Tender For Supply Installation Testing And Commissioning Of 18 Tr Air-Cooled Modular Scroll Chillers And Fcu In Lab No- 215 & 216 Sab Building Iit Ropar.
Tender Value
16.91 Lakhs
Estimated cost
Bid Submission
29 Oct 2026
12 days left
EMD
33830
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Rupnagar → Punjab
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Supply Installation Testing And Commissioning Of 18 Tr Air-Cooled Modular Scroll Chillers And Fcu In Lab No- 215 & 216 Sab Building Iit Ropar.
BOQ
| Sl. No. | Item Description |
| 1 | 20 TR AIR COOLED SCROLL CHILLERS > Supplying, installation, testing and commissioning of following capacity Air-Cooled , Scroll Chiller package complete with VFD (Variable Frequency Drive),hermetic/semi hermetic, multiple scroll type compressors each with step less capacity control of 25 % to 100 % of the rated capacity, with microprocessor based control panel, motor, starter panel (VFD), machine mounted, aircooled condensers, factory fitted chiller insulation, water flow switch , vibration spring Isolators, victaulic couplings, integral refrigerant piping and wiring with single/ two circuits, automatic and safety controls mounted in central console panel and all mounted on a steel frame (completeas per specifications) i/c suitable foundation/mounting structure made of RCC/MS Structure i/c anticorosive paint, anti vibration pad, power control cable and connection inter connection etc. as per design approved by engineer-incharge. Motor shall be suitable for 415±10% 50 cycles. 3 phase AC supply. Refrigerant gas used shall be R-410A. The chiller shall be Building Management System (BMS) compatible. The system shall be in confirmation to IS :16590 and CPWD Specification as amended upto date.BEE Star labeling and CPWD Specification as amendedupto date and tested as per IS 16590.Chilled water Leaving Temp. (6.67 0C)Chilled water Entering Temp. (12.2 0C)Evaporator fouling factor = 0.018 m2. 0C/kWCondenser air entering temp. : As per Site Dry Bulb Temperature Suitable for Seismic Zone and Altitude as per location/site. Microprocessor based controller Upto 50 TR BEE 4 Star Rated |
| 2 | DUCTABLE FAN COIL UNIT 3.0 TR nominal capacity with 1200 CFM air quantitySupplying, installation ,testing and commissioning ofCeiling Concealed Fan Coil Unit comprising of 3 rows deep chilled water cooling coil, centrifugal blowers, fractional horse power (FHP) motor, synthetic fibre filters, insulated & extended condensate drain pan along with L-type auxillary tray, casing, coil piping connections, condensate drain piping connections &wiring. Fan coil units shall be suitable for operation on 220 +10% Volts, 50Hz, single phasepower supply of following sizes & capacities.Complete as per CPWD specification and as directed by Engineer-in-charge |
| 3 | Low Side Work of Heat Pump Inclusion: (Danfoss Pump, Pressure & Temp Gauges,Y Strainers, CPVC Pipes aprox 15 Mtr & Fittings, Tee Fittings, Reducers, Ball Valve, Nipples,Flow Switch, MS Stand for Pumps, Alluminium Grill, 3 Way Valve, Copper Valve, Flare Nuts, CPVC Pipe Insulation, Digital Thermostat, Electrical Wire and Panel; with Components, Copper Pipe, Water StorageTank with Insulation & including Lifting shifting & Labour Work charges with Follwing items = 1 (job) |
| 4 | Horizontal end-suction pump Make: Grundfos Model: CM 10-3 Max Flow - 14000 LPH IE3 Motor HP Rating - 2.3 HP/1.7 KW 3 Phase |
| 5 | SS Pressure Gauge 2-1/2\\" 10K |
| 6 | SS Temperature Gauge 4\\" |
| 7 | Y Stainer 1-1/2\\" |
| 8 | CPVC Brass MABT - 40mm |
| 9 | CPVC Reducer Tee - 40mm |
| 10 | Mini Ball Valve ¼\\" |
| 11 | CPVC Brass FABT - 15 mm |
| 12 | Brass Hex Nipple ½”x1/4” |
| 13 | Brass Hex Nipple ¼”x1/4” |
| 14 | CPVC Pipe 40mm |
| 15 | CPVC Elbow 40mm |
| 16 | CPVC Union 40mm |
| 17 | GI Tee 40 mm |
| 18 | Water Flow Switch |
| 19 | Solvent Solution |
| 20 | Safeda |
| 21 | Dhaga |
| 22 | Tuffin Tape |
| 23 | MS Stand for Pump |
| 24 | Installation of AHU |
| 25 | Aluminum Grill 6”x10” |
| 26 | 3 Way Valve ¾ |
| 27 | Copper pipe inlet/outlet Valve ¾ |
| 28 | Flare Nuts 6/8 |
| 29 | Y-Stanir ¾ |
| 30 | CPVC Pipe Insulation - 9mm |
| 31 | Drain Pipe PVC |
| 32 | Digital Thermostat (Subzero) |
| 33 | Electrical Wire 2.5 Sqmm/ 3 Core (Panel to Pump) |
| 34 | Control Wire 2 Core, Indoor to Remote |
| 35 | Electrical Panel including Magnetic Contactor, Terminal Connection, Volt Meter, Amp Meter, SSP, Push Button, also interlocking |
| 36 | Copper Pipe 6/8 |
| 37 | Water Storage Tank Cap. : 1000 ltr |
| 38 | Insulation on Water Tank, including Insulation, SR Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 15, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 12 daysOct 30, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 13 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender