Tender For Renovation Of electrical installation Work Including Supply Installation Testing and Commissioning of Fire Detection System Of Pratyay Half Way Home Building In Continuation Of Complete Civil Renovation Works At Lumbini Park Mental Hospita
Tender Overview
Project Description
Tender for Renovation Of electrical installation Work Including Supply Installation Testing and Commissioning of Fire Detection System Of Pratyay Half Way Home Building In Continuation Of Complete Civil Renovation Works At Lumbini Park Mental Hospital (Old C Us) Kolkata - 700 039
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling charges of electrical installations from existing position including careful removal, making safe disconnected points and stacking serviceable materials as directed, comprising removal of fluorescent/LED tube light fittings, ceiling/exhaust fans with downrod and accessories, concealed internal wiring with conduit, switch boards, sockets, regulators, distribution boards and other associated electrical accessories, including disconnection of supply, without damage to reusable materials and proper disposal of unserviceable materials as per departmental norms. |
| 2 | Semi-skilled Labour |
| 3 | Unskilled Labour |
| 4 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 5 | 6 Way,(4+18) Double door [Make: Legrand / L&T/Siemens/Crabtree ] |
| 6 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 7 | 12 way , Double door[Make: Legrand / Siemens/L&T] |
| 8 | Supplying and fixing of 63Amp, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make: Legrand/Siemens/ Crabtree/L&T ) |
| 9 | Supplying and fixing of 40 Amp, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make: Legrand/Siemens/ Crabtree/L&T ) |
| 10 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make: Legrand/Siemens/ Crabtree/L&T ) |
| 11 | Single Pole 5-32A |
| 12 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable (Make: Polycab / Finolex / RR kabel) in surface/ recessed medium class PVC conduit(Precision make), with modular switch, modular plate, (Make-Legrand) suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 13 | Group B |
| 14 | Group C |
| 15 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 16 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 17 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 18 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 19 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 20 | Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. |
| 21 | 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 22 | 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 23 | 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC |
| 24 | 4x80/0.4 (16 sqmm) + 2x84/0.3 (10 sqmm) as ECC |
| 25 | Supply & Delivery of 240V , 9W LED Bulb B22/ E27 Base LED lamps of following wattage with glare free light distribution having minimum luminous efficiency of 100 Lm/ Watt or better 8s 50,000 LED burning hours or more. [Make- Philips/Wipro / Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 26 | Supply and Delivery of minimum 10-12 Watt LED Bulkhead light fittings complete with all accessories having die cast aluminium housing finished in premium white powder coating with CCT (5700K-6500K} having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] |LED lamps & accessories shall have BEE certifications |
| 27 | Fixing only lamp to batten point. |
| 28 | Supplying and fixing 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Brand approved by EIC), along with Supplying and fixing 12 Module (200mmX150mm), GI box along with modular base & cover plate for modular switches in recess etc. as required. and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 29 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. |
| 30 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 31 | Supply and Delivery of 4 feet Industrial box type single LED tube fitting incl.Supply & Delivery of 1 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/ Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 32 | Supply and Delivery of 4 feet Industrial box type twin LED tube fitting incl.Supply & Delivery of 2 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT ((5000K-6500K) having minimum luminous efficiency of 105 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro /Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] |LED lamps 8s accessories shall have BEE certification] |
| 33 | Installation, Testing and Commissioning of pre-wired, fluorescent fitting / compact fluorescent/ LED fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 34 | Installation, Testing and Commissioning of pre-wired, fluorescent fitting / compact fluorescent/ LED fitting of all types, complete with all accessories and tube/lamp etc., including supplying and fixing ball and socket arrangement, 2 Nos. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connections with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 35 | Supply and Delivery of 230V, 1-Ph, AC ceiling fan of follwing size incl. all accessories. (Make- Crompton / Usha / Orient) [BEE star rated] |
| 36 | Sweep Size- 1200 mm (48''), Wattage ≤ 55 Watt, R.PM ≤ 380, Air Delivery ≥ 210 |
| 37 | Supply & Delivery of 230V, 50Hz, 450 mm sweep heavy duty full metal body wall bracket fan having wattage ≤ 90 Watt, RPM ≤ 1350, Air Displacement (In CMM) ≥ 100 complete with all accessories. (Make - Orient/Crompton/ EPC) [BEE star rated] |
| 38 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 39 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS |
| 40 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length. |
| 41 | Supply and Delivery of 220V, Single Phase, 50 Hz A.C heavy duty exhaust fan of following sizes having complete metal body. (Make- EPC/ USHA/ Orient CROMTON) [ISI mark, IP55 rated] |
| 42 | 300 mm (12\\"), 4 Blade, RPM ≤ 1420 , Wattage ≤ 90 Watt, Sound level ≤ 56 dB, Air Displacement (In CMH) ≥ 1120 |
| 43 | Fixing only exhaust fan after making holes in wall as per GS |
| 44 | 12\\" Exhaust |
| 45 | Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long) |
| 46 | 30 cm Exhaust fan (12\\") |
| 47 | Supply & Delivery of 240V, 90 Watt LED street lights with optic lens and polycarbonate diffuser having following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection 8s incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminou s efficiency of 110 Lm/ Watt or better 8s 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] {LED lamps & accessories shall have BEE certification] |
| 48 | Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projectedfrom the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc. |
| 49 | Supply & Delivery of 250 Watt , 240V, LED flood lights with optic lens and polycarbonate diffuser having following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certificationl |
| 50 | Fixing only Floodlight Fitting with suitable tie clamps and MS plate for mounting on Pole/Tower or similar structure |
| 51 | S & F 25A timer controller in double door phosphatised powder coated 10 way SPN DB, din rail with IP-43 protection with electrical accessories & front door locking arrangement with all connection , a)10+2 W SPN DB with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. -2 (one) no.b) 32A DP MCB (10kA, C curve)—1(one) noc) 32 A DP MCB Isolator—1(one) nod) 32 A, 240 V DP Contactor with Auxilary Contactor(1 NO-1 NC)- 1 (One) no.e) Daily & weekly programmable basis Astro time switch, ,6 yrs. Battery backup,key pad lock features- 1 (one) nof) LED Indicator Lamp-1 setg) Blank Plate as required.[ Legrand /Schneider/Seimens/ABB/ L &K ] |
| 52 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 53 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 54 | Supply of 2/4 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volte of following sizes [Make Polycab / RR /KEI/ Hazells/ Gloster as approved by E.I.C] |
| 55 | 2 Core 6 sqmm (For street light) |
| 56 | Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting |
| 57 | 2 Core 6 sqmm |
| 58 | Supplying and fixing compression type gland and finishing those for following XLPE / PVC armoured cable (2/ 4 / 3.5)Core as per GS. |
| 59 | 2 Core 6 sqmm |
| 60 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt) as required. |
| 61 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 62 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 63 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 64 | SITC of Fire Detection System |
| 65 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 66 | Two Loop Panel |
| 67 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 68 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required. |
| 69 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 70 | Supplying, installation, testing & commissioning of addressable manual call point complete as required |
| 71 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required |
| 72 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 73 | Supply of XLPE Insulated & unarmoured stranded Copper Conductor control cables h aving following numbers of core for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] |
| 74 | 2 Core 1.5 sqmm |
| 75 | Upon completion of the commissioning process, a comprehensive Single Line Diagram (SLD) and chart of the installed Fire Alarm System shall be submitted. The documentation shall indicate the block/room names, locations of detectors, Manual Call Points (MCPs), hooters/strobes, modules and associated cable/loop path lines. The SLD and chart shall represent the actual installed fire alarm system layout and configuration and shall be suitable for future maintenance, troubleshooting and upgradation. Soft copies as well as printed hard copies of the SLD and chart shall be submitted within three days from the date of commissioning. |
| 76 | less cost of dismantled and unservicable materials(.)Rs.10,000.00/- |
| 77 | Rate should be quoted incl. of all taxes and cess. |
| 78 | Defect Liability period : 1 year Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender