Tender For Providing Electrical Work For The Construction Of Revenue Divisional Officers C Office Cum Quarters At Kumbakonam In Thanjavur District.
Tender Value
Ref. Documents
Estimated cost
Bid Submission
29 Oct 2026
11 days left
EMD
10200
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Thanjavur → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Providing Electrical Work For The Construction Of Revenue Divisional Officers C Office Cum Quarters At Kumbakonam In Thanjavur District.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End ) |
| 2 | Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End |
| 3 | Wiring with 3 x 1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6 A two way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with suitable colour for Concealed PVC pipe Stair case Light point Higher End |
| 4 | Supply and fixing of 4 Feet LED 20 W Fitting with LED 20 W tube (Higher End) complete with TW round blocks on wall or ceiling with PVC unsheathed FRLS Copper leads from terminals to the fitting. |
| 5 | Supply and fixing of 18 W LED Round type Surface mounted downlight on wall or ceiling with PVC unsheathed FRLS Copper leads from terminals to the fitting. |
| 6 | Supply and fixing of WT bulk head fitting with guard suitable with 7W / 9W LED bulb |
| 7 | supply and fixing of 1200 mm (48\\") sweep AC ceiling fan High speed complete with 2 module 100 W fan step regulator (Higher end) with 300 mm down rod with fan clamp with side plates and cross arm of size 450mm (18\\"). |
| 8 | supply and fixing of 1400 mm (56\\") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 300 mm down rod with fan clamp with side plates and cross arm of size 450mm (18\\") |
| 9 | Supply and fixing of 300 mm (12\\") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall |
| 10 | Supply and fixing of louvers shutters arrangements for 300 mm (12\\") sweep (light duty) AC exhaust fan. |
| 11 | Supply and fixing of 48 W LED street light fitting with LED (Higher end) with 32mm dia. GI pipe (class B) with 1 no.32 mm GI bend complete on the existing post/ on wall with PVC unsheathed copper leads with MS clamps and with painting . |
| 12 | Supply and fixing of AC/DC 76mm buzzer/call bell suitable for 230 volts 50c/s single phase AC supply on suitable TW board with push switch. |
| 13 | Supply erection testing and commissioning uninterrupted power supply (UPS) OFFLINE (Pure Sine wave) with copper wound Transformer of 2000 VA with input voltage 24V DC supply output voltage 230V-50Hz AC supply with 150 AH Tubular Battery to work at full load capacity including transportation with following specifications and with following accessories and with 2 hours of battery back up at full load respectively.1. Input Voltage : 230 V, 50 Hz Single Phase AC Supply.2. Output Voltage : 220 V to 240 V 50 Hz AC supply. 3. Battery charging device of suitable rating4. Circuit board suitable capacity.5. Over load and short circuit protection.6. Visual Indication for ON/ OFF/ Trip/ Battery Charging/ Mains Failure/ Low Battery et.,7. Mode Setting For Bypass / Reset.8. 12 V 150 AH Battery - 2 Nos.9. Trolley for heavy UPS & Battery. |
| 14 | Supply erection, testing and commissioning of 1.5 TR (4500 K.cal/Hr) ABS Plastic Split type Air conditioner conforming to IS 1391 (Part-2) 1992 with Amdt No. 1 to 2 fitted with Rotory compressor operating on Non CFC Refrigerant suitable for wall mounting for operation on 230V, 50HZ single phase AC supply with 5 star rating as per BEE specification and capable of performing the functions of1) Cooling 2) Dehumidifying3) Air circulation4) FilteringThe installation works for the above split type AC units includes the following.1.Mounting / Fitting Indoor and outdoor units at their respective locations.2. Laying refrigerant pipeline of required length connecting not exceeding 3 metre Length and both units after drilling hole/holes in the wall if required.3. Insulating the suction pipe with expanded polyeurethene foam 5mm tubing.4. Laying 25 mm dia flexible PVC drain pipe to throw out the condensate water being formed within the indoor unit.5. Leakage testing the entire system unit.6. Charging refrigerant gas in the unit.7. Suitable electric wiring to be provided with 2.5 Sq.mm PVC insulated copper wire between indoor and outdoor units up to 6 Mtrs length and up to switch within 3 Meters of location of indoor unit. |
| 15 | Supply and fixing of 4 KVA electronic automatic voltage stabilizer with input range of 170-270V and output range 200-240 V with high and low voltage cut off and 3 minutes time delay relay with demonstration. |
| 16 | Supply and fixing of MS Stand for fixing the Outdoor unit. |
| 17 | Supply and Laying of 5/8” and 3/8” copper pipe |
| 18 | Supply and fixing of Water drain pipe line (1\\" PVC Pipe) |
| 19 | Supply and fixing of 1 no.6/16A two module socket , 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End |
| 20 | Supply and fixing of 2 no. 6A two module socket, 1no.6/16 A two module socket , 2 nos. 6A one module switch, 2 nos. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End |
| 21 | Supply and fixing of 20A Flush type Wall Socket 32A DP MCB complete set for AC Plug in flush with wall with earth connection (For AC Plug) |
| 22 | Supply and fixing of 6A to 32A DP MCB in DP Sheet Steel Enclosure in Flush with wall and making good of the concealed portion with Earth Connection. (Higher End) |
| 23 | Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A DP MCB as incoming and 6 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End |
| 24 | Supply and fixing of 12 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A DP MCB as incoming and 10 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End |
| 25 | Supply and fixing of 6 way Horizontal Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 No 32A 4P MCB as incoming and 18 Nos 6A to 32A SP MCB as outgoing in flush with wall with Earth connection only. Higher End |
| 26 | Supply and fixing of 32A TPNMC switch on suitable angle iron frame work with MS cable entry box with earth connection only. |
| 27 | Supply and fixing of TNEB meter board suitable for 32A single phase service connection with 32A fuse unit (500V) 32A neutral link and earthlink (1\\"x1/8\\"copper flat) on TW plank of size 375 mm x 300 mm x 19 mm with supporting TWreepers of 1\\" thick an either side with painting with suitable bolt and nuts for fixing the TW plank on wall with earth connection and inter connection with 7/20 PVC insulated copper wire from EB meter to fuse unit with 1No 40Amp 30MA Double Pole RCD / RCCB (Higher End) with suitable necessary connection |
| 28 | Supply and fixing of TNEB meter board suitable for 32A three phase service connection with 3 Nos.32A fuse unit (500V) 32A neutral link and earth link (1\\"x1/8\\"copper flat) on TW plank of size 600mmx450mmx19mm with supporting TW reepers of 1\\" thick an either side with painting with suitable bolt and nuts for fixing the TW plank on wall with earth connection and interconnection with 7/20 PVC insulated copper wire from EB meter to fuse unit with 1No 40Amp 30MA Four Pole RCD / RCCB (Higher End) with suitable necessary connection |
| 29 | Supply and run of 2 of 1.5 sq.mm (22/0.3) PVC insulated SC unsheathed Cu. Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling and making good of the concealed portion with suitable colour. |
| 30 | Supply and Run of 2 of 2.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 2.5 sq.mm copper wire and making good of the concealed portion. |
| 31 | Supply and run of 2 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 4 sq.mm copper wire and making good of the concealed portion with suitable colour. |
| 32 | Supply and run of 2 of 6 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 6 sq.mm copper wire and making good of the concealed portion with suitable colour. |
| 33 | Supply and Run of 2 of 6 sq.mm PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade on 7/20 GI wire for service connection mains. |
| 34 | Supply and Run of 2 of 6 sq.mm (84/0.3 ) PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in 25mm dia GI pipe (class B ) suitably bent at both ends with necessary angle iron upright and end support for service connection mains |
| 35 | Supply and Run of 4 of 6 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 6 sq.mm copper wire and making good of the concealed portion with suitable colour. |
| 36 | Supply and Run of 4 of 6 sq.mm PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade on 7/20 GI wire for service connection mains |
| 37 | Supply and Run of 4 of 6 sq.mm PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in 32 mm dia GI pipe (class B ) suitably bent at both ends with necessary angle iron upright and end support for service connection mains |
| 38 | Earthing as per the ISI specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm, with copper earth plate of size 125mm x 50mm x 6mm with necessary funneling arrangements with necessary masonry work and with 38 mm RCC cover slab for the brick masonry. |
| 39 | Earthing as per PWD standard with an earth electrode of 2 metre Class'B' GI pipe of dia not less than 32mm complete with necessary masonry work |
| 40 | Supply and Run of 1 of No.8 SWG copper wire in suitable PVC rigid pipe on wall / floor / ground for earth connection. |
| 41 | ADD GST 18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 15, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysOct 30, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 12 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender