Tender For Special Repair/Replacement Of Feeder Pillar Boxes Service Cable Alongwith Connected Items Inside Vijay Durg Under Ge(Vd) Kolkata
Tender Value
38 Lakhs
Estimated cost
Bid Submission
05 Nov 2026
17 days left
EMD
76000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kolkata → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Special Repair/Replacement Of Feeder Pillar Boxes Service Cable Alongwith Connected Items Inside Vijay Durg Under Ge(Vd) Kolkata
BOQ
| Sl. No. | Item Description |
| 1 | Supply, install, commissioning and testing of Outdoor type LT panel board mounting in PCC base, cubical type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 75 x 40 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location: Near Sainik Club |
| 2 | INCOMING |
| 3 | (a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 4 | (b)Supply and fixing of 4P 630A 25kA Thermal Magnetic MCCB along with spreader with neutral protection built-in,having Ui (Rated insulation voltage)=800V, Uimp(Rated impulse withstand voltage)=8kV peak, Rated Operational Voltage = 550V, Ics=Icu=100%, There should be no current deration up to 50-degree C.- 03 Pcs (Incoming). Make :Cat No. -669031Legrand/Schnider/Siemens |
| 5 | OUTGOING |
| 6 | (a) MCCB design with thermal-magnetic releases of capacity 200 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 7 | (b) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make Legrand/Schnider/Siemens |
| 8 | METERING INSTRUMENT |
| 9 | (a) 3 Ph Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 10 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 11 | (c) MCB SP 6 Amps, 10 KA - (Set of 3 Pcs) For Protection and Controlling. Make : L&T |
| 12 | (d) LED type indication lamp R Y B - 01 set. |
| 13 | (e) Current Transformer Ratio 250/5A - 03 Nos |
| 14 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 15 | Supply, install, commissioning and testing of feeder Pillar Box mounting on PCC base cubical type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1500mm x 1500mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 40 x 40 x 5 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Adam Branch Panel |
| 16 | INCOMING |
| 17 | (a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 18 | (a) Supply and fixing of 4P 630A 36kA Thermal Magnetic MCCB along with spreader with neutral protection built-in,having Ui (Rated insulation voltage)=800V, Uimp(Rated impulse withstand voltage) =8kV peak, Rated Operational Voltage = 690V, Ics=Icu=100%, There should be no current deration up to 50-degree C. - 01 NosMake: Legrand Cat No. – 667665/Schnider/Siemens |
| 19 | OUTGOING |
| 20 | (a) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 21 | (b) MCCB dsign with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 04 Nos (Outgoing). Make Legrand/Schnider/Siemens |
| 22 | METERING INSTRUMENT |
| 23 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 24 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 25 | (c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 26 | (d) LED type indication lamp R Y B - 01 set. |
| 27 | (e) Current Transformer Ratio 800/5A - 03 Nos |
| 28 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 29 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type mounting on PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1200mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar of 300 Amp size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 75x 40 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location VIJAY SMARAK FEEDER PILLAR BOX |
| 30 | INCOMING |
| 31 | (a) (a) MCCB design with thermal-magnetic releases of capacity 200 Amps, 4 Pole, 36 KA - 01 Nos . Make : Legrand/Schnider/Siemens |
| 32 | OUTGOING |
| 33 | (a) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Incoming). Make : Legrand/Schnider/Siemens |
| 34 | (b) MCCB dsign with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos ((Incoming). Make : Legrand/Schnider/Siemens |
| 35 | (c) MCB 16 Amp, DP, 10KA, |
| 36 | (d) MCB 10 Amp DP 10 KA |
| 37 | METERING INSTRUMENT |
| 38 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 39 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 40 | (c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 41 | (d) LED type indication lamp R Y B - 01 set. |
| 42 | (e) Current Transformer Ratio 600/5A - 03 Nos |
| 43 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 44 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting on PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1200mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 75 x 40 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Opposite barber Shop |
| 45 | (a) MCCB design with microprocessor based release of capacity 200A, 4P, 36 KA - 01 Nos (Incoming). Make : Schneider/Legrand/Siemens |
| 46 | OUTGOING |
| 47 | (a) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 48 | (b) MCCB dsign with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 49 | METERING INSTRUMENT |
| 50 | (a) MCB 6 AMP, SP, 10KA, For Protection/Controlling |
| 51 | (b) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 52 | (c) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 53 | (d) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 54 | (e) LED type indication lamp R Y B - 01 set. |
| 55 | (f) Current Transformer Ratio 250/5A - 03 Nos |
| 56 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 57 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting on PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1200mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 75 x 40 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Water Gate Guard Room back side |
| 58 | (a) MCCB design with microprocessor based release of capacity 200A, 4P, 36 KA - 01 Nos (Incoming). Make : Schneider/Legrand/Siemens |
| 59 | OUTGOING |
| 60 | (a) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 61 | (b) MCCB dsign with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 62 | METERING INSTRUMENT |
| 63 | (a) MCB 6 AMP, SP, 10KA, For Protection/Controlling |
| 64 | (b) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 65 | (c) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 66 | (d) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 67 | (e) LED type indication lamp R Y B - 01 set. |
| 68 | (f) Current Transformer Ratio 250/5A - 03 Nos |
| 69 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 70 | (d) LED type indication lamp R Y B - 01 set. |
| 71 | (e) Current Transformer Ratio 800/5A - 03 Nos |
| 72 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 73 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar of suitable size (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Near AOI |
| 74 | INCOMING |
| 75 | (a) Automatic Transfer Switch 400 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 76 | (b) MCCB design with Thermal Magnetic releases of capacity 400 Amps, 4 Pole, 36 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 77 | OUTGOING |
| 78 | (a) MCCB design with Thermal Magnetic releases of capacity 200 Amps, 4 Pole, 36 KA - 02 Nos (Outgoing). Make :Legrand/Schnider/Siemens |
| 79 | METERING INSTRUMENT |
| 80 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 81 | (g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 82 | (h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 83 | (f) LED type indication lamp R Y B - 01 set. |
| 84 | (g) Current Transformer Ratio 800/5A - 03 Nos |
| 85 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 86 | Supply, install, commissioning and testing of LT feeder Pillar Box, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 600 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Annexe Back side Feeder pillar box |
| 87 | INCOMING |
| 88 | (a) Onload manual Changeover 400 Amp, 4 Pole (open execution) Make: L&T |
| 89 | (b) MCCB design with Microprocessor Release of capacity 400A, 4P, 36 KA - 02 Nos (Incoming). Make : Schneider/Legrand/Siemens |
| 90 | OUTGOING |
| 91 | (c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole,25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 92 | (d) MCCB design with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 93 | METERING INSTRUMENT |
| 94 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 95 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 96 | (c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 97 | (d) LED type indication lamp R Y B - 01 set. |
| 98 | (e) Current Transformer Ratio 600/5A - 03 Nos |
| 99 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 100 | Supply, install, commissioning and testing of Outdoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 800 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Gurudwara |
| 101 | INCOMING |
| 102 | (a) Onload manual Changeover 400 Amp, 4 Pole 36KA (open execution) Make: L&T |
| 103 | OUTGOING |
| 104 | (c) MCCB design with thermal-magnetic releases of capacity 200 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 105 | (c) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 106 | (c) MCCB design with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 107 | METERING INSTRUMENT |
| 108 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 109 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 110 | (c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 111 | (d) LED type indication lamp R Y B - 01 set. |
| 112 | (e) Current Transformer Ratio 600/5A - 03 Nos |
| 113 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 114 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location CALCUTA GATE TUNNEL INSIDE |
| 115 | INCOMING |
| 116 | (a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 117 | OUTGOING |
| 118 | (a) MCCB design with Microprocessor Release of capacity 200 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 119 | (a) MCCB design with Microprocessor Release of capacity 160 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 120 | (a) MCCB design with Microprocessor Release of capacity 125 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 121 | (a) MCCB design with Microprocessor Release of capacity 100 Amps, 4 Pole, 36 KA - 02 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 122 | METERING INSTRUMENT |
| 123 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 124 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 125 | (c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 126 | (d) LED type indication lamp R Y B - 01 set. |
| 127 | (e) Current Transformer Ratio 200/5A - 03 Nos |
| 128 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 129 | Supply, install, commissioning and testing of feeder Pillar Box mounting on PCC base cubical type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1500mm x 1500mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 40 x 40 x 5 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location O2 Mess feeder Pillar Box |
| 130 | INCOMING |
| 131 | (a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 132 | (a) Supply and fixing of 4P 630A 36kA Thermal Magnetic MCCB along with spreader with neutral protection built-in,having Ui (Rated insulation voltage)=800V, Uimp(Rated impulse withstand voltage) =8kV peak, Rated Operational Voltage = 690V, Ics=Icu=100%, There should be no current deration up to 50-degree C. - 01 NosMake: Legrand Cat No. – 667665/Schnider/Siemens |
| 133 | OUTGOING |
| 134 | (a) MCCB design with Microprocessor Release of capacity 200 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 135 | (a) MCCB design with Microprocessor Release of capacity 160 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 136 | (a) MCCB design with Microprocessor Release of capacity 125 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 137 | (a) MCCB design with Microprocessor Release of capacity 100 Amps, 4 Pole, 36 KA - 02 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 138 | METERING INSTRUMENT |
| 139 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 140 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 141 | (c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 142 | (d) LED type indication lamp R Y B - 01 set. |
| 143 | (e) Current Transformer Ratio 800/5A - 03 Nos |
| 144 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 145 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1500mm x 1500mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 600 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Command Mandir |
| 146 | INCOMING |
| 147 | (a) Onload manual Changeover 400 Amp, 4 Pole (open execution) Make: L&T |
| 148 | (b) MCCB design with Microprocessor Release of capacity 400A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens |
| 149 | OUTGOING |
| 150 | (c) MCCB design with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 151 | (c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 152 | (c) MCCB design with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 153 | METERING INSTRUMENT |
| 154 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 155 | (g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 156 | (h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 157 | (f) LED type indication lamp R Y B - 01 set. |
| 158 | (g) Current Transformer Ratio 600/5A - 03 Nos |
| 159 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 160 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 600 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location North Barrack Driver Room Feeder Pillar Box |
| 161 | INCOMING |
| 162 | (a) Onload manual Changeover 400 Amp, 4 Pole (open execution) Make: L&T |
| 163 | (b) MCCB design with Microprocessor Release of capacity 400A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens |
| 164 | OUTGOING |
| 165 | (c) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 166 | (c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 167 | (c) MCCB design with thermal-magnetic releases of capacity 63 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 168 | METERING INSTRUMENT |
| 169 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 170 | (g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 171 | (h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 172 | (f) LED type indication lamp R Y B - 01 set. |
| 173 | (g) Current Transformer Ratio 600/5A - 03 Nos |
| 174 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 175 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1300mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 600 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location North Barrack Driver Room Feeder Pillar Box |
| 176 | INCOMING |
| 177 | (a) Onload manual Changeover 400 Amp, 4 Pole (open execution) Make: L&T |
| 178 | (b) MCCB design with Microprocessor Release of capacity 400A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens |
| 179 | OUTGOING |
| 180 | (c) MCCB design with thermal-magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 181 | (c) MCCB design with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 182 | (c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 183 | METERING INSTRUMENT |
| 184 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 185 | (g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 186 | (h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 187 | (f) LED type indication lamp R Y B - 01 set. |
| 188 | (g) Current Transformer Ratio 600/5A - 03 Nos |
| 189 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 190 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1200mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Power House Mandir Back side Feeder Pillar Box |
| 191 | INCOMING |
| 192 | (b) MCCB design with Microprocessor Release of capacity 325A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens |
| 193 | OUTGOING |
| 194 | (c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 195 | (c) MCCB design with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 196 | METERING INSTRUMENT |
| 197 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 198 | (g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 199 | (h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 200 | (f) LED type indication lamp R Y B - 01 set. |
| 201 | (g) Current Transformer Ratio 600/5A - 03 Nos |
| 202 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 203 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers copper bus bar 300 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Power House Mandir Back side Feeder Pillar Box |
| 204 | INCOMING |
| 205 | (a) MCCB design with Microprocessor Release of capacity 320 A, 4P, 36 KA - 01 Nos + Both End Spreader Link (Incoming). Make :Legrand/Schnider/Siemens |
| 206 | OUTGOING |
| 207 | (b) MCCB design with thermal-magnetic releases of capacity 125 Amps, 4 Pole, 25 KA - 01 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 208 | (c) MCCB design with thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 209 | METERING INSTRUMENT |
| 210 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 211 | (g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 212 | (h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 213 | (f) LED type indication lamp R Y B - 01 set. |
| 214 | (g) Current Transformer Ratio 600/5A - 03 Nos |
| 215 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 216 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 950 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location BACK SIDE OF BARBAR SHOP |
| 217 | INCOMING |
| 218 | (a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 219 | (b) MCCB design with Microprocessor Release of capacity 630 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 220 | OUTGOING |
| 221 | (a) MCCB design with Microprocessor Release of capacity 320 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 222 | (a) MCCB design with Microprocessor Release of capacity 250 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 223 | (a) MCCB design with Microprocessor Release of capacity 160 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 224 | METERING INSTRUMENT |
| 225 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 226 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 227 | (c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 228 | (d) LED type indication lamp R Y B - 01 set. |
| 229 | (e) Current Transformer Ratio 200/5A - 03 Nos |
| 230 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 231 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1300mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 950 Amps of size 50mm x 6mm (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location POWER HOUSE BACK SIDE FEEDER PILLAR BOX |
| 232 | INCOMING |
| 233 | (a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 234 | (b) MCCB design with Microprocessor Release of capacity 630 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 235 | OUTGOING |
| 236 | (a) MCCB design with Microprocessor Release of capacity 400 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 237 | (a) MCCB design with Microprocessor Release of capacity 320 Amps, 4 Pole, 36 KA - 01 Nos (Outgoing). + Both End Spreader Link.Make : Legrand/Schnider/Siemens |
| 238 | METERING INSTRUMENT |
| 239 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 240 | (b) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 241 | (c) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 242 | (d) LED type indication lamp R Y B - 01 set. |
| 243 | (e) Current Transformer Ratio 200/5A - 03 Nos |
| 244 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 245 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 2000mm x 1800mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Engr Branch |
| 246 | INCOMING |
| 247 | (a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 248 | (b) MCCB design with Microprocessor Release of capacity 630A, 4P, 50 KA - 02 Nos (Incoming). Make : Legrand/Schnider/Siemens |
| 249 | OUTGOING |
| 250 | (a) MCCB design with Thermal Magnetic releases of capacity 320 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make :Legrand/Schnider/Siemens |
| 251 | (b) MCCB design with Thermal Magnetic releases of capacity 200 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make :Legrand/Schnider/Siemens |
| 252 | (c) MCCB design with Thermal Magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 253 | (d) MCCB design with Thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 254 | METERING INSTRUMENT |
| 255 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 256 | (g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 257 | (h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 258 | (f) LED type indication lamp R Y B - 01 set. |
| 259 | (g) Current Transformer Ratio 250/5A - 03 Nos |
| 260 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 261 | Excavation in Trenches not exc. 1.50 Metre wide and not exc. 1.50 Metre in depth for laying of UG Cable/Pole/Stays, etc., getting out including forming bottom surface to required level and gradient in Soft/ Loose Soil and getting out, complete all as specified and as directed. |
| 262 | Excavation/Cutting Road/ Hardstanding in Trenches not exc. 1.50 Metre wide and not exc. 1.50 Metre in depth and getting out, complete all as specified and as directed. NOTE : Quoted Unit Rate shall deem to be included Materials and Labour required for repairing to damaged Road/ Hardstanding to match the existing Surfaces and Specifications. |
| 263 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 Cm in Soft/ Loose Soil, complete all as specified and as directed. |
| 264 | Removing excavated materials not exc. 50.00 Metre and depositing where directed at a level not exc. 1.50 Metre above the starting point, complete all as specified and as directed. |
| 265 | Supply & laying in Trenches Sub-class ‘B’ Bricks, kiln burnt, for Cable Protection, complete all as specified and as directed. |
| 266 | Laying in Trenches Bricks (Serviceable Bricks obtained from Item No. 9.00 here-in-after), for Cable Protection, complete all as specified and as directed. |
| 267 | M&L Sand Cushioning (dry) in Trenches/Ducts for protection of UG Cables (below, above and around the UG Cable laid) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180Cm thickness, complete all as specified and as directed. NOTE : For the purpose of Payment, punned thickness of Sand Cushioning only will be Measured. |
| 268 | Supply Laying double wall corrugated HDPE Pipe 120mm Outer Dia, confirming to IS-16205 (Part-24) with couplers end cap & bends as required, laid in trenches for cable protection complete all as specified and directed |
| 269 | Supply Laying double wall corrugated HDPE Pipe 120mm Outer Dia, confirming to IS-16205 (Part-24) with couplers end cap & bends as required, laid in trenches for cable protection complete all as specified and directed |
| 270 | Taking out of interlocking paver block, any shape or size and Re-laying the same after laying of LT cable of any size and also removing all vegetation, algae, grass etc, laid to proper slope & gradient over sand cushioning complete all as specified and directed.NOTE : Sand, if required for connection of cushioning level will be measured and paid seperately. |
| 271 | Supply and Laying of Machine pressed precast concrete interlocking paver block with grey cement and pigment of any shape and size as approved by GE conforming to IS-15658-2006 of 60 mm thickness, M-35 grade with 6 mm top layer of coloured rubberised anti abrasive material complete all as specified and directed. |
| 272 | Taking down unserviceable LT cable for repair/ replacement etc (from cable duct/underground trench/pole), stacking properly (cable, pipe and bricks) complete all as directed by the Engr-in-Charge of the following cross - sections :- (Note :- Necessary earth work to be measured and paid separately. |
| 273 | 25 Sqmm to 50 Sqmm, 3.5 Core |
| 274 | 75 Sqmm to 120 Sqmm, 3.5 Core |
| 275 | Supply, Laying and testing for replacement of XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded aluminium conductor cable, laid in trench or fixed to wall with saddles/Flat iron clamps as per site requirement /passing through pipe/pole complete of the following sizes and cross sectional area :-Note :- Necessary earth work to be measured and paid separately. |
| 276 | 35 Sqmm, 3.5 Core |
| 277 | 50 Sqmm, 3.5 Core |
| 278 | 95 Sqmm, 3.5 Core |
| 279 | M&L for Relaying XLPE Under Ground Cable of any description (Serviceable Cable obtained from Item No. 10.00 here-in-before) 1100 Volt grade, after Fault rectification including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed of the following size and cross sectional area :- |
| 280 | 10 Sqmm to 16 Sqmm 2/3½/4 Core |
| 281 | 25 Sqmm to 50 Sqmm 3½/4 Core |
| 282 | 70 Sqmm to 120 Sqmm 3½ Core |
| 283 | 150 Sqmm to 185 Sqmm 3½ Core |
| 284 | S&F Heat shrinkable straight through Jointing Kit suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion complete all as specified and directed by the Engr-in-Charge for the following size of cables :- |
| 285 | 25 Sqmm to 50 sqmm 3.5/4 core |
| 286 | 70 sqmm to 150 sqmm, 3.5 core |
| 287 | 185 sqmm to 240 sqmm, 3.5 core |
| 288 | Materials and Labour for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized iron strip 25 X 4 mm (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing and dismantling of existing unsv earthing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed. |
| 289 | Supply and fixing GI tubing 50mm bore (light grade) in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by Engineer-in-Charge. |
| 290 | Supply and fixing 80 mm bore galvanized iron pipe (light grade) with all fittings, fixed in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by the Engineer-in-charge. |
| 291 | Supply and fixing 100 mm bore galvanized iron pipe (light grade) with all fittings, fixed in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by the Engineer-in-charge. |
| 292 | Note: Schedule of credit (SCHEDULE OF CREDIT) amount of Rs ________ mentioned on Page No ____ shall be deducted from the total quoted amount of BOQ. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 15, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 05, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysNov 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender