Tender For Thorough Repairing And Overhauling Of 1 No. 800 Acb & 1 Nos. 800 S Acb Bus Coupler With 2 Nos Acbs At Distribution Panels For Station Lighting Loads & Electrical Accessories Under Dhapa Lock Drainage Pumping Station.
Tender Overview
Project Description
Tender for Thorough Repairing And Overhauling Of 1 No. 800 Acb & 1 Nos. 800 S Acb Bus Coupler With 2 Nos Acbs At Distribution Panels For Station Lighting Loads & Electrical Accessories Under Dhapa Lock Drainage Pumping Station.
BOQ
| Sl. No. | Item Description |
| 1 | TOTAL |
| 2 | Thorough checking , testing of the L.T incomer & outgoing ACB's panel by proper instrument in proper way engaging expert personel and detection of fault |
| 3 | Dismantling all the incoming & out going cable (240 Sqmm 4 core) from the panel after disconnetion the L.T source and discharge by the earth rod. |
| 4 | Racking out & drawing out of ACB from L.T incomming & outgoing panel after tripping the ACB's manually & keeping the ACB in a workable position inside the room. |
| 5 | Open out the ACB's cover carefully and complete dismentling all the parts like roller guide, main drive shaft, S.S pin, silt spring, rechet assembly, trip bridge assembly, male & female contact etc, by the proper tools & tackles engaging expert personel and keep in a sutible position at the pumping station. |
| 6 | Complete cleaning & overhauling all the parts of the ACB's in proper way by petrol & C.TC to remove carbon particals, moisture, dust etc & after overhauling refix all the components as per existing way and interlocking arrengement must be checked properly. |
| 7 | Dismantling the carbonized & dusty busbar from the panel, cleaning the carbon, moisture & dust from the busbar by the proper method using petrol & CTC and refixing the busbar after cleaning & reinsulation the busbar by proper method and also thorough cleaning the panel as per existing way and as per direction of EIC |
| 8 | Checking, testing fitting & fixing of the Thermal based release at the existing 800 Amps ACB's in proper way by using proper instruments. |
| 9 | Supply fixing of stud type LED indicating lamp (110 to 230Volt) (For phase & ON/OFF indication) |
| 10 | Re installation the ACB to the existing incomer panel by existing way. |
| 11 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials of 4 core 240 Sq mm cable. And re-connection all the incoming & out going cables (240 sqmm 4 core) in proper compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cable and existing way. |
| 12 | Adjusment of all linkage & contact movement of L.T. A.C.B. |
| 13 | Supply & fixing analog Square Ammeter (AE/ reputed make) as per existing specification and C.T. Ratio. |
| 14 | Supply & fixing analog Square Voltmeter (AE/ reputed make) as per existing specification and C.T. Ratio. |
| 15 | Necessary testing the 800 amps ACB's by the primary injuction method for checking the start, close and trip properly & commissioning of the ACB's & trail run. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 23 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender