Tender For Internal Electrification Of Newly Constructed Building And Strengthening Of Street Light In Bus Terminal Sec-90 , Noida.
Tender Value
69.68 Lakhs
Estimated cost
Bid Submission
27 Oct 2026
8 days left
EMD
1.39 Lakhs
Bank guarantee accepted
Document Fee
2832
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ghaziabad → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Internal Electrification Of Newly Constructed Building And Strengthening Of Street Light In Bus Terminal Sec-90 , Noida.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring point for light with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in heavy guage PVC conduit pipe partly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete with 1.5 sq. mm FRLSH PVC Insulated multistrand single core copper conductor cable as earth wire drawn inside the conduit ,GP Box, piano type switch & ceiling rose/angle/batten holder on 3mm thick phenolic paminated backalite sheet etc complete in all respect as directed ncluding matching colour wash. . (as per PS No. 138C) |
| 2 | Wiring point for fan / fresh air fan (light duty exhaust fan) with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in heavy guage PVC conduit pipe partly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete with 1.5 sq. mm FRLSH PVC Insulated multistrand single core copper conductor cable as earth wire drawn inside the conduit ,GP Box, piano type switch & ceiling rose/angle/batten holder on 3mm thick phenolic paminated backalite sheet etc complete in all respect as directed including matching colour wash. (as per PS No. 140C) |
| 3 | Wiring point for plug with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in heavy guage PVC conduit pipe partly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete with 1.5 sq. mm FRLSH PVC Insulated multistrand single core copper conductor cable as earth wire drawn inside the conduit and piano type switch and socket etc., complete in all respect including matching colour wash.(as per PS No. 141C) |
| 4 | S/F of power plug with15A/240V Flush type switch and 5 pin 15A/250 Flush type universal socket in suitable MS box of 175mmx100mmx50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer as per PS No. 1139 |
| 5 | Wiring point for Exhaust fan with 1.5 sq. mm FRLSH PVC insulated multistrand single core copper conductoer cable in PVC conduit concealed in wall with 1.5 sq, mm FRLSH PVC insulated copper conducter cable as earth wire drawn in side the conduit. GP Box & 15 Amp piano type switch & ceiling rose on 3mm thick phenolic laminated backelite sheet etc. Complete in all respects as directed incl. colour wash PS No. 137(C) |
| 6 | S/W of submain with 2 Nos. 4 sq. mm FR PVC insulated 1100 Volt grade multistrand single core copper cunducter cable. In 20 mm dia heavy duty (2mm thick) PVC conduit with one no. 2.5 sq. mm FR PVC insulated multistrand copper conducter cable as earth contunity wire drawn in counuit. Complete in all respects as per PS No. 216C |
| 7 | S/W of submain with 2 Nos. 6 sq. mm FRLSH PVC insulated 1100 Volt grade multistrand single core copper cunducter cable. In 25 mm dia heavy duty (2mm thick) PVC conduit with one no. 4 sq. mm FRLSH PVC insulated multristrand copper conducter cable as earth contunity wire drawn in counuit. Complete in all respects as per PS No. 217C |
| 8 | S/W of submain with 2 Nos. 10 sq. mm FRLSH PVC insulated 1100 Volt grade multistrand single core copper cunducter cable. In 32 mm dia heavy duty (2mm thick) PVC conduit with one no. 3 sq. mm FRLSH PVC insulated multristrand copper conducter cable as earth contunity wire drawn in counuit. Complete in all respects as per PS No. 273C |
| 9 | S/F of SP MCB 6 Amp to 32 Amp C-curve type Havells make 10 KA complete in all respect PS No. 1002 (Cat-B) |
| 10 | S/F of 40 Amp DP MCB Havells make 10 KA complete in all respect PS No. 1010 (Cat-B) |
| 11 | S/F of 63 Amp FP Isolator Havells make complete in all respect PS No. 1007 (Cat-B) |
| 12 | S/F of 100 amp 415 Volt metal clad TPN HRC type switch fuse unit complete with HRC fuse on angle iron bracket complete in all respects PS No. 328 Cat B |
| 13 | S & F surface/Flush mounting 8ways TPN distribution board without additional Door without MCB complete in all respect, as directed at site by Engineer in charge. PS No. 1028 CAT-B |
| 14 | Supply and buring of safe earthing electrode T-19 (Hot dip galvanized), length up to 2000mm outer type 50mm, inner pipe, 25mm terminal dia 12mm, outer GI pipe of 16 SWG and inner GI pipe of 12 SWG with Hot Dip galvanization up to 100 micron filled with crystalline conductive mixture(CCM) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good micture of retaining capicity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25x3 G.I. strip will be extra as per PS No. 725A |
| 15 | Supply and fixing of LED Tube Light with batten suitable for upto 1x22 watt LED Tube Light fitting including tube on surface. Complete in all respects (PS No. 1413 CAT-AAA) |
| 16 | Supply and Fixing Ceiling fan 1200 mm dai ISI Marked MAke-Bajaj, Crompton,Havells or Equalent Make,(AOR) |
| 17 | Supply and fixing hexagonal/Round G.P.fan box of approved make made up of 1.0 mm thick ISI Marked G.P.sheet spot welded Four to Eight holes of 25.4 mm for pipe entry of the box. Holes should be semi-shuttered type with 0.5 mm G.P. Sheet made upper & lower cover duly screwed fitted with 300 mm round zink coted M.S Bar X 12 mm & brand name should be embossed. Fixing with wiring conduit laid in the R.C.C. roof before concreting alongwith supply of all material, labour, T&P etc. required for proper completion of the work. PS No. 1149 |
| 18 | Supply and fixing and concealing of 25 mm dia. 2mm thick PVC conduit pipe with ISI mark embossed and with PVC accessories confirming to IS No. 3419 for drawing wires duly sealed at joints with original resin / adhesive to make the complete piping rigid, plastering with cement sand mortar finished to the level with matching colour wash including cost of all material labour and T&P etc required for proper completion of the work as per directions and to the satisfaction of Engineer in charge.(as per UPPWD 2018 item No. 149A) |
| 19 | Supply of Totally enclosed 300 mm dia exhaust fan, continously rated highly efficient heavy-dutymotor with ressure die cast aluminium rotor mounted on two ball bearings, Aerodynamically contoured blades handle maximum air with minimum power consumption. Rigid frame with rubber mountings for silent peratins. Expoxy powder coating with specially pretreated components for better resistance to corrosion. Degree of protection against dust & water entry is IP55 as per direction of E/I. (AOR) |
| 20 | Supply and laying of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete inall respect (PS No. 716) |
| 21 | Supply and Fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 110 to 130 Watt. Confirming to IP 66 Protection complete in all respect.. Cat AAA PS 1424(Make -L.T,Havells,Bajaj,Crompton). |
| 22 | Supplying and Laying of 6 sq. mm 2 core PVC Insulated Al. moued cable for street Light pole (as per RESPO-2018) annexure -3 pg. 17. |
| 23 | Numbering of Pole with combination of yellow and black colour paint etc. complte in all respects as per direction of E/I. (AOR) |
| 24 | Supply and burring of Safe Earthing Electrode T-19, (Hot Dip Galvanized), Length up to 3000mm, outer Dia 50 mm inner Dia 25 mm, terminal Dia 12mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity and one earthing ead of 25mm x 3mm G.I. strip, upto switch board (from apron to switch board, the cost of G.I. strip will be extra) along with 30 cm square C.I. frame with hinged cover & masonry housing. Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. PS No. 725 (B) |
| 25 | Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. Clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respects. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. (KEI,Polycab, Havell's make) |
| 26 | 1) 16 Sq.mm. x 4 Core |
| 27 | 2) 50 Sq.mm. 3.5Core (PS No. 501) |
| 28 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge. as per PS No. 504 |
| 29 | 1- 16 Sq.mm. |
| 30 | 4- 50 Sq.mm. |
| 31 | S/Laying of 90 mm dia (OD 76 mm & ID 51 mm nominal) size of (DWC) HDPE Pipes ISI marked along wigh all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench pat excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/Time/CPE make. as per DSR 2018 item no. 14.16.2 page no. 52 |
| 32 | Supply and fixing of 15 Amp TPN capacity of automatic street light cubical control panel painted with anti corrosive alkali and acid proof paint crossing of time switch TSO 100 series with contractors, HRC fuse, isolating swtich metering instrument & instrument box with CTs etc. in case of TPN, Complete in all respects. as per PS No. 807D |
| 33 | Supply and fixing of electronic fan regulator 120-280 V. ISI marked, on the existing switch board including making connections, required material, labour T&P etc. for proper completion of work to the satisfaction of Engineer in charge of work.Make Ankor,Kinjal (PS No. 1203 A) |
| 34 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessedconduit as required. |
| 35 | 20 mm [DSR 1.21.1] |
| 36 | 25 mm [DSR 1.21.2] |
| 37 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections butexcluding modular plate etc. as required. |
| 38 | 5/6 A switch [DSR 1.24.1] |
| 39 | 15/16 A switch [DSR 1.24.3] |
| 40 | 3 pin 5/6 A socket outlet [DSR 1.24.4] |
| 41 | 6 pin 15/16 A socket outlet [DSR 1.24.5] |
| 42 | Supplying and fixing following size/ modules, GI box alongwithmodular base & cover plate for modular switches in recess etc.as required. |
| 43 | 3 Module (100mmX75mm) [DSR 1.27.2] |
| 44 | 4 Module (125mmX75mm) [DSR 1.27.3] |
| 45 | 6 Module (200mmX75mm) [DSR 1.27.4] |
| 46 | Supplying and fixing single pole blanking plate in the existingMCB DB complete etc. as required. [DSR 2.11] |
| 47 | MAIN ELECTIRCAL PANELSupplying, installation, testing & commissioning of cubical type wall mounted motor control Main panel suitable for 415V, 3 Phase, 4Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable capacity extensible type FP Aluminium Alloy bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MV A for I Sec. with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 1.5 sq.mm. PVC insulated FRLS copper conductor Single Core cable, cable alleys, cable gland plates in two half, i/c additional NO/NC contacts in all outgoing starters for automatic operation through BMS and providing, including cost of all control copper cable & fixing following switch gears:-Make- Application Control/Allied Engineers/NICPL |
| 48 | INCOMING :1 Nos 125 A MCCB and 1 No. 100A 4P 230 series ATS with inbuilt controller having AMF features with 1 No. - 100 Amps Four Pole, 25 KA (ICU=ICS), MCCB with microprocessor based release with o/c, s/c protection inbuilt E/F protection release all indication, front operating hand & door interlock with shunt trip relay |
| 49 | Digital Multifunctional meter of class 0.5 or better accuracy to record demand (KVA), energy (KWH),Total power factor, current (in each phase and the neutral), voltage (between phases and between each phase and neutral), comprises of suitable communication port for connection to IBMS.s per IEC61557-12. |
| 50 | 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, |
| 51 | Bus Bar:TPN aluminium bus bars of minimum of 200 A, 25 kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. |
| 52 | Outgoings Digital Multifunctional meter of class 0.5 or better accuracy to record demand (KVA), energy (KWH),Total power factor, current (in each phase and the neutral), voltage (between phases and between each phase and neutral) for shops -09 Nos (Following All MCB's (Ics=Icu upto 433 V) thermal magnetic release with over current and short circuit releases, all indication, front operating handle & door interlock ) & Each MCB to be provided with ON indiation with 2A backup SP MCB) |
| 53 | 63A, 4P MCB with 25KA breaking capacity - 3 No. |
| 54 | 40A, 2P MCCB with 25KA breaking capacity - 7 Nos. |
| 55 | 63A, 2P MCCB with 25KA breaking capacity - 2 Nos. |
| 56 | Digital flush type class-1.0 accuracy Multifunction meter with suitable rating of cast resin CT's, 10VA, Class 1.0 as per SLD complete required with each outgoing feeder for shops.MAIN PANEL Described as above. |
| 57 | Demolishing cement concrete manually/ by mechanical means including disposal of material with in 50 Mtr. Lead as per direction of E/I. Nominal concrete 1:3:6 or richer mix(i/c equivalent design mix) (AOR) |
| 58 | Filling available excavated earth( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth consolidating each deposited layer by ramming & watering, lead upto 50 m and lift upto 1.5 m. (AOR). P- |
| 59 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required (AOR) |
| 60 | a) Bituminous Portion (AOR) (2265.0+18% gst) |
| 61 | b) Water Bound Macadam (AOR) (1400.0+18% gst) |
| 62 | Earth work in Excavation in by mechanical means (Hydraulic excavator) manual means over areas excaading 30 mtr in depth,1.50 mtr width as well as 10sqm on plan)including out and desposal of excavated earth ,load upto 50m and lift upto 1.5 m as directed by the Engineer incharge (AOR). |
| 63 | Supply and fixing of Factory wired integral LED Flood Light Luminaires with die cast Aluminium housing build with driver set suitable for 170 to 200 watt. Confirming to IP66 and above protection. Complete in all respects. (PS No. 1455) CAT-AAA . (Make - Philips/Bajaj /Crompton/Havells/Neri/LT) |
| 64 | Supply,Installation,testing and commissioning of 1.5 Tr. Hiwall split type cooled A.C. Unit suitable for 15mtr to 20mtr length of piping,consisting out door unit,indoor unit as detailed complete with standard factory supplied power and control cable,interconnecting copper refrigent piping insulated with insulationtubingas required as direction of E/I.AOR Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 14, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 27, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysOct 28, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender