Tender For Maintenance / Repair / Replacement / Rerouting Of Lt Electrical Panel And Lt Panel And Maintenance Of Dg Sets Panels At Various Location And At Sp Marg, Tpt Coy, 2 Signal Coy And Connecting Area Of Age E/M-Iii Under Ge (U) Water Supply Del
Tender Overview
Project Description
Tender for Maintenance / Repair / Replacement / Rerouting Of Lt Electrical Panel And Lt Panel And Maintenance Of Dg Sets Panels At Various Location And At Sp Marg, Tpt Coy, 2 Signal Coy And Connecting Area Of Age E/M-Iii Under Ge (U) Water Supply Delhi Cantt-10
BOQ
| Sl. No. | Item Description |
| 1 | Taking down old unsv LT control panel board of any size of bus bar capacity and deposited to MES store yard, taken on charge in salvage ledger as directed by Engr-in-charge |
| 2 | Supply installation, commissioning and testing LT panel outdoor type made out of 3.15 mm thick CRCA sheet (manufactured through CPRI approved manufacturers), floor mounted duly Powder Coated, dust and vermin proof with front opening arrangement with and incl foundation with PCC 1:2:4 type B1, MS channel base frame etc complete comprising of aluminium bus bar of capacity 500 Amps 4 Nos of strip 415 volts and cabinet for housing MCCBs, metering equipments, all accessories prewire with copper cable of suitable capacity. All MCCBs should be connected with aluminium busbar as per there capacities and comprising of following accessories Incoming(i) MCCB TPN, 400 Amps, breaking capacity 36 KA-01 NosOutgoing(i) MCCB TP 200 Amps, breaking capacity 36 KA :- 02No. (ii) Fully Automatic Star Delta Starter type ML-2 complete set - 02 No, (iii) Digital type voltmeter (0-500 Volts) -01 No(iv) Digital type Amp meter 0-100 Amps with CT’s & selector switch - 01 No.(v) Indicator Lamps(LED type) for motor ON/OFF indication-01 set |
| 3 | Supply installation, commissioning and testing LT panel outdoor type made out of 3.15 mm thick CRCA sheet (manufactured through CPRI approved manufacturers), floor mounted duly Powder Coated, dust and vermin proof with front opening arrangement with and incl foundation with PCC 1:2:4 type B1, MS channel base frame etc complete comprising of aluminium bus bar of capacity 600 Amps 4 Nos of strip 415 volts and cabinet for housing MCCBs, metering equipments, all accessories prewire with copper cable of suitable capacity. All MCCBs should be connected with aluminium busbar as per there capacities and comprising of following accessories (a) MCCB 4 pole 400 Amp, rupturing capacity of 36 KA (As In-coming) -01 No(b) MCCB 4 pole 250 Amps, rupturing capacity of 36 KA (As Outgoing)-02 Nos(c) Fully Automatic Star Delta Starter type ML-3 complete set - 02 No, (d) Set of Indicating lamp (one set) set of three.(e) Digital type volt meter (0-500 volts) with selector switch - 01 No.(f) Digital type Amp meter 0-100 Amps with CT’s & selector switch - 01 No. |
| 4 | Supply installation, commissioning and testing LT panel outdoor type made out of 3.15 mm thick CRCA sheet (manufactured through CPRI approved manufacturers), floor mounted duly Powder Coated, dust and vermin proof with front opening arrangement with and incl foundation with PCC 1:2:4 type B1, MS channel base frame etc complete comprising of aluminium bus bar of capacity 200 Amps 4 Nos of strip 415 volts and cabinet for housing MCCBs, metering equipments, all accessories prewire with copper cable of suitable capacity. All MCCBs should be connected with aluminium busbar as per there capacities and comprising of following accessories (a) MCCB 4 pole 160 Amp, rupturing capacity of 10 KA (As In-coming) -01 No(b) MCCB 4 pole 63 Amps, rupturing capacity of 10 KA (As Outgoing)-02 Nos(c) Fully Automatic Star Delta Starter type ML-1.5 complete set - 02 No, (d) MCB DP 32 Amps,10 KA-02 Nos(e) Set of Indicating lamp (one set) set of three.(f) Digital type volt meter (0-500 volts) with selector switch - 01 No.(g) Digital type Amp meter 0-100 Amps with CT’s & selector switch - 01 No. |
| 5 | Supply installation, commissioning and testing LT panel board, outdoor type, floor mounted, dust and vermin proof, CPRI approved factory made , fabricated out of 3 mm thick CRCA sheet suitable for accommodate the followings and for 3 phase 415 volts 50 Hz, AC supply,incl foundation with PCC 1:2:4 type B1, MS channel base frame etc complete and bus bar chamber with aluminium bus bar of 800 amp rating for 3 phase and 4 wire system duly insulated with heat shrinkable sleeved as per colour code, supported on epoxy insulators-01 set common earth bus of suitable size at bottom in side panel board with two earth terminals out side panel board, cable alley, cable glands with independent plates at bottom and complete panel board painted with powder coating in siemens grey colour all as approved & comprising as under:-Incomingi) MCCB TPN, 650A, , breaking capacity 50 KA-01 NosOut Going(a) MCCB TP, 200A, , breaking capacity 50 KA-03 Nos(b) Fully Automatic Star Delta Starter type ML-3 complete set - 03 No, (c) Digital type voltmeter (0-500 Volts) -01 No(d) Digital type Amp meter 0-100 Amps with CT’s & selector switch - 01 No.(e) Indicator Lamps(LED type) for motor ON/OFF indication-01 set |
| 6 | Supply and fixing in replacement, installation, testing and commissioning of feeder pillar box ,outdoor type cubical shape,three phase, 4 wire, Al bus bar for phases and neutral made out of CRCA sheet 3.15 mm thick ,factory fabricated , CPRI approved , powder coated ,dust and vermin proof , provn for ventilation , angle iron frame and four legs of 50x50x6mm thick angle iron ,2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level , grouting properly and of suitable size to accommodate the items mentioned below and having separate compartment /chambers for cable gallery busbar ,switch gear etc all as specified and comprising of following including necessary cable connections to the MCCBs, voltmeter, Ammeter and cable lugs etc .(a) Al bus bar with PVC sleeve suitable for 200 amps for phase & 200 Amp for neutral - 01Set.(b) Voltmeter,digital type 0- 500 volt,with selector switch - 01 set (c) Ammeter Digital type 0-100Amps, with selector switch and CT'-1set(d) Phase indicating lamps LED type ( red , yellow, blue) 01 set(e) Incoming MCCB 100 Amp 3 pole 25 KA with adjustable thermal and fixed magnetic release -01 No(f) outgoing MCCB 63 Amp 3 pole 16 KA with adjustable thermal and fixed magnetic release -02No(g) FASD Starter ML 1.5 FASD with MS sheet enclosure -01 Nos Make-L&T(h) Analog time switch -01 No (j) Single phase preventer-01 No(k) Phase sequence corrector for complete three phase system - 01 Set |
| 7 | Supply,fixing,connecting and testing ON LOAD change over switch,4 pole,415 volt,AC,with SS enclosure,side handle operated including necessary electrical connection of 400 Amps capacity complete all as specified and directed by Engr-in-charge. |
| 8 | Supply and fixing in replacement, installation, testing and commissioning of automatic security ligthing control panel with enclosure, MCB/MCCB incomer, outgoing MCBs, contactors, manual/electronic timer, selector switches, indicating lamps, internal wiring terminal blocks, earthing, labeling all necessary accessories for complete and proper operation , provn for ventilation , angle iron frame and four legs of 50x50x6mm thick angle iron ,2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level ,and taking down the existing from site complete all as specified and directed by Engr-in-Charge. i) MCB TP , 32A, , breaking capacity 25 KA-01 Nosii) Power contactor 32Amps -01 nosiii) Analog timer -01 |
| 9 | Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr deep for pipe line in ordinary soft/loose soil getting out and levelling of bottom surface to required level complete all as specified and directed. |
| 10 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed. |
| 11 | Removing excavated material from site to a distance not exc 50mtr away and depositing where directed not exc 1.5mtr from the starting point complete all as specified and directed. |
| 12 | Supply & laying cable LT XLPE insultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 35 Sq mm including taking down the existing from site complete all as specified and directed. |
| 13 | Supply & laying cable LT XLPE insultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 50 Sq mm including taking down the existing from site complete all as specified and directed. |
| 14 | Supply & laying cable LT XLPE insultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 95 Sq mm including taking down the existing from site complete all as specified and directed. |
| 15 | Supply & laying cable LT XLPE insultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 120 Sq mm including taking down the existing from site complete all as specified and directed. |
| 16 | Supply & laying of Sub Class 'B' brick laid across the cable above the sand cushioning for protection of cable complete all as specified and directed |
| 17 | M/L for sand filling in cable ducts/ trenches with and including removing old sand to a distance not exceeding 50 mtr away and depositing where directed by Engineer-in-charge. |
| 18 | M&L earthing complete with galvanised steel earth plate electrode 60x60 cmx 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below nominal ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanised iron strip 32x6 mm as earthing lead by mean of bolts, nuts, check nuts and washer of galvanised iron or steel all as shown in Electrical plate No-3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed.(Note:- GI strip 32x6mm upto 7.5Rm shall be included in quoted unit rate and if extra required the same shall be measured and paid seperately under respective items.) |
| 19 | S&F GI Strip 32 x 6 mm earth continuty including necessary connection, nuts, bolts, washers complete all as specified and directed |
| 20 | Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m. |
| 21 | S&F in replacement 3 pole power contactor ML-12 ,300 Amps coil voltage 415 volts, 50 HZ |
| 22 | All as per srl item No 21 above herein above but type ML-6, 110 Amps |
| 23 | All as per srl item No 21 above herein above but type ML-4, 70 Amps |
| 24 | All as per srl item No 21 above herein above but type ML-3, 40 Amps |
| 25 | All as per srl item No 21 above herein above but type ML-1.5, 25Amps |
| 26 | Supply and fixing in replacement of FASD star delta starter type ML-1.5 |
| 27 | Supply and fixing in replacement of FASD star delta starter type ML-2 |
| 28 | Supply and fixing in replacement of FASD star delta starter type ML-3 |
| 29 | Supply and fixing LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. |
| 30 | M&L for Providing PCC (1:4:8) type D-2 using 40mm graded crushed stone aggregate as in foundations filling mass concrete bed of pipe etc complete all as specified and directed at site. |
| 31 | M&L for Provinding PCC (1:2:4) type B-1 using 20mm grded crushed stone aggregate as in coping bed plate including weathering slightly rounded or chamfered angles and throating etc all as directed.,complete all as specified and directed at site. |
| 32 | Supply and fixing in replacement 60 watt LED lumens street light 115 Lm/watt new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having TOP Opening seperate driver compartment with IP-66 protection and impact resistance of IK07 including making connections with GI pipe 0.6 mtr angle bracket fixing on wall using suitable fastners and connectng to ceiling rose with appropriate copper wire complete all as specified and directed. |
| 33 | Taking up existing CI/DI water mains of the following bore size including all fittings complete all as specified and as directed :- |
| 34 | 300 mm bore pipe. |
| 35 | 400 mm bore pipe. |
| 36 | Supply, laying jointing, testing of DI pipe with class-K-7 spigot socketed ends, conforming to IS-8329 laid in trenches including providing route indicators of suitable height and laying at spacing of @ 50m center to center at GL mentioning name of contractor, date of execution & CA No with name of work & rubber gasket (Tyton) joints with jointing material & route indicators of the following sizes including taking down of existing CI/DI pipe complete all as specified and directed by Engineer-in-Charge:- Note 1: - Excavation & earth work shall be measured and paid seperately under respective items of BOQ.Note 2:- Contractors will provide route indicators mild steel body with top 150 mm plate 3mm thick and height not less than 300mm above finished GL at suitable intervals as directed by EIC. Cost of route indicators shall be deemed included in quoted unit rates.Note 3:- Layout plan for laying of DI pipe shall be given by EIC in writing.Note 4 :- Cost of Rubber gasket joints (Tyton Joint) included in quoted unit rates. |
| 37 | 300 mm bore pipe. |
| 38 | 400 mm bore pipe. |
| 39 | M&L for Painting of LT Panel after complete removing of old paint by paint removers or burning off by blow lamps and cleaning with scrapers, any number of coats, any width or girth from the existing MS Base frame of Centrifugal Motor and Pumps of Cap of 10HP to upto 200 HP and Painting of LT Panel by applying two coat of syenthetic enamel paint over a coat of red oxide primer complete all as specified and directed |
| 40 | Supply and fixing in replacement Fire hose real drum suitable for 20 mm dia rubber hose pipe upto 30 mtr length complete all as specified and directed. |
| 41 | Supply and fixing in replacement manual call point break glass type enclosed in aluminium cast alloy body of 3 mm thickness complete with chain and harmer and incl inscriber in case of fired break glass complete all as specified and directed |
| 42 | Supply and fixing in replacement 2 way fire brigade hydrant including nuts, bolts, washer and rubber flanges etc complete all as specified and directed |
| 43 | Supply and fixing fire hydrant post/stand post made out of 80 mm dia MS Pipe heavy duty class 'C' both ends flanged 1.5 mtr height complete all as specified and directed. |
| 44 | Supply, fixing, in replacement cast Iron Sluice Valve 100 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body, Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed |
| 45 | Supply, fixing, in replacement cast Iron Sluice Valve 150 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body, Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed |
| 46 | M&L prepration of painting to existing steel surface for fire cabinet box with one coat primer and two coat of synthetic enamel paint including scratching old paint complete all as specified and directed |
| 47 | M&L for welding work for existing door, hinges, handels and locking arrangement complete all as specified and directed (Note:- Each butt weld not exe 2cm shall be measured and paid as one unit.) |
| 48 | Supply and fixing MS Pipe heavy duty class C of size 100 mm bore heavy grade including necessary nut and bolts with washers required at site condition complete all as specified and directed. |
| 49 | Supply and laying in replacement of MS Pipes \\"Heavy grade\\" with all fittings as required at site laid in floors or fixed to walls and ceilings including welding as required at site and removing old rusted pipe of size 150mm bore complete all as specified and directed |
| 50 | Supply and fixing in replacement flanges duly welded on ends of MS pipe, flange size not less than 20 mm thick incl nuts and bolts and washer etc reqd at site complete all as specified and directed of following sizes |
| 51 | 100 mm bore |
| 52 | 150 mm bore |
| 53 | M&L Machine pressed precast concrete interlocking paverblocks any shape and size confirming to IS 15658-2006 of 60 mm thick, M-40 Grade with grey cement and no pigments, over 25 mm thick sand cushioning including taking down existing pavers complete all as specified and as directed. |
| 54 | An amount of Rs 1,10,850.00 shall be deducted from BOQ on account of schedule of credit Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender