Two SPDT ( Single Pole Double Track ) Synchronised Switches 7) Serviceable Without Draining Pipes
66Supplying and erecting 15 mm (½\\") dia. NBCM Body chrome finished quartzoid bulb sprinkler having 68º C fixed temperature rating with deflector disc of conventional construction and quality conforming to international standards and listed by LPC (formally FOC U.K.) U.L.F.M. of USA or approved and listed by Tariff Advisory Committee (TAC) OF India
67Providng and fixing in position sprinkler guards to protect open sprinkler in basement from mechanical damage.
68SITC of Hydraulic flexible pipe of one meter length with size
69Work Supply & laying of 25 mm dia C class GI pipe, flow control valves from makeup water tank. To. If necessary suitable capacity boosters pump shall be provided for makeup water line.
70Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver Paint.
71Supply, Installation, testing & commissioning of addressable 2 loop main fire alarm electronic control panel, expendable up to 4 loop & having maximum 250 devices (any combination detectors plus devices) per loop & Audio/ Visual alarm complete as per IS: 2189 specification - modular type front operated with interlocking door arrangement totally encloseddust and vermin proof for indoor type applications.
72Supply, Installation, testing & commissioning of Active Repeater panel with all accessories, which shall be replica of main fire alarm panel with control keys I,e. Mute, silent & sounder alarm.
73Supply, Installation, testing & commissioning of expandable Loop card for main fire alarm electronic control panel, shall support 254 devices both detectors and modules and shall support both class 'A' & class 'B' wiring.
74Supply, Installation, testing & commissioning of conventional optical type smoke detector complete on box as per Specification
75Supply, Installation, testing & commissioning of conventional Manual Call Point (Pill box) with break glass push button in metal enclosure complete with back mounting box.
76Supply, Installation, testing & commissioning of conventional Hooters with CRCA enclosure complete with external power supply & junction boxes.
77SITC of Addressable control Relay module with required accessories along with junction box, glands and terminators ( For AC trip off, Access trip off, PA system, sprinkler flow switch, lift interface, sounder, fire fighter & telephone jack)
78Supply, Installation, testing & commissioning of Isolator Module along with mounting box & termination glands.
79Supply, Installation, testing & commissioning of remoteresponse indicator
80Cable End Termination For Copper Cables – 2C x 1.5 / 2.5 Sq.mm
81Supplying and erecting FRLS armoured cable 4 core 1.5 sq.mm.copper complete erected on wall/ceiling/trusses as per specification
82Supply and installation of Mixer amplifier 120W (4 channel input & 1 line level balanced output)
83Supply and installation of Booster amplifier 500W with all accessories.
84Chairman Unit Microphone
856W/100V. PA Ceiling Speaker
86Supply & installation of 6W/100V wall mounting box speakers.
87Speaker wiring using 40/36 cable with PVC conduit
88SITC of Auto glow signage for Emergency Fire Exit
89SITC of Auto glow signage for Do not use lift in case of Fire etc
90Clean Agent Fire Extinguisher
91B form charges
92Mock drill
93Trolley Mounted water mist cum CAFS System
94Providing and fixing fire doors with 2 hour fire rating conforming to IS: 3614 (Part 2), BS 476 (Parts 20 & 22), ISO 834 ; 45 mm thickfully flush, double skin door shell with lock seam joints at stileedges made from 1.25 mm thick galvanized steel sheet including door frames made from 1.6 mm thick galvanized steel sheet formedto double rebate profile of size 143 mm x 57mm as per manufacturer's instructions, door frames and shutter primed withZinc Phosphate stoving Primer and finished with PolyurethaneAliphatic grade or epoxy paint including ironmongery consisting of stainless steel ball bearing butt hinges 3 mm thick fixed flush to the frame and shutter, full width horizontal handles (panic bar),concealed flush bolts, door closers, other standards fixtures and fasteners, etc. complete for the following clear opening sizes:
95CSMC 5% for 2nd year after completing 1 year DLP.
96CSMC 5% for 3rd year
97CSMC 5% for 4th year
98CSMC 5% for 5th year Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58075170
AUTHORITY Local Bodies
TENDER VALUE Ref. Documents
LAST DATE 05-11-2026
Authority
Authority Name Municipal Corporation Of Greater Mumbai
Work Description Tender for Fire Compliance Works At Various Buildings In Kem Hospital, Parel.
Basic Detail
Tender No Ch.E./MnE/3109 dtd 14.10.2026
Bidding Type Tender
Location
City Mumbai
State Maharashtra
Key Dates
Publish Date 16 Oct 2026
Submission Date 05 Nov 2026
Open Date 06 Nov 2026
Finance
Tender Value Ref. Documents
Tender Fee 23560
EMD 8.36 Lakhs
Exemption Not Available
Document List
BOQ_2298518.xls
eef2c195-792d-43ee-9a14-af954c7c2882.html
SBD1344887.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 16, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 05, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Nov 06, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 18 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_2298518.xls

html

eef2c195-792d-43ee-9a14-af954c7c2882.html

pdf

SBD1344887.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender