BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point / Fan point / Exhaust Fan point / Call Bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch , modular plate , suitable GI box and earthing the point with 1.5 sqmm.FRLS PVC insulated copper conducotor single core cable etc. as required . |
| 2 | Group-C |
| 3 | Wirirng for Twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit , 2 way modular switch , modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 4 | Wiring for Light/ power plug wiring with 2 x 4 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 1 No. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as reqd. |
| 5 | Wiring for Circuit/ sub main Wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed PVC conduit as reqd. |
| 6 | 2 x 1.5 sq.mm + 1 x 1.5 sq.mm. earth wire |
| 7 | 2 x 2.5 sq.mm + 1 x 2.5 sq.mm. earth wire |
| 8 | 2 x 6 sq.mm + 1 x 6 sq.mm. earth wire |
| 9 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 10 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 11 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 12 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 13 | 20 mm |
| 14 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 15 | 5/6 A switch |
| 16 | 15/16 A switch |
| 17 | 3 pin 5/6 A socket outlet |
| 18 | 6 pin 15/16 A socket outlet |
| 19 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 20 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 21 | 1 or 2 Module (75mmX75mm) |
| 22 | 6 Module (200 mmX75 mm) |
| 23 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box / wooden block including connection etc as required. |
| 24 | Installation, testing and commissioning of wall barcket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 25 | Supplying and fixing call bell/buzzer suitable for single phase, 230 V, complete as required. |
| 26 | Installation, Testing and Commissioning of Ceiling Fan, including wiring the down rod of standard length (up to 30 cm) with 1.5 sq.mm FRLS PVC insulated copper conductor, single core cable etc as reqd. |
| 27 | Installation of exhaust fan in the existing opening, including making good the damage, connections, testing, commissioning etc. as required. |
| 28 | Upto 450 mm |
| 29 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board , 415volts, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnection , powder painted including, earthing etc as required. (But without MCB/RCCB/Isolator). |
| 30 | 4 way (4 + 12), Double door |
| 31 | 8 way (4 + 24), Double door |
| 32 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA 'C' curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 33 | Single Pole |
| 34 | Supplying and Fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 35 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing andcommissioning etc. as required. |
| 36 | 100 A |
| 37 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut,bolt, spring, washer excavation and re-filling etc. as required. |
| 38 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 39 | 3½ X 150 sq. mm (50mm) |
| 40 | Supply of 15W ,6500K rating LED Recessed type Round light fittings similar to Make: Philips model No. DN172 15S LED DL G2 (CDL) or its equivalent. |
| 41 | Supply of 36W LED,6500K, 2x2 Feet light fitting suitable for 230 Volts,50 Hz AC supply similar to Philips, Model no. RC370B LED36S-6500 G6 L60W60 PSU OD S6 or its equivalent to IS specification. |
| 42 | Supplying of 5 star Energy saving ceiling fans BLDC (26W to 32W), 1200mm sweep (White), Make: USHA Model: Techno Air (Without remote) or equivalent. |
| 43 | Supplying of PVC Exhaust Fan of 250 mm sweep with Louvers Make:- Havells, Model No.- Thrill Air DX or their equivalent. |
| 44 | Supply and fixing of RJ 45 ethernet wall socket (cat6) ,similar to Anchor Roma cat No. 35763S or its equivalent. |
| 45 | Supplying and drawing of CAT-6 cable 4 pair UTP 23 AWG cable in existing Medium class PVC pipe/PVC Channel etc as required. Make: CP Plus/ Havells/Polycab etc or its equivalent . |
| 46 | Supplying and fixing of Modular AC DB box including 20Amps SP MCBwith plastic enclosure and plug top including connection as required Similar to Anchor code 98488 or its equivalent. |
| 47 | Supplying and fixing Single door 4-way, triple pole and neutral, sheet steel, MCB distribution board, on surface/recess, including TPN MCB of rating 32 Amps C-type, complete with necessary connetions. make : Anchor : 98294 & 98038 |
| 48 | Supplying and fixing Wall fan of 400mm sweep (White colour) similar to Havells Sameera or its equivalents complete with necessary connetions as required. |
| 49 | Supplying of following size XLPE insulated PVC outer sheathed with galvanised round steel wire or steel srtip armoured aluminium conductor power cable of 1.1 Kv grade conforming to IS 7098 (Part-I) 1988 amended upto date. |
| 50 | 3.5 core X 150 sq. mm |
| 51 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the open surface as required. |
| 52 | Above 95 sq. mm and upto 185 sq. mm |
| 53 | Supplying and laying of DWC HDPE pipe of following size, ISI marked along with all accessories like socket, bend, couplers etc. Conforming to IS 16205 (Part 24): 2018/IS 14930 (Part 2) : 2001, complete with fitting and cutting, jointing etc. on existing duct/ ground/surface etc as required. |
| 54 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 55 | Supplyingh and laying of following size DWC HDPE pipe ISI marked alomg with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (50 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. complete as required. |
| 56 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 57 | Supplying and laying of DWC HDPE pipe of following size, ISI marked along with all accessories like socket, bend, couplers etc. Conforming to IS 16205 (Part 24): 2018/IS 14930 (Part 2) : 2001, complete with fitting and cutting, jointing etc. on surface/wall including providing clamping arrangement etc as required. |
| 58 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 59 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1.KV grade of following size in the existing DWC/PVC/RCC/ HUME/GI/METAL pipe as required. |
| 60 | Above 95 sq. mm and upto 185 sq. mm |
| 61 | Supplying and fixing of 10 Ltrs Water Heater with inlet and outlet pipe the wall surface including necessary connection etc. as required Similar to Havells Monza DX Nodel No. GHWAMGSIB010 or its equivalent. |
| 62 | Fabrication, installation, testing and commissioning of L.T Indoor type self supported cubical LT Panel board of size not less then 1.8m(H) X 1.8m(W) X 0.5m(D) , dust and vermin proof made out of 2 mm thickness Galvanised Plain(GP) sheet with 7-Tank powder coated with cubical chamber for MCCBs and rear opening with copper Busbar strips of size 25 X 6mm as required length fixed on procelain insulators and base channel of 40 mm x40 mm x 3 mm MS angle frame welded as per the direction of E in C suitable for fixing following switchgears and fittings. Also fixing of 01 set phase( RYB) Indicating LEDs (in each switchgears) and Digital Volt/Ammeter fitted on the front door conneted to the main busbar including making necessaary interconnections with 25 Sq mm copper cable/strips & lugs of respective sizes etc as required. Busbar shall be provided with colour coded rubberized sleeves bands for phases and neutral identification conforming to section 4 of CPWD specification for Electrical works part IV substation 2007. etc complete as required.a) FP MCCB 63 Amps, 18kA ( L&T DY125U Cat No.EM90984OOOHO ) = 08 Nos. with Extended rotary handle b) FP MCCB 125 Amps ,18kA ( L&T DU125D Cat No.CM90676OOLO ) = 02 Nos. with Extended rotary handle c) FP MCCB 400 Amps, 50kA ( L&T DU400N Cat No.CM98404OORO ) = 01 No. with Extended rotary handle d) Open type Manual change over switch FP 400Amps ( L&T Cat No. CO44000OOOO) = 01 No. |
| 63 | Providing Earthing with safe earthing electrode of galvanization 80 to 100 microns length 2000 mm, 48mm dia and inner space to be filled with crystaline conuctive mixture including filling - up with electrodite (Back fill Compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arragement etc. as required. (Similar to ASHLOK make SEE brand safe earthing or equivalent) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 15, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 26, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysOct 26, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender