Power Government Departments Closing in 15 days TDR #57964437

Tender For Augmentation Of Grid Station Khellani From 100 Mva To 150 Mva Along With Supply Installation Testing and Commissioning of 250 Kva,33/0.433 Kv Auxiliary Transformer, Supply Installation Testing and Commissioning of 63 Kva Dg Set , Replaceme

Issued by Government Departments · Doda, Jammu and Kashmir
Tender Value
11.04 Crore
Estimated cost
Bid Submission
30 Oct 2026
15 days left
EMD
22.10 Lakhs
Bank guarantee accepted
Document Fee
5000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Doda → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Augmentation Of Grid Station Khellani From 100 Mva To 150 Mva Along With Supply Installation Testing and Commissioning of 250 Kva,33/0.433 Kv Auxiliary Transformer, Supply Installation Testing and Commissioning of 63 Kva Dg Set , Replacement Of 132 Kv Bus Coupler Panel And Replacement Of Old 132 Kv 33 Kv Isolators At Gss Khellani

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 14-Oct-2026 Corrigendum-I Other 30-Oct-2026

BOQ

Name of Work:- Augmentation of Grid Station Khellani from 100 MVA to 150 MVA along with SITC of 250 KVA,33/0.433 KV Auxiliary Transformer, SITC of 63 KVA DG Set , replacement of 132 KV Bus coupler panel and replacement of old 132 KV 33 KV Isolators at GSS Khellani
Sl. No. Item Description
1SITC of 50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and other required accessories and fittings with online DGA monitoring Kit, online dehydration kit and maintenance free automatic breathers as per technical specifications with mandatory spares as per SBD.(as per cost data 2023-24 with PV as per IEEMA calculation)
2SITC of STRUCTURES
3Galvanised Structures
4Galvanised Nuts and Bolts
5SITC of POWER AND CONTROL CABLES
63.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
78 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
816 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor controlcable complete
919 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor controlcable complete
10SITC OF CONDUCTOR AND HARD WARE FITTINGS
11400mm2 ACSR Zebra (a)Aluminium =54/3.18 mm (b) Steel= 7/3.18mm overall diameter =28.62mm Approx. Wt. =1621kg/km ultimate strength = 130.32KN
12Single Tension Fittings For Twin Zebra shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
13Single Suspension Fittings For Twin Zebra shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN.
14T Clamps Twin 0.4/ Twin 0.4, made of Alluminium Alloy and shall comply in all respects with IS:5561 1970 (latest edition)
15Disc Insulators 120 KN,Ball &Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected
16Disc Insulators 70 KN,Ball &Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected.
17Spacer for twin Zebra
18P G Clamps 0.4 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
19CT/LA Bimetallic Clamps Twin 0.4, made of Alluminium Alloy and shall comply in all respects with IS:5561 1970 (latest edition) for Current transformers and surge arrestors
20Bimetallic Pad Clamps Twin 0.4, made of Alluminium Alloy and shall comply in all respects with IS:5561 1970 (latest edition) for isolator/circuit breaker
21T Clamps 0.4/0.4, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
22Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75x10 / 50x 6 / 25x3 )mm risers for Equipment and Structural Earthing
23CIVIL WORKS
24Laying of 132KV Column foundations
25Laying of Transformer foundations for Three phase 50 MVA Transformer (as per Drawing)
26Construction of Oil sump & Tank for three phase 50 MVA Transformer
27Construction of fire protection wall
28Dismantling of old transformer foundation
29Dismantling of 20 MVA Power Transmformer along with hardwares etc.
30Dragging, Loading, Carriage, Transportation of 20 MVA Power trasnformer and all accessories from GSS Khellani to Divisional Staore Udhampur and unloading therof.
31SITC of 33KV EQUIPMENTS along with dismantling of exsiting equipments
32Single Phase 36KV 50 c/s, outdoor metal oxide gapless type, 30KV (rms) Surge Arrestor class 3 including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
3333 KV Control and Realy panel for transformer bay simplex/duplex as per requirement, completely wired including substation automation supporting IED/numerical relaysof makeABB/SIEMENS/GE/MICOM/ALSTOM/SCHNEIDERwith IEC61850 compatibility
34SITC of 132KV EQUIPMENTS
35145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades
36132KV Control and Relay Panel for transformer bay completely wired includingSubstation automation/SCADA, supporting IEDs/numerical relays inlcuding Distance Recorder of make ABB/SIEMENS/GE/MICOM/ALSTOM/SCHNEIDER withIEC 61850 Compatibility including under frequency relay,differencial protection,directional o/c and e/f protection(on HV &LV side) ,numericale communicable REF protection relay,,over flux protection,local breaker backup protection(integrated in distance protection and backup protection),separate relays for primary and backup protection
37SITC of 63 KVA DG Set, 3 phase, silent type, Rated Engine Power at 100% load :50KW including construction of foundation, canopy, local chemical earthing pit, supply of cables & change-over including cabling etc, as per site specifications / requirements.
