Tender For Repairs / Replacement Of Lt Poles, Acsr Conductor, Mcb And Cables, Street Lights, Security Lights And Misc E/M Works At Chh Sambhajinagar Mil Station Under Ge (S) Ahilyanagar
Tender Value
36 Lakhs
Estimated cost
Bid Submission
02 Nov 2026
5 days left
EMD
72000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Aurangabad → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repairs / Replacement Of Lt Poles, Acsr Conductor, Mcb And Cables, Street Lights, Security Lights And Misc E/M Works At Chh Sambhajinagar Mil Station Under Ge (S) Ahilyanagar
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches by manual/ mechanical means (Hydraulic excavator) not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of pipe, foundation etc. or for Shafts, wells, cesspits, manholes, pier holes, etc not exceeding 10 Sq m on plan, including dresssing of sides and ramming of bottoms, lift upto 1.5 m, including getting out any type of soil (soft/hard/dense soil) and disposal of surplus excavated soil to a distance not exceeding 50 m complete all as specified and as directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming of soil in layers not exceeding 25 cm thick complete all as specified and directed by Engr in Charge. |
| 3 | Supply & laying DWC HDPE Cable duct pipe of size 50 mm bore confirming to IS :16205 Part 24 Type 450N for laying of LT cables etc complete with all accessories laid in trenches suitable for cable protection complete all as specified and directed. |
| 4 | Supply & laying DWC HDPE Cable duct pipe of size 63 mm bore confirming to IS :16205 Part 24 Type 450N for laying of LT cables etc complete with all accessories laid in trenches suitable for cable protection complete all as specified and directed. |
| 5 | Supply & laying DWC HDPE Cable duct pipe of size 120 mm bore confirming to IS :16205 Part 24 Type 450N for laying of LT cables etc complete with all accessories laid in trenches suitable for cable protection complete all as specified and directed. |
| 6 | Supply, Laying and testing in replacement LT UG cable of size 120 sqmm 3.5 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 7 | Supply, Laying and testing in replacement LT UG cable of size 95 sqmm 3.5 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 8 | Supply, Laying and testing in replacement LT UG cable of size 70 sqmm 3.5 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 9 | Supply, Laying and testing in replacement LT UG cable of size 50 sqmm 3.5 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 10 | Supply, Laying and testing in replacement LT UG cable of size 35 sqmm 3.5 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 11 | Supply, Laying and testing in replacement LT UG cable of size 25 sqmm 3.5 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 12 | Supply, Laying and testing in replacement LT UG cable of size 16 sqmm 4 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 13 | Supply, Laying and testing in replacement LT UG cable of size 10 sqmm 4 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 14 | Supply, Laying and testing in replacement LT UG cable of size 10 sqmm 2 core, XLPE insulated, PVC Sheathed ,ISI marked ,earthed system , armoured heavy duty ,electric cable with aluminium conductor,1100 Volts grade in trenches/wall/floor/pole complete and making connection including suitable size aluminium lugs all as specified and directed by Engineer in charge including dismantling and taking out of existing cable and covers complete all as specified and directed.Note : Excavation and earth work shall be measured and paid separately. |
| 15 | S & F in replacement Straight through cable jointing kit, heat shrinkable for 1.1 KV grade XLPE cable of size 10 to 16 sqmm 4 core with jointing material and accessories and testing after jointing complete all as specified and directed. |
| 16 | S & F in replacement Straight through cable jointing kit, heat shrinkable for 1.1 KV grade XLPE cable of size 25 to 50 sqmm 3.5 core with jointing material and accessories and testing after jointing complete all as specified and directed. |
| 17 | S & F in replacement Straight through cable jointing kit, heat shrinkable for 1.1 KV grade XLPE cable of size 70 to 120 sqmm 3.5 core with jointing material and accessories and testing after jointing complete all as specified and directed. |
| 18 | S&F in replacement galvanised iron, 80 mm bore tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including taking out old unserviceable pipe complete all as specified and directed. |
| 19 | S&F in replacement galvanised iron, 50 mm bore tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including taking out old unserviceable pipe complete all as specified and directed. |
| 20 | S&F in replacement galvanised iron 40 mm bore tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including taking out old unserviceable pipe complete all as specified and directed. |
| 21 | M&L for cutting existing road/hard standing surfaces to a depth 60 cm and 50 cm width and getting out for laying underground pipe including returning filling in, watering well ramming in layers not exceeding 25cm in soil and filling the trench top with 15cm thick PCC 1:2:4, type B1 (using 20 mm graded stone aggregate) and making good the disturbed surface complete all as specified and as directed. |
| 22 | Dismantling of ACSR or AAC conductors/Guard wire of any size and any description from any heights/ poles or any location, complete all as specified and as directed. |
| 23 | Dismantling of Unserviceable LT insulators Pin/ shackle/ Disc & loop type from existing OH lines complete all as specified and directed by Engr in Charge. |
| 24 | Dismantling and taking down cross-arms of M.S. channel or angle sections with nuts, bolts ,washers etc complete all as specified and directd. |
| 25 | Dismantling of GI wire cradles,earth wire guarding , fabricated with galvanised steel wire 4mm dia hexagonal / rectangular shape of any type complete all as specified and as directed . |
| 26 | Dismantling of LT stay Assembly all as specified and directed. |
| 27 | Supply and fixing in replacement Cable route indicator made out cast iron and embossed HT Cable on the plate of size 80 mm dia 5 mm thick with angle iron legs of 0.9 metre and grouting legs in PCC 1:3:6 foundation of suitable size complete all as directed and directed by Engr in Charge. |
| 28 | M&L for taking out old burnt cables & thimbles from loop and fixing to LT Panel completely after making good condition with suitable lugs upto cable 16 to 120 sqmm fixing to MCCB's including necessary excavation work & minor spare parts i.e thimbles, nut, bolts ,para tape etc complete all as specified and directed. |
| 29 | M&L for denting, welding/fixing of hinge to panel door of various capacity including painting of doors after welding, with Smoke grey paint & cleaning of exposed surface with brush, empry paper complete all as specified and directed by Engineer-in-Charge |
| 30 | M&L for preparation of surfaces of LT pole by scrapping old damaged paint of poles including cross arms, channels, clamps, etc and painting with two coats of silver aluminium paint over a coat of primer and making 30cm wide strips (total 5 Nos) with yellow and black paint alternately on external surface above PCC coping upto 1.5 meter height and writing pole No with white letters on black background complete all as specified and as directed. |
| 31 | Trimming of tree branches touching to the LT/HT over head line or near to the LT/HT over head line as per the direction of AGE E/M/JE incharge complete including removing the tree branches from site complete all as specified and directed.Note : (i) Written shut down shall be obtained from concerned JE/AGE (E/M) before taking the trimming work in hand by contractor. (ii) Span from one pole to next pole (30 to 50 RM) will be considered as a one Job (iii) Any damage caused due to negligence of workmen will be rectified without any extra payment (iv) T & P such as ladder, rope, cutter, Axes and other related material will be provided by the contractor. |
| 32 | Cleaning of bushes /small plants up to root level aruound and surrounding area E/M installations (i.e two pole / four pole structures,out door substation yards & misc E/M installations etc including surface dressing n.exc 15 cm deep and removing debris to distance n.exc 50m complete all as specified and directed by Engr-in-charge. |
| 33 | S&F in replacement 1100 Volt grade, heavy duty cable PVC insulated aluminium solid conductor served with inner sheathing of PVC tape and over all PVC sheathed in service connection with twin core cable flat with multistranded aluminium conductor of size 4 Sqmm suspended by insulating hangers not more than 1 mtr apart including 4 mm suspension wire one complete all as specified and as directed. |
| 34 | S&F in replacement 1100 Volt grade, heavy duty cable PVC insulated aluminium solid conductor served with inner sheathing of PVC tape and over all PVC sheathed in service connection with twin core cable flat with multistranded aluminium conductor of size 6 Sqmm suspended by insulating hangers not more than 1 mtr apart including 4 mm suspension wire one complete all as specified and as directed. |
| 35 | Supply and fixing Danger notice Plate of 1.6 mm thick mild steel sheet , vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps, bolts and nuts of approved size, for LT 20 x15 cm size and directed by Engr in Charge. |
| 36 | S&F in replacement FRP Junction box, light weight low corrosive suitable for pole mounting including MCB SP 6/10 amps , Box size not less than 250x200x100 mm including necessary connection for loop in and loop out cable connector and suitable size for cable glands complete all as specified and directed by Engr in Charge. |
| 37 | S & F in replacement PVC insulated and over all PVC sheathed, stranded copper conductor wire 1.5 sqmm x 3 core ISI marked complete from light fitting to pole junction box complete all as specified. |
| 38 | S&F in replacement Voltmeter three phase class 0.5 with digital display including taking down old UNSV Voltmeter complete all as specified and directed by Engr in Charge. |
| 39 | S&F in replacement ammeter three phase class 0.5 with digital display including taking down old UNSV ammeter complete all as specified and directed by Engr in Charge. |
| 40 | S&F in replacement LED type indicator lamp (RYB) including taking down old UNSV indicator lamp set of three complete all as specified and directed by Engr in Charge. |
| 41 | S&F in rep, MCCB 4 Pole , 63 Amps , 16 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge. |
| 42 | S&F in replacement , MCCB 4 Pole , 100 Amps , 16 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge. |
| 43 | S&F in replacement, MCCB 4 Pole , 125 Amps , 16 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge. |
| 44 | S&F in replacement , MCCB 4 Pole , 160 Amps , 36 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge. |
| 45 | S&F in replacement , MCCB 4 Pole , 200 Amps , 36 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge. |
| 46 | S&F in replacement , MCCB 4 Pole , 250 Amps , 36 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge. |
| 47 | S&F in replacement , MCCB 4 Pole , 400 Amps , 36 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge. |
| 48 | S&F in replacement LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete including PVC copper wire 1.5 sqmm of suitable length for connection of street light from Overhead conductor /junction box complete all as specified and directed by Engr in Charge.Make : Make : Havells Cat No ENDURASUNDOWNNXTSL60WLEDCWPASYBOPC or equivalent of makes specified. |
| 49 | S&F in replacement bracket for street light,made out of GI Pipe medium grade of suitable size (40 mm dia and 1.2 mtr long) bent to shape ,fixed with and including necessary heavy duty clamps of suitable size including painting the clamps with two coats of synthetic enamel paint over a coat of primer all as specified and as directed. |
| 50 | Supply and errection of steel tubular swaged poles complete with cast iron base plate , finial tapper plug , bolts,nuts & screws as specified type 410 SP - 31, 9.00 Mtr long including one coat of red-oxide zinc chrome primer and two coats of aluminium paint on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with yellow and black paint alternately on external surface above PCC benching and painting with bituminous paint internally and externally for portion embedded in PCC, including writing the pole number in white letters on black back ground, including dismantling of old unserviceable pole complete all as specified and directed. Note :- Excavation & earthwork and PCC in foundation of poles,coping etc shall be measured and paid under respective items |
| 51 | M&L for PCC 1:4:8 Type D2 using 40mm graded aggregate for base foundation complete all as specified and directed by Engr in Charge. |
| 52 | M&L for PCC (1:3:6) type C-1 with 20 mm gradded stone aggregate for coping of poles Pedestal including necessary form work complete all as specified and directed by Engr in Charge. |
| 53 | M&L for stay assembly comprising of 16 mm dia stay rod, 1800 mm long, loop type insulator of size 65 mm x 90 mm, galvanised stay plate 6 mm thick of size 250 x 250 mm and stay bow & dismantling of old Stay assembly complete all as specified and directed & as shown in Electrical Plate No. 1 of SSR Pt I complete all as specified and as directed. Note : Excavation/earth work PCC shall be measured and paid seperately. |
| 54 | M&L for servicing of LT Three Phase Sequencer, automatic and manual control of power supply source in correct suquence (RYB), panel board indoor type complete all as specified and directed.Notes :- (i) Spares required shall be measured and paid separately under respective items as supply only.(ii) Cost of fixing of spares is deemed to be included in this item. |
| 55 | Supply only Power Contactor MNX 185 Amps 3 Pole ,AC3 type all as specified and directed. |
| 56 | Supply only Termination Block 200 Amp all as specified and directed. |
| 57 | Supply only Three Phase Sequence sensing relay all as specified and directed. |
| 58 | Supply install in replacement and testing out door wheather proof bus bar chamber of size 100 cm x 60cm x 30cm made out of 3.15mm CRCA MS sheet having one side openable hinged door shuter with looking arangement/provn of two nos 80cm long 40x40x6mm anlge iron legs welded and 04 nos Aluminium bus bar of 200 Amp rating provn of one MCCB TPN 100 Amp 25 KA for controlling Electric supply complete erracted on ground with necessary PCC 1:3:6 type C2 foundation complete bus bar chamber painted with two coats of approved enamel paints over one coat of primer including making cable connection with necessary gland, lugs/thimbles all as specified. |
| 59 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated Aluminium bus bars 600 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes : The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL |
| 60 | in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m from GL to the bottom of panel board )Location : Near P4 P.E & P9 R.EIncoming:-(a) MCCB 250 Amp 4 pole 35/36 KA with overload & thermal release setting - 01 No(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 60cm long mounted on insulators for outgoing supply -01 Set.(RYB) (c) Neon LED indicator lamp - 01 Set (03 Nos)(d) Multifunction Digital square type intelligent panel meter to measure voltage, current, frequency & Power factor - 01 No Outgoing:- (a) MCCB 100 Amp 4 pole 25 KA with overload & adjustable thermal release setting - 03 Nos(b) Astronomical time switch 1P Module, 24 hours program, Programmable every 15 min., backup of 100 hours, current capacity 16A, with 1 changeover (1 CO) complete with all accessories - 01 Nos |
| 61 | Material & labour for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6.0mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and connections by using Galvanised Iron strip of 32 x 6 mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2020(Part-I) complete all as specified and directed. |
| 62 | S&F in replacement LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete including PVC copper wire 1.5 sqmm of suitable length for connection of street light from Overhead conductor /junction box complete all as specified and directed by Engr in Charge.Make : Havells Cat No ENDURASUNDOWNNXTSL70WLEDCWPASYBOPC or equivalent of makes specified. |
| 63 | S&F in replacement LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete including PVC copper wire 1.5 sqmm of suitable length for connection of street light from Overhead conductor /junction box complete all as specified and directed by Engr in Charge.Make : Havells Cat No ENDURASUNDOWNNXTSL90WLEDCWPASYBOPC or equivalent of makes specified. |
| 64 | S&F in replacement LED street light fitting 120 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete including PVC copper wire 1.5 sqmm of suitable length for connection of street light from Overhead conductor /junction box complete all as specified and directed by Engr in Charge.Make : Havells Cat No ENDURASUNDOWNNXTSL120WLEDCWPASYBOPC or equivalent of makes specified. |
| 65 | S&F in replacement LED flood light fitting 70 Watts, having pressure die cast housing with IP 65 efficient high outout emitter LED for better distribution, protection with heat resistant toughned glass with individual LED lenses complete including making connection with flood light box or OH line using PVC insulated and sheathed single core multi stranded alumn conductor cable of size 1.5 sq mm including MS clamps nuts, bolts and washers of required size complete all as specified and directed by Engr in Charge.Make : Havells Cat No. JETAADORNFLS70WLED757SSYMTOTGV2 |
| 66 | S&F in replacement LED flood light fitting 100 Watts, having pressure die cast housing with IP 65 efficient high outout emitter LED for better distribution, protection with heat resistant toughned glass with individual LED lenses complete including making connection with flood light box or OH line using PVC insulated and sheathed single core multi stranded alumn conductor cable of size 1.5 sq mm including MS clamps nuts, bolts and washers of required size complete all as specified and directed by Engr in Charge.Make : Havells Cat No. JETALEGANZAFLS100WLED757P60DTOTG |
| 67 | S&F in replacement LED flood light fitting 120 Watts, having pressure die cast housing with IP 65 efficient high outout emitter LED for better distribution, protection with heat resistant toughned glass with individual LED lenses complete including making connection with flood light box or OH line using PVC insulated and sheathed single core multi stranded alumn conductor cable of size 1.5 sq mm including MS clamps nuts, bolts and washers of required size complete all as specified and directed by Engr in Charge.Make : Havells Cat No. JETAADORNNXTFLS120WLED757SSYMTOTGV2 |
| 68 | Taking down old unserviceable street light fittings from street light poles of any type/ gun shed for repairs and refixing the same in existing position after repair and testing complete all as directed. Note- Parts/ Items as required for repairs and replacement shall be measured and paid for separately under respective items . |
| 69 | S&F in replacement Driver for LED Street Light 20 Watt to 50 Watt complete all as specified and directed.Make : Havells/Crompton Greaves/Bajaj/ Luker/ Surya |
| 70 | S&F in replacement Driver for LED Street Light 50 Watt to 160 Watt complete all as specified and directed. Make : Havells/Crompton Greaves/Bajaj/ Luker/ Surya. |
| 71 | Supply and fix in replacement post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete including suitable size of GI Pipe as per lamp size including connection and testing complete all as specified and directed .Make : Havells cat No CORALPT25WLED757PSYMTOPC or equivalent of makes specified. |
| 72 | S&F in replacement, Analog street light timer switch, 3P Module , 24 hours programme, programmable every 15 min , backup of 100 hrs , current capacity 16 A with (with battery back up) electronic type with digital display suitable for Indian region longitude/ latitude including suitable size of contactor with 1 changeover complete with all accessories and prewired suitable for a panel / pole mouting box complete all as specified and as directed. |
| 73 | Taking down High mast light of any length for repairs or carried out general maintenance including greasing, oiling to electric motor/steel wire rope etc and replacement / tightining of nuts & bolts , including all other repair as per site requirement etc including refixing in its original position and testing on completion complete all as specified & directed.Note : Greasing/Oiling/Nut bolts & all other minor parts shall deemed to be included in the unit rate quoted against the item. |
| 74 | Disconnecting electric connection, taking out and transporting to workshop old unserviceable motor from High Mast light of capacity 2/3 HP for repair/replacement, opening up the motor and rewinding with suitable gauge of super enamelled copper wire of 'F' class insulation , warnishing heating & replacement of worn out parts such as motor bearings, fan blade, reassembling after painting by preparing the surface, scrapping the old painting and removing the grease, oil, dirt etc, filling the cavities, spray painting with two coats of super enameled anti corrosive paint of approved colour, over a coat of primer transporting the repaired motor back to the original location, reinstalling, testing & commissioning complete all as specified & directed by Engr in Charge. Note :- Any nut/bolts/ studs and packing required shall deemed to be included in the rates quoted by the contractor. |
| 75 | S&F Winch Handle of suitable dia & Size for opearating High Mast light up & down complete all as specified & directed. |
| 76 | S&F in replacement of steel wire rope of 6 mm dia 7/19 gauge including greasing ,oiling tightining of nuts & bolts etc for High mast light of any length complete all as specified and directed by Engr in Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 12, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysNov 04, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender