Tender For special Repair / Replacement Of Lt Cable At Sbs Enclave Under Ge (East) Ferozepur Cantt
Tender Overview
Project Description
Tender for special Repair / Replacement Of Lt Cable At Sbs Enclave Under Ge (East) Ferozepur Cantt
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 16-Oct-2026 | Corrigendum | Financial Bid | 30-Oct-2026 |
| 2 | 30-Oct-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 06-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep for laying of cable, pole foundation, etc including taking out old brick cable protection cover and getting out forming bottom surface to required gradient, complete all as specified and directed. |
| 2 | Returning, filling in, earth including spreading, leveling watering and well ramming in layers each not exceeding 25 cm thick each layer, complete all as specified and directed. |
| 3 | Removal of surplus soil to a distance not exc. 50 meter and depositing where directed at a level not exc. 1.5 meter above the starting point, complete all as specified and directed. |
| 4 | Material and labour brick protection layer for cables laid in trenches using sub-class ‘B’ bricks laid dry width wise acrose the line of cable (perpendicular to the direction of cable), complete all as specified and directed. |
| 5 | M& L for Dry and clean fine sand for cable cushioning to underground cable protection, complete all as specified and directed. (Excavation and earth work measured separately). Note- Punned down thickness shall be measured and complete all as specified and directed. |
| 6 | Dismantling and taking down old UNSV LT UG cable of any type and size complete all as specified and directed. |
| 7 | Material & labour for boring hole under the road/ payment/ hard standing upto 100 mm Bore Pipe not less than one metre below ground level, complete all as specified and directed.. |
| 8 | Supply & fixing galvanised iron pipe light grade ISI marked 100 mm bore for passing of cable, fixed to poles/ walls/ laid under floor complete with and including fittings, complete all as specified and directed. |
| 9 | All as per item No 8 here-in-before but size 50 mm bore, complete all as specified and directed. |
| 10 | All as per item No 8 here-in-before but size 40 mm bore, complete all as specified and directed. |
| 11 | Supply & laying & testing in replacement cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, aluminium conductor, electric power cable (heavy duty) of size 500 Sqmm 3.5 Core1100 Volts. Note: Rate of underground cable excludes earth work, sand cushioning, brick of PCC/RCC covering, light grade GI tubing where necessary, etc, quantity of the same will be measured and paid separately. |
| 12 | ll as per item No 11 here-in-before but size 240 sq mm 3.5 core complete all as specified & directed. |
| 13 | ll as per item No 11 here-in-before but size 185 sq mm 3.5 core complete all as specified & directed. |
| 14 | ll as per item No 11 here-in-before but size 150 sq mm 3.5 core complete all as specified & directed. |
| 15 | ll as per item No 11 here-in-before but size 50 sq mm 3.5 core complete all as specified & directed. |
| 16 | ll as per item No 11 here-in-before but size 35 sq mm 3.5 core complete all as specified & directed. |
| 17 | ll as per item No 11 here-in-before but size 25 sq mm 4.0 core complete all as specified & directed. |
| 18 | Supply, installation, testing and commissioning in replacement of CPRI approved, factory made, LT panel board cubical, Outdoor type, floor mounted double door, suitable for AC, 3 phase 4 wire, 50 cycles, 415 Volts, Front & Rear openable double door with locking arrangement. The panel board shall be made of 3.15 thick CRCA/MS sheet duly powder coated with pure polyester based paint on both externally and internally. The panel have to provide proper compartment as per IS specification and wiring of panel with suitable size of copper conductor FRLS cable not less than 2.5 Sqmm , thimbles including cable entry glands, complete all as specified & directed.Base frame of the panel shall be made of angle iron of size 50 x 50 x 6 mm embedded in PCC (1:3:6) type C-2 using 40 mm stone aggregate of upto 1/2 mtr height below GL & 1/2 mtr for above GL. (i) Panel having common aluminium bus bar of capacity 12000 Amp TPN each and suitable capacity TPN bus bar for outgoing MCCB's, including aluminium lugs to connect the cable and cable gland for Each cable entry as per cable size. Contd...18.01/- |
| 19 | (ii) Incoming:-(a) ACB 4 Pole, 415 V, Microprocessor release type (Manual Draw out type) of capacity 630 Amps. ICu= 50 KA with adjustable thermal setting 0.8 to 1 In and Adjustable magntic setting 5 to10 In. (Incoming)(iii) Outgoing:-(a) MCCB fixed TM type based with overload short circuit release suitable size and capacity, 250 Amp 4 Pole ICU = ICS = 36 KA. - 06 Nos. (outgoing)(b) Same as above but of Capacity 63 Amps, 4 Pole 25 KA -01 Nos. (outgoing)(iv) Volt Meter 0 - 500 Volts digital type square shape flush mounted with selector switch - 1 Nos(v) Ammeter 0 - 800 Amps digital type square shape 96mm flush mounted with selector switch and CT's 630/5 A - 1 Nos.(vi) Indicator lamp RYB :01 Set. with CT Coil complete |
| 20 | Supply, installation, testing and commissioning in replacement of CPRI approved, factory made, LT panel board cubical, Outdoor type, floor mounted double door, suitable for AC, 3 phase 4 wire, 50 cycles, 415 Volts, Front & Rear openable double door with locking arrangement. The panel board shall be made of 3.15 thick CRCA/MS sheet duly powder coated with pure polyester based paint on both externally and internally. The panel have to provide proper compartment as per IS specification and wiring of panel with suitable size of copper conductor FRLS cable not less than 2.5 Sqmm , thimbles including cable entry glands, complete all as specified & directed.Base frame of the panel shall be made of angle iron of size 50 x 50 x 6 mm embedded in PCC (1:3:6) type C-2 using 40 mm stone aggregate of upto 1/2 mtr height below GL & 1/2 mtr for above GL. (i) Panel having common aluminium bus bar of capacity 500 Amp TPN each and suitable capacity TPN bus bar for outgoing MCCB's, including aluminium lugs to connect the cable and cable gland for Each cable entry as per cable size. Contd...19.01/- |
| 21 | (ii) Incoming:-(a) MCCB Adjustable type thermal released 0.8 to 1 In setting and adjustable magnetic setting type with overload short circuit release suitable size and capacity, 250 Amp 4 Pole ICU = ICS = 36 KA. - 01 Nos. (Incoming) (iii) Outgoing:-(a) MCCB Fixed TM type based with overload short circuit release suitable size and capacity, 63 Amp 4 Pole ICU = ICS = 25 KA. - 06 Nos. (outgoing) (b) All as per (a) above but MCCB of Capacity 32 Amps, 4 Pole 18 KA -01 Nos . (outgoing) (iv) Volt Meter 0 - 500 Volts digital type square shape flush mounted with selector switch - 1 Nos(v) Ammeter 0 - 300 Amps digital type square shape 96mm flush mounted with selector switch and CT's 300/5 A - 1 Nos.(vi) Indicator lamp RYB :01 Set. |
| 22 | Earthing complete with galvanized mild steel earth plate electrode size 600 mm x 600 mm x 6.3 mm thick buried directly in ground (Preferably in vertical position) earth pit not less than 2.25 metre below normal ground level with top edge of the earth plate not less 1.5 metre below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20 mm bore medium grade galvanized iron water tubing fixed with cast iron funnel and wire mesh and 50 mm bore light grade galvanized iron protection pipe for earth strip 32 x 6 mm upto 7.5 m length, charcoal, common salt, complete all as shown in EP No 1 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion, complete all as specified and directed. |
| 23 | Supply, Installation and Fixing LT Cable junction box shall be made out of Thermoplastic Polycarbonate and size should be not less than 200mm x 160mm x 98 mm(upto Cable Size 16/25sq.mm). The Polycarbonate JB shall be environment friendly, recyclable, halogen & silicon free, anti acid & anti corrosive,IP 65 in accordance with IEC 60529,Weatherproof UV-resistant, rainwater-proof, temperature-resistant. the Degree of protection against mechanical load shall be in accordance with EN 50298 - 98 for IK 08 including one No. 4 pole connector and MCB of 6 amp and complete all accessories. Complete all as specified and directed. |
| 24 | Supply & fixing 1.5 sqmm, 3 core PVC insulated and FR PVC round sheathed copper conductor flexible cable, 1100 volts grade for connection from Junction Box to street light fittings complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.