384 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
3910 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLSgalvanised steel wire/ strip armoured stranded copper conductor control cable complete
40Dismantling of old DG Set & associated Hardwares needed.
413 pole, SF6 gas filled, out door Circuit Breaker , including all accessories,auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps of 3 phase, 50 c/s and 31.5KA for 1 second). With pad clamps & spare T/C coils
42145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators withEarthing Blades with pad clamps
43Single phase, 50 c/s 145KV Current Transformers (600-300-150/1-1-1-1-1 A or 1200- 600-300/1-1-1-1-1A or 2000-1600-1200/1-1-1-1-1A or as per site specifications), 40 KA for one second, rated dynamic current 100KA(peak),Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accesories, auxiliaries etc.
44132KV Control and Relay Panel completely wired including Substation automation/SCADA, supporting IEDs/numerical relays inlcuding of make ABB/SIEMENS/GE/MICOM/ALSTOM/SCHNEIDER withIEC 61850 Compatibility including BUS BAR protection
45132KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage 275KVP Dry lightning impulse withstand voltage ± 650 (KVP) with clamps
46SITC of STRUCTURES
47Galvanised Structures
48Galvanised Nuts and Bolts
49SITC of POWER AND CONTROL CABLES
502 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
518 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5210 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5316 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5419 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
552 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
564 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
573.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
58Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self- supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 micronS
59SITC of CONDUCTOR AND HARD WARE FITTINGS
60400mm2 ACSR Zebra (a)Aluminium =54/3.18 mm (b) Steel= 7/3.18mm overall diameter =28.62mm Approx. Wt. =1621kg/km ultimate strength = 130.32KN
61Single Tension Fittings For Single 400mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 120 KN.
62Single Suspension Fittings For Single 400mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
63Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia.Creepage total 430 mm and 260 mm protected.
64Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia.Creepage total 430 mm and 260 mm protected.
65T Clamps 400mm2 /400mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
66P I Clamps made of Alluminium Alloy and shall comply in all respects withIS:5561-1970 (latest edition)
67P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
68Earth Wire 7/3.15mm
69Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
70Cable Ducts With Covers
71Main Duct of Size 1200mm x 1200mm with 75mm Concrete Covers grade M15 of size 1300x500 mm
72Sub Main Duct of Size 600mm x 600mm with 75mm Concrete Covers grade M15 of size 700x500 mm
73Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing
74Concreting of yard & Laying Of Gravel
75CIVIL WORKS
76Laying of 132KV Column foundations (as per Drawing)
77Laying of 132KV Isolator foundations (as per Drawing)
78Laying of 132KV SF6 Breaker foundations (as per Drawing)
79Laying of 132KV CT foundations (as per Drawing)
80Laying of 132KV Post Insulator foundations (as per Drawing)
81Development of land (Excavation,Filling,Levelling etc) for construction of 132kv bay
82Chain Link Fencing adjacent to 132kv bay
83RCC wall
84RRM wall in 1:6
85Construction of Ramp/approach road for new 132kv bus-coupler bay
86SITC of 33/0.433 KV, 250 KVA, 3-Phase Distribution Transformers withBimettalic Terminal Connectors Energy Level-2 along with dismantling of old auxillary transformer. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57964437
AUTHORITY Government Departments
TENDER VALUE 11.04 Crore
LAST DATE 30-10-2026
Authority
Authority Name Power Development Department
Work Description Tender for Augmentation Of Grid Station Khellani From 100 Mva To 150 Mva Along With Supply Installation Testing and Commissioning of 250 Kva,33/0.433 Kv Auxiliary Transformer, Supply Installation Testing and Commissioning of 63 Kva Dg Set , Replacement Of 132 Kv Bus Coupler Panel And Replacement Of Old 132 Kv 33 Kv Isolators At Gss Khellani
Basic Detail
Tender No TLMD-III/Udh/13 of 2026-27 Dated 09-10-2026
Bidding Type Tender
Location
City Doda
State Jammu and Kashmir
Key Dates
Publish Date 14 Oct 2026
Submission Date 30 Oct 2026
Open Date 01 Jan 0001
Finance
Tender Value 11.04 Crore
Tender Fee 5000
EMD 22.10 Lakhs
Exemption Available
Document List
5b5620bf-3fc5-4585-bde6-0ea2ba1e8866.html
BOQ_1108601.xls
Tendernotice_1.pdf
Tendernotice_2.pdf
Tendernotice_3.pdf
Tendernotice_4.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 14, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 30, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 15 days
Oct 30, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 15 days

Tender Documents

Download All (ZIP) ↓
html

5b5620bf-3fc5-4585-bde6-0ea2ba1e8866.html

xls

BOQ_1108601.xls

pdf

Tendernotice_1.pdf

pdf

Tendernotice_2.pdf

pdf

Tendernotice_3.pdf

pdf

Tendernotice_4.pdf