Defence Statutory Bodies & Commissions/Committees Closing in 6 days TDR #57968182

Tender For Special Repairs / Replacement Of Lt Panels / Feeder Pillar Box And Connected Lt Cables Of Certain Md Accn Area At Darjipura At Af Stn Vadodara.

Issued by Statutory Bodies & Commissions/Committees · Vadodara, Gujarat
Tender Value
43.74 Lakhs
Estimated cost
Bid Submission
31 Oct 2026
6 days left
EMD
87500
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Vadodara → Gujarat
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Special Repairs / Replacement Of Lt Panels / Feeder Pillar Box And Connected Lt Cables Of Certain Md Accn Area At Darjipura At Af Stn Vadodara.

BOQ

Name of Work:- SPECIAL REPAIRS / REPLACEMENT OF LT PANELS / FEEDER PILLAR BOX AND CONNECTED LT CABLES OF CERTAIN MD ACCN AREA AT DARJIPURA AT AF STN VADODARA.
Sl. No. Item Description
1Supply, install, commissioning and testing factory made, CPRI approved, confirming to IS 5039, LT panel board out door type, size not less then 1500 mm W x 1500 mm H x 500 mm D, platform mounted suitable for 415 volt, 3 phases, 4 wire, 50 Hz AC supply system, bus bar chamber, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA sheet outer & inner and individual compartment for MCCB / volt/ Amps meter and 50 x 50 x 6 mm thick angle iron for base frame work having angle iron 4 Nos suitable long welded to frame / cubical and grouted in ground up to 0.5 Meter by using PCC 1:2:4 B2 of Suitable size, bottom of panel shall be 600 mm above from ground level, 2 Nos earth terminal to be welded with LT Panel. The complete Panel should be anti corrosive coating and finally epoxy polyester powder coating of flint grey shade (RAL-7032) including internal wiring with PVC insulated multistranded copper conductor FRLS cables appropriate size but not less than 2.5 Sqmm. Front and back opening type for cable entry with double door shutter including locking arrangement latch type as per manufacturers with 2 Keys reconnecting all existing UG cable with suitable lugs for incoming / outgoing feeders, and ferrule and comprising of following accessories all as specified ( Location P- 106, P- 229, P- 241, P- 150, P 148, P- 137,P- 206)
2Incomer
3(a) MCCB FP 200 A 36 kA with Electronic microprocessor release with over load Zone of adjustment 0.4 to 1.0 In and Electronic release with Short circuit Zone of adjustment 1.5 to 10.0 Ir. (Adjusted current) with time with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -01 No
4(b) 4 Nos Aluminium Bus bars of 400 Amp current rating capacity, of suitable size of length as actually required at site for 3 phase and neutral, mounted on epoxy / FRP bus bar insulator complete with nut bolt fixing arrangement complete - 01 set
5Outgoing :-
6(c) MCCB FP 100 A 16 kA with Adjustable Thermal release for over load 0.7 to 1.0 and Adjustable magnetic release (10.0 In) for Short circuit with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -04 Nos
7(d) MCB TPN 32 Amps - 02 Nos
8Metering Compartment
9(f) Digital type Amp meter 0-200 Amp(size 96mmx96mm) with Selector switch and 3 Nos CT of ratio 200 A/5A - 1No
10(g) Digital Type volt meter 0-500 V with selector switch -1Nos
11(h) Digital Multifunction meter having for mearing KW, KVA KVar, KWAH, KVAH , Pf, Hz etc-1 No
12(i) RYB LED indicating lamp -3 Nos
13Note :- (i) Earth work, PCC base etc. is deemed to be included with unit rate of item. (iii) All MCCB to be installed vertically and panel shall be designed accordingly.
14S&F meter box panel indoor type wall mounted suitable for fixing of 04 Nos of 1 Ph metering unit made out of CRCA sheet 2 mm thick, overall powder coated, power wiring with minimum 10 Sqmm PVC insulated FRLS multistranded copper conductor cable, meter shall be fixed over and including 10 mm thick backlit sheet of suitable size, door of panel shall be provided with transparent toughen glass of suitable size for all metre with following Accessories :-a) MCCB 100 Amp 4 pole 16 KA -01 Nos (As incomer)b) Copper bus bar of 300 Amp suitable for 4 wire system mounted on rubber insulators (Outgoing)(c) MCB 63 Amp TPN -05 Nos(d) MCB SPN 32 Amp-01 Nos (for Staircase 25X30CM)(e) Separate compartment for 4 Nos metering units(f) Metre shall be measured and paid separately.
15Excavation in trenches not exc. 1.5 m wide and not exc 1.5 metre deep in soft / loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom surface to required level all as specified and directed by Engineer-in-Charge.
16Removing excavated soil n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed.
17Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick using excavated soil complete all as specified and as directed.
18M&L for Providing cement concrete type B-1, 1:2:4 (using 20mm graded aggregate) as in copings, apex stones, bed plates, kerbs etc including weathering, slightly rounded or chamfered angles and throating as directed
19Material and labour for dry river sand, washed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading, levelling & punning complete as specified and directed .Note :- Punned thickness (18 cm) shall only be considered for payment.
20Supplying and laying unreinforced precast concrete cable cover, LV, Type 2, flat, size 300 mm x 180 mm x 40 mm complete all as specified
21M&L for cutting of Road / PCC Hard standing / similar work, not exceeding 30 cm in width, not exceeding 45 cm in depth for passing of LT cable / Pipe etc, making good disturbed surface by returning filling excavated material after laying of pipe / cable and top 20 cm portion filled with PCC (1:2:4) type B-1 using 20 mm graded aggregate, removing surplus excavated material to a distance not exceeding 50 metre complete all as specified and directed .
22M&L for 40 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable including taking down old pipe complete all as specified and directed by Engr-in-Charge.
23M&L for 50 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable including taking down old pipe complete all as specified and directed by Engr-in-Charge.
24M&L for 80 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable including taking down old pipe complete all as specified and directed by Engr-in-Charge.
25Taking out existing unserviceable LT UG cable any size, from trenches etcNote :- Excavation, earth work, shall be measured and paid separately under appropriate items of this BOQ.
26Taking out existing U/S panel from existing site including disconnecting of existing cable complete
27Material & Laying, jointing and testing of LT under ground electric power cable crossed linked polyethylene (XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 16 sqmm cross sectional area, 4 core, laid in trenches / laid under floor or fixed naked with walls / on poles / in ducts / in GI pipes etc. with and including MS Clamps, nuts, bolts, washers complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks / PCC cover and pipe shall be measured and paid separately under appropriate items of this BOQ.
28Description as per Item No 15 here in above but of size 3.5 core 25 Sqmm.
29Description as per Item No 15 here in above but of size 3.5 core 35 Sqmm.
30Description as per Item No 15 here in above but of size 3.5 core 50 Sqmm,
31Description as per Item No 15 here in above but of size 3.5 core 95 Sqmm,
32Description as per Item No 15 here in above but of size 3.5 core 120 Sqmm.
33Description as per Item No 15 here in above but of size 3.5 core 150 Sqmm.
34Description as per Item No 15 here in above but of size 3.5 core 185 Sqm.
35M&L for straight through joint outdoor type for LT UG cable including jointing kits heat shrinkable type complete suitable for aluminium conductor cables of Size of 25 to 50 sqmm 3.5 core complete all as specified and directed
36M&L for straight through joint outdoor type for LT UG cable including jointing kits heat shrinkable type complete suitable for aluminium conductor cables of Size of 70 to 120 sqmm 3.5 core complete all as specified and directed
37M&L for straight through joint outdoor type for LT UG cable including jointing kits heat shrinkable type complete suitable for aluminium conductor cables of Size of 150 to 185 sqmm 3.5 core complete all as specified and directed
38S&F in repairs MCCB FP 400 A 50 kA with Electronic microprocessor release with over load Zone of adjustment 0.4 to 1.0 In and Electronic release with Short circuit Zone of adjustment 1.5 to 10.0 Ir. (Adjusted current) with time with Extended Rotary Handle vari-depth type and Spreader between phases and neutral, fixed in existing panel & connecting complete all as specified & directed
39S&F in repairs MCCB 200 Amps, 4 pole, breaking capacity 25 kA, with thermal Magnetic release adjustable type fixed in existing panel & connecting complete all as specified & directed
40S&F in repairs MCCB 100 Amps, 4 pole, breaking capacity 16 kA, with thermal Magnetic release adjustable type fixed in existing panel & connecting complete all as specified & directed
41M&L for boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including supply & inserting HDPE pipe of 150 mm dia 0.4 mpa working pressure
42M&L for renewal of Earthing complete with galvanised steel earth electrode 60 cm x 60 cm x 6 mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level connected to and including galvanised earth lead as GI wire of 4 mm dia size by means of bolts,nuts, check nuts and washer etc made of galvanised iron and connected to earthing test point all as shown in electrical plate No.3 of SSR Part I 2009 and as specified or indicated and testing on completion including excavation earth work in any type of strata, PCC (1:3:6) type C1 earthing chamber, precast RCC slab 50 mm thick in reinforced cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric (XPM jali weight not less than 4 Kg/Sqm), cast iron frame, funnel with wire mesh, 20 mm bore medium grade GI watering pipe, lugs, 15 mm bore medium grade GI protection pipe, test point etc. complete all as specified and directed.
43Note: (i) Rate quoted under this item is deemed to include the cost of 7.5m length of earth lead and its protection tube. Any addition in length shall be measured and paid extra.
44M&L Earthing complete with galvanised steel earth electrode 60 cm x 60 cm x 6 mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level connected to and including galvanised earth lead as GI strip of 32X6mm size by means of bolts,nuts, check nuts and washer etc made of galvanised iron and connected to earthing test point all as shown in electrical plate No.3 of SSR Part I 2009 and as specified or indicated and testing on completion including excavation earth work in any type of strata, PCC (1:3:6) type C1 earthing chamber, precast RCC slab 50 mm thick in reinforced cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric (XPM jali weight not less than 4 Kg/Sqm), cast iron frame, funnel with wire mesh, 40 mm bore medium grade GI watering pipe, lugs, 40 mm bore medium grade GI protection pipe, test point etc. complete all as specified and directed.
45Note: (i) Rate quoted under this item is deemed to include the cost of 7.5m length of earth lead and its protection tube. Any addition in length shall be measured and paid extra. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57968182
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 43.74 Lakhs
LAST DATE 31-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Special Repairs / Replacement Of Lt Panels / Feeder Pillar Box And Connected Lt Cables Of Certain Md Accn Area At Darjipura At Af Stn Vadodara.
Basic Detail
Tender No 8240/E8
Bidding Type Tender
Location
City Vadodara
State Gujarat
Key Dates
Publish Date 10 Oct 2026
Submission Date 31 Oct 2026
Open Date 02 Nov 2026
Finance
Tender Value 43.74 Lakhs
Tender Fee 500
EMD 87500
Exemption Not Available
Document List
8240PS.pdf
b9a1e606-e456-4c84-b1eb-7a52bae121c2.html
BOQ_889552.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 10, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 31, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 6 days
Nov 02, 2026

Bid Opening Date

Technical bids will be opened and evaluated.