Tender For Electrical Repair & Renovation For 2 No. maintenance of Quarter, 2 Nos. Nurshing Staff Quarter And 4 Nos. Group D Quarter At Silbarihat Phc In The District Of Alipurduar-----Electrical Installation Work.
Tender Overview
Project Description
Tender for Electrical Repair & Renovation For 2 No. maintenance of Quarter, 2 Nos. Nurshing Staff Quarter And 4 Nos. Group D Quarter At Silbarihat Phc In The District Of Alipurduar-----Electrical Installation Work.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 28-Oct-2026 | DateCorri1 | Date | 17-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | SUB-HEAD - Distribution Wiring |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 3 | Group B |
| 4 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 5 | 3 x 1.5 sq. mm |
| 6 | 3 x 2.5 sq. mm |
| 7 | 3 x 4 sq. mm |
| 8 | 3 x 6 sq. mm |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 20 mm |
| 11 | 25 mm |
| 12 | SUB-HEAD - PLUGS & SOCKETS |
| 13 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 14 | 5/6 A switch |
| 15 | 15/16 A switch |
| 16 | 3 pin 5/6 A socket outlet |
| 17 | 6 pin 15/16 A socket outlet |
| 18 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 19 | 4 Module (125mmX75mm) |
| 20 | 6 Module (200mmX75mm) |
| 21 | Supplying and fixing 2-Module GI box with modular plate and cover in front on surface or in recess, including providing and fixing 15/16 A modular socket outlet ,connections etc. as required. |
| 22 | SUB-HEAD - BDB,PDB,VTPN ETC |
| 23 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 24 | 16 way , Double door |
| 25 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 26 | Single pole |
| 27 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 28 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 29 | SUB-HEAD - Laying of Cable |
| 30 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 31 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 32 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 33 | 2 X 6 sq. mm (19mm) |
| 34 | SUB-HEAD - SUPPLY & FIXING OF FANS |
| 35 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 36 | Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar, bent to shape with hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete. |
| 37 | Installation, Testing and Commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable etc. as required. |
| 38 | Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 39 | Upto 450 mm sweep |
| 40 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 41 | SUB-HEAD - Supply & Fixing of Light Fittings |
| 42 | Installation, Testing and Commissioning of pre-wired, fluorescent fitting / compact fluorescent/ LED fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 43 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. |
| 44 | SUB-HEAD - Compound Light |
| 45 | Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM |
| 46 | (Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt). |
| 47 | 45 watt |
| 48 | SUB-HEAD - Call Bell |
| 49 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 50 | SUB-HEAD - Earthing Installation |
| 51 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt) as required. |
| 52 | Supplying and laying 6 SWG G.I. wire at 0.50 Meter below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 53 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 54 | PART-B - PWD SOR and Non-Schedule Items |
| 55 | SUB-HEAD - MISCELLANEOUS |
| 56 | Dismantling the existing fitting, fixture, DBs, etc from old position and reinstalled the same useable accessories as per the site situation with own tools and tackles. |
| 57 | Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 58 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint |
| 59 | SUB-HEAD - Supply of Cable |
| 60 | Supplying and delivery of following size Armoured cables XLPE/PVC insulated are designed for 1.1 kV Stranded Aluminium conductor, high tensile galvanized steel wire/strip armour for mechanical protection, and PVC/FR PVC outer sheathing power cable of following size.(IS 7098 Part - 1/2011 with Up To Date Amendments.) |
| 61 | 2 core 6 Sq. mm |
| 62 | SUB-HEAD - FANS |
| 63 | Supply & delivery of 230 V, 50 Hz, single phase, 58 watts, 56\\" (1400 mm) Sweep, speed 300 rpm (minimum), A.C. Ceiling Fan and class ofinsulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod (14 SWG & higher thickness), 2 nos. canopies, safety rope, copperwinding, steel/Al body. Power Factor not less than 0.9 and minimum airdelivery 250 cu.m/min (minimum), without Regulator including capacitorwith safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 64 | Supply & delivery of 230 V, 50 Hz, single phase, 40 watts , 9\\" (230 mm) Sweep, speed 1350 rpm (minimum), A.C. Exhaust Fan and class of insulation: B, 3 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 650 cmh (minimum) including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required.[Make: EPC/Crompton/Usha/Havells/Orient] |
| 65 | SUB-HEAD - Supply of Light Fittings |
| 66 | Supply & Fixing of 240V, 9 watt LED lamps of following wattage with glare free light distribution having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 67 | Supply & Delivery of minimum10-12 Watt LED Bulkhead light fittings complete with all accessories having die cast aluminium housing finished in premium white powder coating with CCT (5700K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Crompton/ Wipro or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 68 | Supplying and delivery of LED Industrial Batten light made of CRCA Sheet Body (Thickness ≥ 0.50 mm) and construction as per relevant IS, along with LED lamp (Opal finish polycarbonate housing with Aluminium end-cap) voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range 0o to 40o C, internal surge protection of 2.5 KV(internal) with Short & Open circuit protection , THD < 10% , P. F.≥0.9, IP20, CRI >80, and minimum 40000 Burning Hours (Life projection shall be calculated as per TM-21 methodology), CCT 5700°K /6500°K, and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing, with Minimum 5 year OEM warranty. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted.(System lumen efficacy ≥115 lm/Watt) |
| 69 | Single fittings along with S/F of 1 no. 18-20 W LED lamp as per specification |
| 70 | Note: 1) All the above rates should be quoted inclusive of all taxes, duties and all ancilery charges with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 16 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender