Defence Statutory Bodies & Commissions/Committees Closing in 2 days TDR #57954603

Tender For Repair/Maint And Improvement To Certain E/M, Stp & Dg Set Installations And Attending Complaints And Misc Works Under Ge (A) Jaisalmer

Issued by Statutory Bodies & Commissions/Committees · Jaisalmer, Rajasthan
Tender Value
49.45 Lakhs
Estimated cost
Bid Submission
12 Nov 2026
2 days left
EMD
98900
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jaisalmer → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maint And Improvement To Certain E/M, Stp & Dg Set Installations And Attending Complaints And Misc Works Under Ge (A) Jaisalmer

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 21-Oct-2026 DateCorrigendum Date 12-Nov-2026

BOQ

Name of Work:- REPAIR/MAINT AND IMPROVEMENT TO CERTAIN E/M, STP & DG SET INSTALLATIONS AND ATTENDING COMPLAINTS AND MISC WORKS UNDER GE (A) JAISALMER
Sl. No. Item Description
1Supply installing ,connecting , testing and commissioning of design automation Panel of adequate size in repair having degree of ingress protection IP-67, cubicle type, floor mounted made out of 1.8 mm thick CRCA sheet & MS angle section 50mmx50mmx6 mm frame with sloping roof top type panel cover & compartmentalized for following equipments controls, and door etc with front openable, double door system lockable/openable by keys from front side having flush pattern fancy locks with louvers & air vent gasket for natural flow of air for 3 phase, 2 wire, 440 volts, 50 Hz and CPRI approved make, factory made in approved factory duly powder coated externally as well as internally provided with suitable ''U'' type gasket to make it dust and vermin proof & genral construction confirming to IS:8623/93, with provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder piller box safely including containing of detachable plate having provision for entry of armoured cable of adequate size with glands and mounted on a powder coated metal stand including and other jointing material complete incl taking down old with comprising of the following features:-a) Automatic Valve Control (Motorised Operating Valve). b) Ultrasonic Level transmitter (3 No.) c) Automatic Motor Pump control (6 no.s) d) Single phase motorised operating valves control (13 No.s Nos of MOV)
2The panel shall consist of the following equipments :- (a) Selector Switch (Main AUTO/MAN Mode, VALVE Mode, Pump AUTO/MAN Mode). Make:Schneider/ESBEE/SCHINDLER/ C&S (b) Indicator Lamp 230V AC (RED, YELLOW, GREEN, BLUE) Make:Schneider/ESBEE/SCHINDLER/ C&S. (c) Relays / Relay card (24 V DC, 230V AC) MAKE: LEONE/IDEC/SCHNEIDER (d) Hooter/Alarm 230 V AC/24 V DC. MAKE: MINILEC/SCHNEIDER/L&T/C&S/MIMIC (e) Push Buttons & Push Button with LED indicator (24V DC, 240V AC). Make:Schneider/ESBEE/SCHINDLER/ C&S (f) SMPS of suitable current & voltage rating. INPUT 230V AC & OUT 24 VDC, 5 A. MAKE: L&T/ C&S/ MINWELL/SCHNEIDER/NHP (g) Step down Transformer of input 230VAC & output 12VAC, 2A. (h) Programmable Logic Controller (PLC 24V DC). MAKE: ALLEN BRADLEY/ SIEMENS/MITSUBISHI/UNITRONICS(i) 0.5 sqmm internal control wiring. MAKE: POLYCAB/FINOLEX/PRIMECAB/TORRENT. (j) Separate MCB’s for 24VDC & 230 VAC equipment & internal wiring. Supply: 240V, 50 Hz Mounting: Wall Mounting type. (k) Water level controller. Make:- S M INSTRUMENTATION/ L&T/SIEMENS/Minilec
3Supply, Installation, Testing and commissioning in repair of Flow/Pressure Switch 1-10KG/sq.cm with Pressure Guage nad necessary fittings with proper wiring installed at delivery line of each pump set as directed by Engineer in charge. Make: INDFOSS/DANFOSS/RAPID CONTROL
4Supply, Installation, Testing and commissioning of Air releasing solenoid valve in repair for automatic air release while auto priming mode of each pump set having 10mm dia, 230 V AC operated coil installed at suction line of each pump set complete all as specified & directed by engineer-in-charge. Make:- ROTEX/AVCON/JOHNSON CONTROLS/ASCO
5Supply, Installation, Testing and commissioning of magnetic point level sensor in repair for level indication of UG sump and OHT. Make: S M Instrumentation/ Mahalaxmi/Crystal
6Supply, Installation, Testing and commissioning of Priming solenoid valve/ Actuator in repair for automatic priming mode of each pump set having 25mm dia, 230 V AC operated coil with complete bypass arrangement for Auto as well as Manual operation complete all as specified & directed, Make:- ROTEX/AVCON/JOHNSON CONTROLS/ASCO
7Supply, Installation, Testing and commissioning of motor actuated butterfly valve with the following specifications including all accessories (CI/DI/MS fittings required at site) incl taking down old valve complete as directed by Engineer-in-Charge. (a) Valve size 200mm dia. (b) Designed line pressure 6 kg/Sqcm(c) Operating Angle : 90 degrees(d) Disc material CI with nylon coating(e) Limit switches : 02 Nos for open and close(f) Mounting : Splash proof-Direct on valve/ Extended type as per site requirement.(g) Input Supply : 230V, AC, 50 HZ (h) In built wireless modem compatibility for remote communication(i) Valve position indication with an output of 4-20m A(j) The actuator should be capable of accepting 4-20m A of input of regulating purposes (k) Mannual Operation : Hand Wheel/Rapid ControlMake:ROTORK/ S M INSTRUMENTATION/ EMTORK/ HASSEL HOFFNER/ S D TORQUE/ AUMA
8Supply, Installation, Testing and commissioning of motor actuated butterfly valve with the following specifications including all accessories ((CI/DI/MS fittings required at site) incl taking down old valve complete as directed by Engineer-in-Charge.(a) Valve size 300mm dia. (b) Designed line pressure 6 kg/Sqcm(c) Operating Angle : 90 degrees(d) Disc material CI with nylon coating(e) Limit switches : 02 Nos for open and close(f) Mounting : Splash proof-Direct on valve/ Extended type as per site requirement.(g) Input Supply : 230V, AC, 50 HZ (h) In built wireless modem compatibility for remote communication(i) Valve position indication with an output of 4-20m A(j) The actuator should be capable of accepting 4-20m A of input of regulating purposes (k) Mannual Operation : Hand Wheel/Rapid ControlMake:ROTORK/S M INSTRUMENTATION / EMTORK/ HASSEL HOFFNER/ S D TORQUE/ AUMA
9Supply, Installation, Testing and commissioning of motor actuated butterfly valve with the following specifications including all accessories ((CI/DI/MS fittings required at site) incl taking down old valve complete as directed by Engineer-in-Charge (a) Valve size 350mm dia. (b) Designed line pressure 6 kg/Sqcm(c) Operating Angle : 90 degrees(d) Disc material CI with nylon coating(e) Limit switches : 02 Nos for open and close(f) Mounting : Splash proof-Direct on valve/ Extended type as per site requirement.(g) Input Supply : 230V, AC, 50 HZ (h) In built wireless modem compatibility for remote communication(i) Valve position indication with an output of 4-20m A(j) The actuator should be capable of accepting 4-20m A of input of regulating purposes (k) Mannual Operation : Hand Wheel/Rapid ControlMake:ROTORK/S M INSTRUMENTATION/EMTORK/ HASSEL HOFFNER/ S D TORQUE/ AUMA
10Supply & fixing in replacement 6 core, 1.5 sqmm cross sectional area armoured copper conductor cables, 1100 volts grade heavy duty cable PVC insulated and PVc sheathed, laid in trenches/ laid under floor or fixed maked with walls / on poles/in ducts/in GI pipes etc complete all as specified, Make: Polycab/FSC/Torrent/Finolex
11Supply & fixing in replacement 4 core, 1.5 sqmm cross sectional area copper conductor cables, 1100 volts grade heavy duty cable PVC insulated and PVc sheathed, laid in trenches/ laid under floor or fixed maked with walls / on poles/in ducts/in GI pipes etc complete all as specified, Make: Polycab/FSC/Torrent/Finolex
12Supply & fixing in replacement 5 Pair x 0.5 sqmm cross sectional area copper conductor cables, heavy duty cable PVC insulated and PVC sheathed, laid in trenches/ laid under floor or fixed maked with walls / on poles/in ducts/in GI pipes etc complete all as specified, Make: Polycab/FSC/Torrent/Finolex
13Supply & fixing in replacement 2 core, 1.5 sqmm cross sectional area copper conductor cables, 1100 volts grade heavy duty cable PVC insulated and PVC sheathed, laid in trenches/ laid under floor or fixed maked with walls / on poles/in ducts/in GI pipes etc complete all as specified, Make: Polycab/FSC/Torrent/Finolex
14Excavating in trenches not exc 1.5 metre wide and not exc 1.5 metre in depth for foundation or for shafts, walls, manholes, laying of cables, pipes etc not exc 10 Sqm on plan and getting out in soft/loose soil.
15Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil.
16Removal of excavated soil/ material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified.
17Supply and laying DOUBLE WALL CORRUGATED (DWC) pipe 40 mm outer dIa 32 mm bore as per is 16205 part 24 cable protectionincluding all fitting as required complete all as specified and directed by engineer- in-charge.
18Supply, installation and testing in repair of online Electrostatic Non-chemical water treatment system with electrically operated control panel to be fixed on sub header of AC Plant with Stainless Steel Shell 304 (Negative Electrode) & Catalytic Copper Electrode (Positive Electrode). The outer casing shall be of 304 grade stainless steel with both ends flanged and capable preventing scale formation. The same shall be suitable for water flow rate 1500 LPM for dia of pipe 4” / 100 MM in condenser circuit. The work includes cutting of existing GI/MS sub header and providing mild steel flange heavy duty and joining with nut & bolts, gaskets at both ends with welding and modification in existing system complete as reqd all as directed by Engr-in-Charge.MAKES: SCALEOFF(POLO)/HYDROKON/DOLPHIN or equivalent in PS list of make/approved by AO.Note:- Design should be prior approved by GE. Note: (a) Installation and Testing shall be carried out by OEM/authorised representative only at site in presence of JE E/M/Engr-in-Charge & Satisfactory testing reports shall be submitted before release of payment, if not contractor shall rectify the same till obtaining testing reports satisfactory without any additional cost.
19Supply, installation and testing in repair Control Panel is made of MS Powder Coated 220VAC 50HZ Single Phase. It has input, output Meters and ON and FAULTY Indicator with inbuilt SMPS to protect it from Voltage Fluctuation suitable for 4\\"/100mm dia scaleoff preventor complete as reqd all as directed by Engr-in-Charge.MAKES: SCALEOFF(POLO)/HYDROKON/DOLPHIN/WELDON or equivalent in PS list of make/ approved by AO.Note:- Design should be prior approved by GE. Note: (a) Installation and Testing shall be carried out by OEM/authorised representative only at site in presence of JE E/M/Engr-in-Charge & Satisfactory testing results shall be submitted before release of payment, if not contractor shall rectify the same till obtaining testing reports satisfactory without any additional cost.
20Supply, installation and testing in repair of online Electrostatic Non-chemical water treatment system with electrically operated control panel to be fixed on sub header of AC Plant with Stainless Steel Shell 304 (Negative Electrode) & Catalytic Copper Electrode (Positive Electrode). The outer casing shall be of 304 grade stainless steel with both ends flanged and capable preventing scale formation. The same shall be suitable for water flow rate 1500 LPM for dia of pipe 3” / 80 MM in condenser circuit. The work includes cutting of existing GI/MS sub header and providing mild steel flange heavy duty and joining with nut & bolts, gaskets at both ends with welding and modification in existing system complete as reqd all as directed by Engr-in-Charge.MAKES: SCALEOFF(POLO)/HYDROKON/DOLPHIN or equivalent in PS list of make/approved by AO.Note:- Design should be prior approved by GE. Note: (a) Installation and Testing shall be carried out by OEM/authorised representative only at site in presence of JE E/M/Engr-in-Charge & Satisfactory testing reports shall be submitted before release of payment, if not contractor shall rectify the same till obtaining testing reports satisfactory without any additional cost.
21Supply, installation and testing in repair Control Panel is made of MS Powder Coated 220VAC 50HZ Single Phase. It has input, output Meters and ON and FAULTY Indicator with inbuilt SMPS to protect it from Voltage Fluctuation suitable for 3\\"/80mm dia scale off preventor complete as reqd all as directed by Engr-in-Charge.MAKES: SCALEOFF(POLO)/HYDROKON/DOLPHIN/WELDON or equivalent in PS list of make/or approved by AO.Note:- Design should be prior approved by GE. Note: (a) Installation and Testing shall be carried out by OEM/authorised representative only at site in presence of JE E/M/Engr-in-Charge & Satisfactory testing results shall be submitted before release of payment, if not contractor shall rectify the same till obtaining testing reports satisfactory without any additional cost.
22M&L for Cutting and taking out compressor of split type AC of 1.5 TR and supply and fixing the compressor with jointing of copper refrigent pipe line in and including charging of refrigerant gas to required level , NRV VALVE ,RELAY AND OVERLOAD RALAY AND CAPILLARY, FILTER AND BRIZING complete all as specified & directed by Engineer-in-charge. Make- As per existing make and model
23M&L for Cutting and taking out compressor of split type/ Cassette AC of 2TR and supply and fixing the suitable compressor with jointing of copper refrigerant pipe line in and including charging of refrigerant gas to required level , NRV VALVE ,RELAY AND OVERLOAD RALAY AND CAPILLARY, FILTER AND BRIZING complete all as specified & directed by Engineer-in-charge. Make- As per existing make and model
24S&F in repair automatic voltage stabilizer of working range 90V-300VAC±5V,50Hz suitable for for one AC(ordinary/inverter) suitable for capacity 1.5 TR with calibration accuracy ±2% complete all as specified and directed by Engr-in-charge. Make: Microtek of model PEARL EM4090 or equivalent in PS list of make.
25S&F in repair automatic voltage stabilizer of working range 90V-300VAC±5V,50Hz suitable for for one AC(ordinary/inverter) suitable for capacity 2 TR with calibration accuracy ±2% complete all as specified and directed by Engr-in-charge. Make: Microtek of model PEARL EM5090 or equivalent in PS list of make.
26M&L for cleaning of E/M plants surrounding area by surface excavation upto 10 cm depth incl removing shrubs,grass,miniplants and other unwanted materials and levelling complete in soft/loose soil all as specified and directed by Engineer-in-charge.
27M & L for cutting of branches of tree of various length to keep a clear E/M installations surrounding area and depositioning the cut branches upto 50 mtr from pump house all as specified and directed by Engineer-in-charge.
28Material and labour for cross arms, bracing supports, clamps fabricated out of structural steel such as ISMC, angle iron, flat iron sections including hot galvanised nuts & bolts, washers for single and two pole structure welding, bending cold or hot, drilling holes for bolts, in any shape or size for supporting of plant equipments as specified and including of one under coat and finishing coat with aluminium paint over a coat of red oxide primer.Note:- Design should be approved by EIC prior giving orders for manufacturing the items.
29Supply & fixing in repair 3 core, 2.5 sqmm copper conductor cables, 1100 volts grade heavy duty cable pvc insulated and pvc sheathed with 5/15 amps modular switch socket, laid in trenches/ laid under floor or fixed maked with walls / on poles/in ducts/in GI pipes etc complete all as specified and directed by engr-in-charge.
30Supply & charging of refrigerant gas non flammble R-134C (freon) for Refrigerator/water cooler/DF/ window/split type ACs of any capacity complete and checking/testing for proper functioning all as specified & directed by Engineer-in-charge.
31Supply & charging of refrigerant gas non flammable R-407 for ACs of any capacity complete and checking/testing for proper functioning all as specified & directed by Engineer-in-charge.
32Material and labour for carrying out ‘D’ check for Major Overhaul for various capacity DG set by replacing the necessary accessories of DG set including replacement of defective parts with new ones i.e., piston rings, cylinder liners, main/connecting rod bearings, thrust washers, and a full engine gasket packing set if necessary, Inspect and clean the fuel injection system & Turbo Service, fuel injection pump (FIP) calibration, fuel injector nozzles, and turbocharger core overhauling, Cooling & Lubrication,Heavy coolant system flush, thermostat valves, water pump repair kit, Electrical wiring, Inspection of Starter motor and alternator bearing servicing, engine head face skimming/decarbonization if necessary, Inspect the crankshaft, connecting rods and cylinder head. Inspect alternator windings, bearings, insulation resistance and terminals.Inspect AVR, excitation system and control panel and full on-site reassembly complete all as specified and directed by Engineer-in-Charge.Note :- (i) Service Certificate of the 'D' Check shall be submitted by Contractor.Make of DG set shall be repaired : KIRLOSKER/ CUMMINS /GREAVES/Ashok Leyland/Mahindra&Mahindra.
33All as per item No. 31 here-in-before but for capacity of 20 KVA to 40 KVA DG Set.
34All as per item No. 31 here-in-before but for capacity of 62.5 KVA to 125 KVA DG Set.
35All as per item No. 31 here-in-before but for capacity of 150 KVA to 200 KVA DG Set.
36All as per item No. 31 here-in-before but for capacity of 250 KVA DG Set.
37All as per item No. 31 here-in-before but for capacity of 500 KVA to 600 KVA DG Set.
38Disconnecting and removal existing unservicable radiator supply and fixing,testing and commissioning of new radiator of following capacity including coolant reqd suitable for existing complete all as specified and directed by Engr-in-Charge.
39Radiator of DG Set capacity suitable for 40 to 62.5KVA
40Radiator of DG Set capacity suitable for 75/100 KVA Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57954603
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 49.45 Lakhs
LAST DATE 12-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maint And Improvement To Certain E/M, Stp & Dg Set Installations And Attending Complaints And Misc Works Under Ge (A) Jaisalmer
Basic Detail
Tender No 8138/26-27/E8
Bidding Type Tender
Location
City Jaisalmer
State Rajasthan
Key Dates
Publish Date 21 Oct 2026
Submission Date 12 Nov 2026
Open Date 14 Nov 2026
Finance
Tender Value 49.45 Lakhs
Tender Fee 500
EMD 98900
Exemption Available
Document List
83d2ee40-4818-43a2-8589-ad0e66f33353.html
BOQ_889461.xls
TenderDocuments8138.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 21, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 12, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 2 days
Nov 12, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 2 days
Nov 14, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 4 days

Tender Documents

Download All (ZIP) ↓
html

83d2ee40-4818-43a2-8589-ad0e66f33353.html

xls

BOQ_889461.xls

pdf

TenderDocuments8138.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender