Defence Statutory Bodies & Commissions/Committees Closing in 17 days TDR #58073301

Tender For Special Repair/Replacement Of Feeder Pillar Boxes Service Cable Alongwith Connected Items Inside Vijay Durg Under Ge(Vd) Kolkata

Issued by Statutory Bodies & Commissions/Committees · Kolkata, West Bengal
Tender Value
38 Lakhs
Estimated cost
Bid Submission
05 Nov 2026
17 days left
EMD
76000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Kolkata → West Bengal
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Special Repair/Replacement Of Feeder Pillar Boxes Service Cable Alongwith Connected Items Inside Vijay Durg Under Ge(Vd) Kolkata

BOQ

Name of Work:- SPECIAL REPAIR/REPLACEMENT OF FEEDER PILLAR BOXES SERVICE CABLE ALONGWITH CONNECTED ITEMS INSIDE VIJAY DURG UNDER GE(VD) KOLKATA
Sl. No. Item Description
1Supply, install, commissioning and testing of Outdoor type LT panel board mounting in PCC base, cubical type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 75 x 40 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location: Near Sainik Club
2INCOMING
3(a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T
4(b)Supply and fixing of 4P 630A 25kA Thermal Magnetic MCCB along with spreader with neutral protection built-in,having Ui (Rated insulation voltage)=800V, Uimp(Rated impulse withstand voltage)=8kV peak, Rated Operational Voltage = 550V, Ics=Icu=100%, There should be no current deration up to 50-degree C.- 03 Pcs (Incoming). Make :Cat No. -669031Legrand/Schnider/Siemens
5OUTGOING
6(a) MCCB design with thermal-magnetic releases of capacity 200 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
7(b) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make Legrand/Schnider/Siemens
8METERING INSTRUMENT
9(a) 3 Ph Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
10(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
11(c) MCB SP 6 Amps, 10 KA - (Set of 3 Pcs) For Protection and Controlling. Make : L&T
12(d) LED type indication lamp R Y B - 01 set.
13(e) Current Transformer Ratio 250/5A - 03 Nos
14Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
15Supply, install, commissioning and testing of feeder Pillar Box mounting on PCC base cubical type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1500mm x 1500mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 40 x 40 x 5 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Adam Branch Panel
16INCOMING
17(a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T
18(a) Supply and fixing of 4P 630A 36kA Thermal Magnetic MCCB along with spreader with neutral protection built-in,having Ui (Rated insulation voltage)=800V, Uimp(Rated impulse withstand voltage) =8kV peak, Rated Operational Voltage = 690V, Ics=Icu=100%, There should be no current deration up to 50-degree C. - 01 NosMake: Legrand Cat No. – 667665/Schnider/Siemens
19OUTGOING
20(a) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
21(b) MCCB dsign with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 04 Nos (Outgoing). Make Legrand/Schnider/Siemens
22METERING INSTRUMENT
23(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
24(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
25(c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
26(d) LED type indication lamp R Y B - 01 set.
27(e) Current Transformer Ratio 800/5A - 03 Nos
28Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
29Supply, install, commissioning and testing of Indoor type LT panel board, cubical type mounting on PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1200mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar of 300 Amp size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 75x 40 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location VIJAY SMARAK FEEDER PILLAR BOX
30INCOMING
31(a) (a) MCCB design with thermal-magnetic releases of capacity 200 Amps, 4 Pole, 36 KA - 01 Nos . Make : Legrand/Schnider/Siemens
32OUTGOING
33(a) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Incoming). Make : Legrand/Schnider/Siemens
34(b) MCCB dsign with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos ((Incoming). Make : Legrand/Schnider/Siemens
35(c) MCB 16 Amp, DP, 10KA,
36(d) MCB 10 Amp DP 10 KA
37METERING INSTRUMENT
38(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
39(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
40(c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
41(d) LED type indication lamp R Y B - 01 set.
42(e) Current Transformer Ratio 600/5A - 03 Nos
43Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
44Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting on PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1200mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 75 x 40 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Opposite barber Shop
45(a) MCCB design with microprocessor based release of capacity 200A, 4P, 36 KA - 01 Nos (Incoming). Make : Schneider/Legrand/Siemens
46OUTGOING
47(a) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
48(b) MCCB dsign with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
49METERING INSTRUMENT
50(a) MCB 6 AMP, SP, 10KA, For Protection/Controlling
51(b) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
52(c) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
53(d) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
54(e) LED type indication lamp R Y B - 01 set.
55(f) Current Transformer Ratio 250/5A - 03 Nos
56Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
57Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting on PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1200mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 75 x 40 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Water Gate Guard Room back side
58(a) MCCB design with microprocessor based release of capacity 200A, 4P, 36 KA - 01 Nos (Incoming). Make : Schneider/Legrand/Siemens
59OUTGOING
60(a) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
61(b) MCCB dsign with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
62METERING INSTRUMENT
63(a) MCB 6 AMP, SP, 10KA, For Protection/Controlling
64(b) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
65(c) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
66(d) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
67(e) LED type indication lamp R Y B - 01 set.
68(f) Current Transformer Ratio 250/5A - 03 Nos
69Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
70(d) LED type indication lamp R Y B - 01 set.
71(e) Current Transformer Ratio 800/5A - 03 Nos
72Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
73Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar of suitable size (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Near AOI
74INCOMING
75(a) Automatic Transfer Switch 400 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T
76(b) MCCB design with Thermal Magnetic releases of capacity 400 Amps, 4 Pole, 36 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
77OUTGOING
78(a) MCCB design with Thermal Magnetic releases of capacity 200 Amps, 4 Pole, 36 KA - 02 Nos (Outgoing). Make :Legrand/Schnider/Siemens
79METERING INSTRUMENT
80(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
81(g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
82(h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
83(f) LED type indication lamp R Y B - 01 set.
84(g) Current Transformer Ratio 800/5A - 03 Nos
85Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
86Supply, install, commissioning and testing of LT feeder Pillar Box, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 600 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Annexe Back side Feeder pillar box
87INCOMING
88(a) Onload manual Changeover 400 Amp, 4 Pole (open execution) Make: L&T
89(b) MCCB design with Microprocessor Release of capacity 400A, 4P, 36 KA - 02 Nos (Incoming). Make : Schneider/Legrand/Siemens
90OUTGOING
91(c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole,25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
92(d) MCCB design with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
93METERING INSTRUMENT
94(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
95(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
96(c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
97(d) LED type indication lamp R Y B - 01 set.
98(e) Current Transformer Ratio 600/5A - 03 Nos
99Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
100Supply, install, commissioning and testing of Outdoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 800 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Gurudwara
101INCOMING
102(a) Onload manual Changeover 400 Amp, 4 Pole 36KA (open execution) Make: L&T
103OUTGOING
104(c) MCCB design with thermal-magnetic releases of capacity 200 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
105(c) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
106(c) MCCB design with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
107METERING INSTRUMENT
108(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
109(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
110(c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
111(d) LED type indication lamp R Y B - 01 set.
112(e) Current Transformer Ratio 600/5A - 03 Nos
113Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
114Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location CALCUTA GATE TUNNEL INSIDE
115INCOMING
116(a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T
117OUTGOING
118(a) MCCB design with Microprocessor Release of capacity 200 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
119(a) MCCB design with Microprocessor Release of capacity 160 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
120(a) MCCB design with Microprocessor Release of capacity 125 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
121(a) MCCB design with Microprocessor Release of capacity 100 Amps, 4 Pole, 36 KA - 02 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
122METERING INSTRUMENT
123(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
124(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
125(c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
126(d) LED type indication lamp R Y B - 01 set.
127(e) Current Transformer Ratio 200/5A - 03 Nos
128Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
129Supply, install, commissioning and testing of feeder Pillar Box mounting on PCC base cubical type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1500mm x 1500mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 40 x 40 x 5 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location O2 Mess feeder Pillar Box
130INCOMING
131(a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T
132(a) Supply and fixing of 4P 630A 36kA Thermal Magnetic MCCB along with spreader with neutral protection built-in,having Ui (Rated insulation voltage)=800V, Uimp(Rated impulse withstand voltage) =8kV peak, Rated Operational Voltage = 690V, Ics=Icu=100%, There should be no current deration up to 50-degree C. - 01 NosMake: Legrand Cat No. – 667665/Schnider/Siemens
133OUTGOING
134(a) MCCB design with Microprocessor Release of capacity 200 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
135(a) MCCB design with Microprocessor Release of capacity 160 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
136(a) MCCB design with Microprocessor Release of capacity 125 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
137(a) MCCB design with Microprocessor Release of capacity 100 Amps, 4 Pole, 36 KA - 02 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
138METERING INSTRUMENT
139(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
140(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
141(c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
142(d) LED type indication lamp R Y B - 01 set.
143(e) Current Transformer Ratio 800/5A - 03 Nos
144Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
145Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1500mm x 1500mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 600 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Command Mandir
146INCOMING
147(a) Onload manual Changeover 400 Amp, 4 Pole (open execution) Make: L&T
148(b) MCCB design with Microprocessor Release of capacity 400A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens
149OUTGOING
150(c) MCCB design with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
151(c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
152(c) MCCB design with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
153METERING INSTRUMENT
154(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
155(g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
156(h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
157(f) LED type indication lamp R Y B - 01 set.
158(g) Current Transformer Ratio 600/5A - 03 Nos
159Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
160Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 600 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location North Barrack Driver Room Feeder Pillar Box
161INCOMING
162(a) Onload manual Changeover 400 Amp, 4 Pole (open execution) Make: L&T
163(b) MCCB design with Microprocessor Release of capacity 400A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens
164OUTGOING
165(c) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
166(c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
167(c) MCCB design with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
168METERING INSTRUMENT
169(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
170(g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
171(h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
172(f) LED type indication lamp R Y B - 01 set.
173(g) Current Transformer Ratio 600/5A - 03 Nos
174Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
175Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 600 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location North Barrack Driver Room Feeder Pillar Box
176INCOMING
177(a) Onload manual Changeover 400 Amp, 4 Pole (open execution) Make: L&T
178(b) MCCB design with Microprocessor Release of capacity 400A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens
179OUTGOING
180(c) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
181(c) MCCB design with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
182(c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
183METERING INSTRUMENT
184(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
185(g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
186(h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
187(f) LED type indication lamp R Y B - 01 set.
188(g) Current Transformer Ratio 600/5A - 03 Nos
189Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
190Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1200mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Power House Mandir Back side Feeder Pillar Box
191INCOMING
192(b) MCCB design with Microprocessor Release of capacity 325A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens
193OUTGOING
194(c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
195(c) MCCB design with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
196METERING INSTRUMENT
197(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
198(g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
199(h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
200(f) LED type indication lamp R Y B - 01 set.
201(g) Current Transformer Ratio 600/5A - 03 Nos
202Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
203Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Power House Mandir Back side Feeder Pillar Box
204INCOMING
205(a) MCCB design with Microprocessor Release of capacity 320 A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens
206OUTGOING
207(b) MCCB design with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens
208(c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
209METERING INSTRUMENT
210(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
211(g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
212(h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
213(f) LED type indication lamp R Y B - 01 set.
214(g) Current Transformer Ratio 600/5A - 03 Nos
215Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
216Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 950 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location BACK SIDE OF BARBAR SHOP
217INCOMING
218(a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T
219(b) MCCB design with Microprocessor Release of capacity 630 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
220OUTGOING
221(a) MCCB design with Microprocessor Release of capacity 320 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
222(a) MCCB design with Microprocessor Release of capacity 250 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
223(a) MCCB design with Microprocessor Release of capacity 160 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
224METERING INSTRUMENT
225(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
226(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
227(c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
228(d) LED type indication lamp R Y B - 01 set.
229(e) Current Transformer Ratio 200/5A - 03 Nos
230Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
231Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 950 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location POWER HOUSE BACK SIDE FEEDER PILLAR BOX
232INCOMING
233(a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T
234(b) MCCB design with Microprocessor Release of capacity 630 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
235OUTGOING
236(a) MCCB design with Microprocessor Release of capacity 400 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
237(a) MCCB design with Microprocessor Release of capacity 320 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens
238METERING INSTRUMENT
239(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
240(b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
241(c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
242(d) LED type indication lamp R Y B - 01 set.
243(e) Current Transformer Ratio 200/5A - 03 Nos
244Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
245Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 2000mm x 1800mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Engr Branch
246INCOMING
247(a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T
248(b) MCCB design with Microprocessor Release of capacity 630A, 4P, 50 KA - 02 Nos (Incoming). Make : Legrand/Schnider/Siemens
249OUTGOING
250(a) MCCB design with Thermal Magnetic releases of capacity 320 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make :Legrand/Schnider/Siemens
251(b) MCCB design with Thermal Magnetic releases of capacity 200 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make :Legrand/Schnider/Siemens
252(c) MCCB design with Thermal Magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
253(d) MCCB design with Thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens
254METERING INSTRUMENT
255(a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T
256(g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T
257(h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T
258(f) LED type indication lamp R Y B - 01 set.
259(g) Current Transformer Ratio 250/5A - 03 Nos
260Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge.
261Excavation in Trenches not exc. 1.50 Metre wide and not exc. 1.50 Metre in depth for laying of UG Cable/Pole/Stays, etc., getting out including forming bottom surface to required level and gradient in Soft/ Loose Soil and getting out, complete all as specified and as directed.
262Excavation/Cutting Road/ Hardstanding in Trenches not exc. 1.50 Metre wide and not exc. 1.50 Metre in depth and getting out, complete all as specified and as directed. NOTE : Quoted Unit Rate shall deem to be included Materials and Labour required for repairing to damaged Road/ Hardstanding to match the existing Surfaces and Specifications.
263Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 Cm in Soft/ Loose Soil, complete all as specified and as directed.
264Removing excavated materials not exc. 50.00 Metre and depositing where directed at a level not exc. 1.50 Metre above the starting point, complete all as specified and as directed.
265Supply & laying in Trenches Sub-class ‘B’ Bricks, kiln burnt, for Cable Protection, complete all as specified and as directed.
266Laying in Trenches Bricks (Serviceable Bricks obtained from Item No. 9.00 here-in-after), for Cable Protection, complete all as specified and as directed.
267M&L Sand Cushioning (dry) in Trenches/Ducts for protection of UG Cables (below, above and around the UG Cable laid) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180Cm thickness, complete all as specified and as directed. NOTE : For the purpose of Payment, punned thickness of Sand Cushioning only will be Measured.
268Supply Laying double wall corrugated HDPE Pipe 120mm Outer Dia, confirming to IS-16205 (Part-24) with couplers end cap & bends as required, laid in trenches for cable protection complete all as specified and directed
269Supply Laying double wall corrugated HDPE Pipe 120mm Outer Dia, confirming to IS-16205 (Part-24) with couplers end cap & bends as required, laid in trenches for cable protection complete all as specified and directed
270Taking out of interlocking paver block, any shape or size and Re-laying the same after laying of LT cable of any size and also removing all vegetation, algae, grass etc, laid to proper slope & gradient over sand cushioning complete all as specified and directed.NOTE : Sand, if required for connection of cushioning level will be measured and paid seperately.
271Supply and Laying of Machine pressed precast concrete interlocking paver block with grey cement and pigment of any shape and size as approved by GE conforming to IS-15658-2006 of 60 mm thickness, M-35 grade with 6 mm top layer of coloured rubberised anti abrasive material complete all as specified and directed.
272Taking down unserviceable LT cable for repair/ replacement etc (from cable duct/underground trench/pole), stacking properly (cable, pipe and bricks) complete all as directed by the Engr-in-Charge of the following cross - sections :- (Note :- Necessary earth work to be measured and paid separately.
27325 Sqmm to 50 Sqmm, 3.5 Core
27475 Sqmm to 120 Sqmm, 3.5 Core
275Supply, Laying and testing for replacement of XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded aluminium conductor cable, laid in trench or fixed to wall with saddles/Flat iron clamps as per site requirement /passing through pipe/pole complete of the following sizes and cross sectional area :-Note :- Necessary earth work to be measured and paid separately.
27635 Sqmm, 3.5 Core
27750 Sqmm, 3.5 Core
27895 Sqmm, 3.5 Core
279M&L for Relaying XLPE Under Ground Cable of any description (Serviceable Cable obtained from Item No. 10.00 here-in-before) 1100 Volt grade, after Fault rectification including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed of the following size and cross sectional area :-
28010 Sqmm to 16 Sqmm 2/3½/4 Core
28125 Sqmm to 50 Sqmm 3½/4 Core
28270 Sqmm to 120 Sqmm 3½ Core
283150 Sqmm to 185 Sqmm 3½ Core
284S&F Heat shrinkable straight through Jointing Kit suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion complete all as specified and directed by the Engr-in-Charge for the following size of cables :-
28525 Sqmm to 50 sqmm 3.5/4 core
28670 sqmm to 150 sqmm, 3.5 core
287185 sqmm to 240 sqmm, 3.5 core
288Materials and Labour for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized iron strip 25 X 4 mm (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing and dismantling of existing unsv earthing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed.
289Supply and fixing GI tubing 50mm bore (light grade) in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by Engineer-in-Charge.
290Supply and fixing 80 mm bore galvanized iron pipe (light grade) with all fittings, fixed in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by the Engineer-in-charge.
291Supply and fixing 100 mm bore galvanized iron pipe (light grade) with all fittings, fixed in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by the Engineer-in-charge.
292Note: Schedule of credit (SCHEDULE OF CREDIT) amount of Rs ________ mentioned on Page No ____ shall be deducted from the total quoted amount of BOQ. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58073301
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 38 Lakhs
LAST DATE 05-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Special Repair/Replacement Of Feeder Pillar Boxes Service Cable Alongwith Connected Items Inside Vijay Durg Under Ge(Vd) Kolkata
Basic Detail
Tender No 8659/E8
Bidding Type Tender
Location
City Kolkata
State West Bengal
Key Dates
Publish Date 15 Oct 2026
Submission Date 05 Nov 2026
Open Date 06 Nov 2026
Finance
Tender Value 38 Lakhs
Tender Fee 500
EMD 76000
Exemption Not Available
Document List
BOQ_890462.xls
c114bc2b-f28f-4342-935d-97d4ebcb44e5.html
TENDERDOCUMENTS8659JOINER.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 15, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 05, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Nov 06, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 18 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_890462.xls

html

c114bc2b-f28f-4342-935d-97d4ebcb44e5.html

pdf

TENDERDOCUMENTS8659JOINER.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender