Tender For Provision Of Stand By Ht Cable From Hallomajra To N Area And Augumentation To Ht Electric Supply At N Area Under Ge Chandigarh
Tender Overview
Project Description
Tender for Provision Of Stand By Ht Cable From Hallomajra To N Area And Augumentation To Ht Electric Supply At N Area Under Ge Chandigarh
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 03-Nov-2026 | CORRIGENDUM NO 01 | Date | 18-Nov-2026 |
| 2 | 11-Nov-2026 | CORRIGENDUM02 | Date | 23-Nov-2026 |
| 3 | 03-Nov-2026 | CORRIGENDUM NO 01 | Date | 18-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply and fixing of 11KV Extensible Outdoor duty (IP 55 enclosure) SF6 gas insulated 4-way motor operated Ring Main Unit comprising of 2 nos. 630 Amps Vacuum Circuit Breaker as incomer and 2nos. 630 AmpsVacuum Circuit Breaker as outgoing , cable termination from the front, breaking capacity 21KA/3sec (Internal Arc Classification AFLR 21kA-1sec with Bottom Exhaust both for tank and cable box as per IEC 62271-200), enclosed in insulated welded stainless steel tank having IP67 Degree of Protection, leak rate of SF6 gas less than 0.1% and tested as per IEC 60056/60694/60298. Protection CTs shall be ring core type, complete all as specified and directed. The outer enclosure shall have IP 55 protection, it shall be Top Opening Canopy type, Indoor RMU placed inside Outdoor Enclosure shall not be acceptable. Both the Load break switch and Breaker shall have line side earth switch. Both incomer shall be electrically & mechanically interlock. (Incoming From Hallomajra Feeder RMU and RMU No-1) |
| 2 | (A) NOTE:- Other details:- System Particulars: (i) Nominal System Voltage : 11kV. (ii) Voltage variation on supply side : ±10 %.(iii) Corresponding Highest System Voltage: 12kV. (iv) Frequency : 50 Hz with ± 3 % tolerance.(v) Number of Phase : 3 Phases. (vi) Neutral earthing : Solidly earthed. (vii) Fault level (minimum) kA /Sec : 25/1).(viii) Lightning Impulse Withstand Voltage (kVp) : 75 (ix) One minute dry/wet power frequency withstand voltage primary (kV rms) : 28KV(x) Rated Dynamic Withstand Current (kAp) : 52.5KA.(xi) Number of Short Circuit Operations at rated short circuit current of 25 kA for Breaker - 50 Nos.(xii) Earth switch shall have 5 closing operation at short circuit current (making operations E2 class) independent of breaker. Earth switch manual closing shall be driven by a fast acting / snap action mechanism, independent of operator and VCB action.(xiii) All operation, interlock, cable terminations and door shall be front side only. |
| 3 | (B) Applicable Standards for this RMU scope of work - IEC 62271-200. (i) The Ring Main Units shall confirm to the latest applicable, IEC 62271-100, IEC 62271-200. (ii) All live parts, bus bars, shall preferably be enclosed in non- magnetic and non-ferrite grade stainless steel tank Grade SS441 of minimum 2 mm thickness. The RMU shall be type tested for internal arc test of 21KA/1 sec AFLR with Bottom Exhaust for Safety of Personnel for both Tank as well as Cable Compartment as per IEC62271-200. The outer enclosure shall have IP 55 protection for complete switchgears, however it shall be Top Opening Canopy. The protection relay shall be for 3 O/C + 1E/F (IDMT Type) Self powered numerical protection relay with low and high set of over current and earth fault , MODBUS communication along with RS 485 Port / USB Port. (iii) Internal Arc Classification shall be with Bottom exhaust only. RMUs shall be manufactured, inspected, and invoiced from the OEM factory. (iv) Wireless Temperature & climatic sensor shall be provided, Thermal Sensors to be mounted in Cable chamber on each function on cable termination and one number of wireless climatic sensor to be mounted on RMU at suitable location to monitor temperature and humidity data on HMI though PLC. (v) 1 set of surge arrester fix in outgoing way. (vi) VCB, Numerical Relay, HMI, FRTU and Thermal / climatic sensor shall be of same make for better functioning, maintenance, and coordination. |
| 4 | (C) Air Insulated Bus Connected Unit comprising the following:- (1) Air Insulated enclosure with necessary bus connection via bushing. VT’s from the manufacturer and according to IS 3156 shall beaccepted. (2) 11KV/rt3/110V/rt3; 50VA class 0.5. Single phase bus PT for metering. (3) 11KV/230V AC,1KVA control transformer. (4) MFM – EM 6400 NG Class0.5 for each Incomer. (5) Metering CT Class 0.5, 2.5 VA.(D). Accessories :- (1) Antireflex operating handle. (2) Battery 24V DC , 12Ah. (3) Battery charger (I/P-230V AC, O/P - 24V DC). (4) Manometer with remote contact.(E) FRTU per RMU shall be provided with provision to send data on SCADA |
| 5 | Supply and fixing of 11KV Extensible Outdoor duty (IP 55 enclosure) SF6 gas insulated 3-way motor operated Ring Main Unit comprising of 1 nos. 630 Amps Vacuum Circuit Breaker as incomer and 2nos. 630 Amps Vacuum Circuit Breaker as outgoing , cable termination from the front, breaking capacity 21KA/3sec (Internal Arc Classification AFLR 21kA-1sec with Bottom Exhaust both for tank and cable box as per IEC 62271-200), enclosed in insulated welded stainless steel tank having IP67 Degree of Protection, leak rate of SF6 gas less than 0.1% and tested as per IEC 60056/60694/60298. Protection CTs shall be ring core type, complete all as specified and directed. The outer enclosure shall have IP 55 protection, it shall be top opening canopy type. Both the Load break switch and Breaker shall have line side earth switch. (Hallomajra TOP) |
| 6 | (A) NOTE:- Other details:- System Particulars: (i) Nominal System Voltage : 11kV. (ii) Voltage variation on supply side : ±10 %. (iii) Corresponding Highest System Voltage: 12kV. (iv) Frequency : 50 Hz with ± 3 % tolerance. (v) Number of Phase : 3 Phases.(vi) Neutral earthing : Solidly earthed.(vii) Fault level (minimum) kA /Sec : 25/1). (viii) Lightning Impulse Withstand Voltage (kVp) : 75(ix) One minute dry/wet power frequency withstand voltage primary (kV rms) : 28KV (x) Rated Dynamic withstand Current (kAp) : 52.5KA. (xi) Number of Short Circuit Operations at rated short circuit current of 25 kA for Breaker - 50 Nos.(xii) Earth switch shall have 5 closing operation at short circuit current (making operations E2 class) independent of breaker. Earth switch manual closing shall be driven by a fast acting / snap action mechanism, independent of operator and VCB action.(xiii) All operation, interlock, cable terminations and door shall be front side only. |
| 7 | (B) Applicable Standards for this RMU scope of work - IEC 62271-200. (i) The Ring Main Units shall confirm to the latest applicable, IEC 62271-100, IEC 62271-200. (ii) All live parts, bus bars, shall preferably be enclosed in non- magnetic and non-ferrite grade stainless steel tank Grade SS441 of minimum 2 mm thickness. The RMU shall be type tested for internal arc test of 21KA/1 sec AFLR with Bottom Exhaust for Safety of Personnel for both Tank as well as Cable Compartment as per IEC62271-200. The outer enclosure shall have IP 55 protection for complete switchgears, however it shall be Top Opening Canopy . The protection relay shall be for 3 O/C + 1E/F (IDMT Type) Self powered numerical protection relay with low and high set of over current and earth fault , MODBUS communication along with RS 485 Port /USB Port. (iii) Internal Arc Classification shall be with Bottom exhaust only. RMUs shall be manufactured, inspected, and invoiced from the OEM factory. (iv) Wireless Temperature & climatic sensor shall be provided, Thermal Sensors to be mounted in Cable chamber on each function on cable termination and one number of wireless climatic sensor to be mounted on RMU at suitable location to monitor temperature and humidity data on HMI though PLC. (v) 1 set of surge arrester fix in outgoing way. (vi) VCB, Numerical Relay, HMI, FRTU and Thermal / climatic sensor shall be of same make for better functioning, maintenance, and coordination. |
| 8 | (C) Air Insulated Bus Connected Unit comprising the following, (1) Air Insulated enclosure with necessary bus connection via bushing. VT’s from the manufacturer and according to IS 3156 shall be accepted. (2) 11KV/rt3/110V/rt3; 50VA class 0.5. Single phase bus PT for metering. (3) 11KV/230V AC, 1KVA control transformer. (4) MFM – EM 6400 NG Class0.5 for each Incomer. (5) Metering CT in respective Function’s Cable Compartment , Class 0.5, 2.5 VA. (D). Accessories :- (1) Antireflex operating handle. (2) Battery 24V DC , 12Ah. (3) Battery charger (I/P- 230V AC, O/P - 24V DC). (4) Manometer with remote contact.(E) FRTU per RMU shall be provided with provision to send data on SCADA. |
| 9 | Supply and fixing of 11KV Extensible Outdoor duty (IP 55 enclosure) SF6 gas insulated 6-way motor operated Ring Main Unit comprising of 2 nos. 630 Amps Vacuum Circuit Breaker as incomer and 4nos. 630 Amps Vacuum Circuit Breaker as outgoing , cable termination from the front, breaking capacity 21KA/3sec (Internal Arc Classification AFLR 21kA-1sec with Bottom Exhaust both for tank and cable box as per IEC 62271-200), enclosed in insulated welded stainless steel tank having IP67 Degree of Protection, leak rate of SF6 gas less than 0.1% and tested as per IEC 60056/60694/60298. Protection CTs shall be ring core type, complete all as specified and directed. The outer enclosure shall have IP 55 protection, it shall be Top Opening Canopy type. Both the Load break switch and Breaker shall have line side earth switch. Both incomer shall be electrically & mechanically interlock. (RMU No-3 & 4) |
| 10 | (A) NOTE:- Other details:- System Particulars: (i) Nominal System Voltage : 11kV. (ii) Voltage variation on supply side : ±10 %.(iii) Corresponding Highest System Voltage: 12kV. (iv) Frequency : 50 Hz with ± 3 % tolerance.(v) Number of Phase : 3 Phases. (vi) Neutral earthing : Solidly earthed. (vii) Fault level (minimum) kA /Sec : 25/1). (viii) Lightning Impulse Withstand Voltage (kVp) : 75 (ix) One minute dry/wet power frequency withstand voltage primary (kV rms) : 28KV (x) Rated Dynamic Withstand Current (kAp) : 52.5KA. (xi) Number of Short Circuit Operations at rated short circuit current of 25 kA for Breaker - 50 Nos. (xii) Earth switch shall have 5 closing operation at short circuit current (making operations E2 class) independent of breaker. Earth switch manual closing shall be driven by a fast acting / snap action mechanism, independent of operator and VCB action. (xiii) All operation, interlock, cable terminations and door shall be front side only. |
| 11 | (B) Applicable Standards for this RMU scope of work - IEC 62271-200. (i) The Ring Main Units shall confirm to the latest applicable, IEC 62271-100, IEC 62271-200. (ii) All live parts, bus bars, shall preferably be enclosed in non- magnetic and non-ferrite grade stainless steel tank Grade SS441 of minimum 2 mm thickness. The RMU shall be type tested for internal arc test of 21KA/1 sec AFLR with Bottom Exhaust for Safety of Personnel for both Tank as well as Cable Compartment as per IEC62271-200. The outer enclosure shall have IP 55 protection for complete switchgears, however it shall be Top Opening Canopy . The protection relay shall be for 3 O/C + 1E/F (IDMT Type) Self powered numerical protection relay with low and high set of over current and earth fault , MODBUS communication along with RS 485 Port /USB Port. (iii) Internal Arc Classification shall be with Bottom exhaust only. RMUs shall be manufactured, inspected, and invoiced from the OEM factory. (iv) Wireless Temperature & climatic sensor shall be provided, Thermal Sensors to be mounted in Cable chamber on each function on cable termination and one number of wireless climatic sensor to be mounted on RMU at suitable location to monitor temperature and humidity data on HMI though PLC. (v) 1 set of surge arrester fix in outgoing way. (vi) VCB, Numerical Relay, HMI, FRTU and Thermal / climatic sensor shall be of same make for better functioning, maintenance, and coordination. |
| 12 | (C) Air Insulated Bus Connected Unit comprising the following, (1) Air Insulated enclosure with necessary bus connection via bushing. VT’s from the manufacturer and according to IS 3156 shall be accepted. (2) 11KV/rt3/110V/rt3; 50VA class 0.5. Single phase bus PT for metering. (3) 11KV/230V AC, 1KVA control transformer . (4) MFM – EM 6400 NG Class0.5 for each Incomer. (5) Metering CT class 0.5, 2.5 VA. (D) Accessories :- (1) Antireflex operating handle. (2) Battery 24V DC , 12Ah. (3) Battery charger (I/P- 230V AC, O/P - 24V DC). (4) Manometer with remote contact. (E) FRTU per RMU shall be provided with provision to send data on SCADA. |
| 13 | Shifting of Existing RMU,11 KV,400 A,Outdoor,3 Way (01 Incoming Load Break Switch & 02 Outgoing Load Break Switch) including Suitable size of PCC plinth with HT supply Connection complete all as specified and directed. |
| 14 | Supply and install HT 11 KV outdoor gang operated device air -break switch suitable for horizontal or vertical mounting switch dropout fuse having 12 insulators of rating 200 amps complete all as specified and directed. |
| 15 | Supply and fixing lightening arrestors expulsion type complete with all fittings transmission class discharge capacity 65 KA ,11 KV complete all as specified and directed. |
| 16 | Supply and fixing of arial bunched conductor having phase conductor of stranded compacted circular aluminium conductor screen of extruded semi conducting compound extruded XLPE insulated 11000 volts grade , insulation screen of extruded semi conducting compound over all metellic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS 7098 Part-II of size 3x120 SQMM + 1x 95 SQMM including Dead-End Clamp,Suspension clamp asemmby,pole bracket/pole clamp,stainless steel band & buckles,Tee joint/Tee-off connector kit,Compression connectors,Lugs,Eye hooks UV resistant cable ties etc,complete all as specified and directed. |
| 17 | Supplying, laying, jointing, testing and commissioning 120 Sqmm, 3 core, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminum conductors, 11 KV grade of , IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole complete all as specified and directed.(Note :- Excavation & earth work, GI pipe for laying of cable, sand cushioning, cable protection cover shall be measured and paid for seprately under respective items of the schedule.) |
| 18 | Excavation in trenches in SOFT & LOOSE soil not exceeding 1.5 metre deep and not exceeding 1.5 metre wide and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes for HT Poles etc, complete all as specified and directed. Note : (i) Excavation shall be made carefully in order to avoid damage of existing cables and protection covers (ii) The excavation work shall be carried out in short lengths for locating fault in under ground cables at different locations. |
| 19 | All as per item No 9 here-in-before but exceeding 1.5 deep and not exceeding 3 metre width complete all as specified and directed. |
| 20 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick each in SOFT & LOOSE soil, complete all as specified and directed. |
| 21 | Material and labour for sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable) complete all as specified and directed.Note- Punned quantity of sand shall be measured for purpose of payment. |
| 22 | Material and labour for Plain cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate in foundation including necessary formwork,complete all as specified and as directed. |
| 23 | Material & Labour for PCC (1:3:6) type C-1 (using 20 mm graded black trap/granite/balast stone aggregate) around the pole including necessary form work complete all as specified and directed. |
| 24 | Material & Labour for PCC (1:2:4) type B-1 (using 20 mm graded black trap/granite/balast stone aggregate) for coping of the pole including necessary form work complete all as specified and directed. |
| 25 | Material and labour for Galvanised iron tubing light grade, 100 mm bore of tube, fixed on walls / laid in trenches as protection pipe for under ground cable including all fittings, clamps etc complete all as speified and directed.(Note - Excavation to be paid separately in respective items) |
| 26 | Supply, jointing and testing cable jointing kit of 11 KV grade cable for straight through, heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 Sq mm including taking down old unserviceable one complete all as specified and directed. |
| 27 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including GI pipe of 100 mm dia suitable for 0.4 mpa working pressure, complete all as specified and as directed.Note:-1. Length of bore hole under road /pavement shall be as per site requirement.2. GI pipe shall be measured and paid separately under respective items. |
| 28 | Supply, jointing and testing cable jointing kit of 11 KV grade cable for indoor termination, Heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 Sq mm including taking down old unserviceable one complete all as specified and directed. |
| 29 | Supply, jointing and testing cable jointing kit of 11 KV grade cable for outdoor termination, Heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sq mm including taking down old unserviceable one complete all as specified and directed. |
| 30 | Removal of surplus/excavated soil to a distance not exceeding 50 metre distance and depositing where directed at a level not exceeding 1.5 m above the starting point ,complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 31 | Removal of surplus/excavated soil to a distance not exceeding 50 metre distance and depositing where directed at a level not exceeding 1.5 m above the starting point ,complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 1 dayCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender