Tender For B.O.Q For Repair/ Renovation Of Four Storied Fire Complex Of F&Es Command Sopore (Part-A) B.W.O Electric Work
Tender Value
8.30 Lakhs
Estimated cost
Bid Submission
02 Nov 2026
17 days left
EMD
16616
Bank guarantee accepted
Document Fee
600
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Baramulla → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for B.O.Q For Repair/ Renovation Of Four Storied Fire Complex Of F&Es Command Sopore (Part-A) B.W.O Electric Work
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for Light point/Fan point/Exhaust fan/Bell point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable, (Havells Lifeguard/Anchor fireguard/Polycab Green/Eq Make) in surface/recessed Conduits laid in slabs (Including Cost of Conduit 25mm) with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified/Schneider Zencelo/ Havells Crab tree/ Legrand Arteor/Anchor roma plus/ABB Tvisha/Eq.Make & items shall be approved before execution of work by SDO. |
| 2 | Supply and fixing of 6 amp/250 V A.C fan dimmer step type 2 module with cover plate ( Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified/Schneider Zencelo/ Havells Crab tree/ Legrand Arteor/Anchor roma plus/ABB Tvisha/Eq.Make) |
| 3 | Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells Lifeguard/Anchor fireguard/Polycab Green/Eq Make) |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required, ISO/IEC Certified of Schneider Zencelo/ Havells Crab tree/ Legrand Arteor/Anchor roma plus/ABB Tvisha/Eq.Make & shall be approved before execution of work by SDO. |
| 5 | Wiring for 6Amp Plug(Computer Point) with (P+N+E) 3 x 2.5 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells Lifeguard/Anchor fireguard/Polycab Green/Eq Make) |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including proving and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings), ISO/IEC Certified ofSchneider Zencelo/ Havells Crab tree/ Legrand Arteor/Anchor roma plus/ABB Tvisha/Eq.Make & shall be approved before execution of work. |
| 7 | Wiring for Sub main Wiring along with earth Wire with the following Sizes of FRLS-H PVC insulated copper conductor, single core Cable in surface/Recessed medium class PVC conduit (Havells Lifeguard/Anchor fireguard/Polycab Green/Eq Make) & shall be approved before execution of work (Including Cost of Conduit/Channel) |
| 8 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 9 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 10 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 11 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 12 | Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/Havells/ABB/Eq. Make) |
| 13 | Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/Havells/ABB/Eq Make) |
| 14 | 63 Amp. |
| 15 | 40 Amp. |
| 16 | 32 Amp. |
| 17 | Supplying and Fixing of MCB way 6-way (4 + 18), horizontal typed , sheet steel, Double Door Distribution Board, TPN 240V/415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ Schneider/ABB/Eq Make) |
| 18 | Supplying and Fixing of MCB way 6-way horizontal typed , sheet steel, Double Door Distribution Board, SPN 240V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ Schneider/ABB/Eq Make) |
| 19 | Supply/Installation/Testing and Commissioning of 15W + LED Conceal/Surface (Commerical Type) light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of Philips/Havell's/Wipro/Halonix/Eq Make. |
| 20 | Providing & Fixing of IK08 IP-66 protected high power LED 50 Watt flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 Im/wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K 355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR:-High Power LED Flood Light Minimum lumen output 6200 Im of Havells/Crompton/Philips Make as approved and to be installed on outside block including S/F of suitable size of Gyser bolt.The job further includes replacement warranty of fixture (if damaged/burnt out what so ever reason) for a period of two years reckoned from date of successful commissioning /handing over of site to intending department. |
| 21 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, ceiling fan with 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Havells/Polycab/ Eq Make |
| 22 | Supply/Installation/Testing and Commissioning of 225-250mm Shutter Typed,320 Cu.m/Hr.AC 220-240 Volts, 50 Hz Exhaust fan made out of ABS Plastic Material with inbuilt thermo cut-off Protection and Noise Level not exceeding 37dB of Following Sizes including connection etc USHA/Havells/Crompton/Eq. Make.(Min 1-Star) |
| 23 | Supply/Laying/Connecting and Commissioning of 70 sq.mm 3.5-Core XLPE/PVC insulated and steel armored 1.1 KV grade Aluminum Cable of Havells/Polycab/Eq. Make with required size of thimbles dully crimped with hydraulic crimping tool including Providing/Fixing of saddles/clips with making of connection and partially to be laid underground through DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refilling the Trench .(Material to be approved before execution) |
| 24 | Supply/Installation/Testing and Commissioning of CPRI Approved (IS/IEC:61439) Main Controlling Panel,fabricated out of heavy gauge sheet steel ,dully Painted with powder coated paint ,dust protected ,earth terminal fitted on epoxy cleats, volt meter & Ammeters with selector switch & CT Coil of required ratio with all necessary connections & inner wiring of panel on both heating and lighting circuits. The switches are connected with bus bars inside panel & manufacturer CPRI Certified.The switch are adjustable type made of Havells/ L&T/ABB/Legrand/Siemens Make and change over switch should be of Havells/ L&T/Legrand/ Schneider Make.(1) Normal Incomer:a) 160 Amp-4-Pole ,35kA C-CURVE MCCB with extended terminals Havells/L&T/Legrand/Schneider Make as approved=01 No. b) 300 Amps TPN Al. Bus Bar Set = 01 Set,Digital Voltmeter ,Ammeter ,C.T Coils with Selector Switch & Phase indicator Set.Outgoing:(1) Normal outgoing for Heating/AC/Lighting/Inverter etc load(a) 63-Amp DP MCB = 04 No. for Heating Sub-main.(b) 40-Amp DP MCB= 04No. for Lighting/Machine Sub-main(c) 32-Amp DP MCB = 04 No. for inverter Sub-main |
| 25 | ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER Rod EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value .Supplying, Installation and Testing of 75 mm copper Pipe Filled with Crystallineconductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 2OMM Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through DWC High Density Poly ethylene Pipe having Corrugation complete job |
| 26 | Supply and fixing of PVC ceiling rose (2/3 pin), ISI marked, suitable for connection of light/fan point, complete with necessary accessories, including connections and testing as required of Havells/Anchor/Legrand/Eq.make |
| 27 | Supply and fixing of Hylum sheet (phenolic laminated sheet), 3 mm / 6 mm / 10 mm thick (as specified), duly cut to required size and shape, fixed with necessary nuts, bolts, screws, washers, spacers etc., including finishing and making good the surface, complete as required Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 13, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysNov 03, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender