Tender For Repair/Replacement And Maintenance Of Fire Fighting Equipments Including Fire Alarm At Hospital Bldg Under Age (I) Asvini, Colaba, Mumbai
Tender Value
35 Lakhs
Estimated cost
Bid Submission
02 Nov 2026
15 days left
EMD
70000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mumbai → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Replacement And Maintenance Of Fire Fighting Equipments Including Fire Alarm At Hospital Bldg Under Age (I) Asvini, Colaba, Mumbai
BOQ
| Sl. No. | Item Description |
| 1 | Part IComprehensive monthly maintenance of automatic fire alarm system and fire suppression system, installed at Hospital bldg, Fire Station & Guard Room including attendIing day-to-day complaints, complete all as specified and direscted by the Engineer-in-Charge. i) The scope of work shall include comprehensive maintenance of all equipment forming part of the fire detection and fire suppression systems installed in the above locations. The maintenance shall include attending day-to-day complaints related to false alarms, system faults, trouble signals and similar issues on an emergency basis, ensuring prompt response and restoration of the system to normal working condition.(ii) The work shall also include cleaning, inspection, checking and rectification/repair of defencts such as faulty detectors, wiring problems, power supply failures, nuisance alarms and other operational issues, as required for all equipment of the fire detection and fire suppression systems. iii) Operational testing of all equipment of the fire detection system, including control panels and field devices, shall be carried out periodically and as required, in the presence of the User's Representative and the Engineer-in-Charge to verify satisfactory performance. iv) Emergency visits shall be carried out whenever called, in addition to routine monthly maintenance, in the event of any systems failure due to any cause, without any additional cost to the department. v) Materials required for replacement of defective components shall be measured and paid for separately under the respective items of this Schedule as SUPPLY ONLY. Note- Comprehensive monthly maintenance of the fire alarm detection systems shall be carried out in accordance with the maintenance schedule specified in Annexure -I (Page 102&103), and detailed maintenance and test reports shall be submitted to the Engineer-in-Charge within the stipulated time, which shall be manditorily required before payment of RARs. |
| 2 | RF translator wireless device |
| 3 | RF expander wireless device |
| 4 | Optical thermal detector (heat & smoke) |
| 5 | Manual call point wireless device |
| 6 | Analogue addressable dual rellay controller |
| 7 | Transmitter-receiver type beam detecter of 5-100m range |
| 8 | Analogue addressable multi-sensor |
| 9 | Analogue addressable manual call point |
| 10 | Analogue addressable single monitor input module |
| 11 | Respones indicator for detector on false ceilling |
| 12 | Addressable loop powered wall sounder beacon |
| 13 | Addressable loop powered base sounder beacon |
| 14 | 2 core x 1.5 sq mm. multistrand copper cable, |
| 15 | 4 core x 1.5 sq mm. multistrand copper cable |
| 16 | Note for above items Sr No 1 :-(a) Technician in requisite number shall be there during Comprehensive maintance for all fire alarm system of Hospital as mentioned above.(b) Technician should also have diploma certfication & practical experience and shall passes through knowledge to defect rectify and maint of fire alarm system. |
| 17 | Part IISupply,install & test in replacement of batteries of capacity 12 V 7 AH dry type complete all as specified and as directed by Engineer-in-Charge. |
| 18 | Supply, install, test & commissioning in replacement of manual call point wireless device operating at frequency range of 865-867 MHz, operating frequency channels 7, communication range with the translator or expander 150m in open space all as specified and directed by Engineer-in-Charge. |
| 19 | Supply install test & commissioning in replacement of analogue addressable type multi-sensor detector with heat and smoke combination which is fully compatible with analogue addressable protocol having removable high performance chamber with twin fire LED's allow 360 degree viewing, user selectable modes 1% to 4.5% obs/ft, incorporate optical and dual heat elements lock mechanism (sensor to base), electrically addressed, approved by LPCB & Vds, all as specified and directed by Engineer-in-Charge. |
| 20 | Supply, install, test & commissioning in replacment of analogue addressable manual call point resettable type with integral short circuit isolator, analogue addressable protocol having status LED for alarming & Standby mode, electronically addressed, approved by LPCB all as specified by Engineer-in-Charge. |
| 21 | Supply, install, test & commissioning in replacement of remote respones indicator fire detector on false ceilling all as specified and directed by Engineer-in-Charge. |
| 22 | Supply, install, test & commissioning in replacement of addressable loop powered wall sounder beacon, variable sound output 90~102 dB(A) (±2 db (A)) output at 1 metre,high intensity LED technology, 51 user-selectable tones (all tones EN54-3 compatible), all as specified by Engineer-in-Charge. |
| 23 | Supply, install, test & commissioning in replacement of addressable fire alarm chip card or XPERT card involves setting a unique binary number on the devices base so that central panel can idenitfy its exact location Complete all as specified and directed by Engineer-in-Charge. |
| 24 | Supply and laying in replacement of two core 1.5 Sq.mm, Multistranded, twisted Copper cable, FRLS Armoured cable laid through existing conduit / fixed to wall / ceiling / loop using proper clamps / clips complete all as specified and as directed by Engineer-in-Charge. |
| 25 | Supply and fix in replacement PVC conduit heavy duty, 25mm dia size, for passing cable including saddle clips, and all connected accessories complete all as specified and directed by Engineer-in-Charge. |
| 26 | Supply ,install,test & commissioning in replacement of active repeater panel to be integrated with fire alaram control panel, largr touch screen LCD disply the status of any fire/fault of integrated fire alarm panels, all as specified and directed and directed by Engineer-in-Charge . Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 13, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 02, 2026
17:00 IST