Tender for Maint/Repair & Replacement In Lt Distribution Network Alongwith Replacement Of Oh Lines And Allied Works At Afs Yelahanka.
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil complete all as specified and directed. |
| 2 | Returning filling in excavated soil up to a depth of 30 cm after riddling of excavated soil (in lieu of sand) for cushioning of cable and refilling of trenches with left over normal excavated soil including spreading, levelling, watering and well ramming in layers complete all as specified and directed. |
| 3 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 4 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 1 with peak, size250 mm x 150mm x 40mm complete all as specified and directed. |
| 5 | Supply and laying in trenches, LT underground cable of size 16 Sqmm 4 core XLPE insulated armoured and PVC sheathed 1100 Volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall including taking down complete all as specified and directed. |
| 6 | All as per item No 5 here-in-before but 25 Sqmm 3.5 core |
| 7 | All as per item No 5 here-in-before but 35 Sqmm 3.5 core |
| 8 | All as per item No 5 here-in-before but 50 Sqmm 3.5 core |
| 9 | All as per item No 5 here-in-before but 70 Sqmm 3.5 core |
| 10 | All as per item No 5 here-in-before but 95 Sqmm 3.5 core |
| 11 | All as per item No 5 here-in-before but 120 Sqmm 3.5 core Note: For Sl No 5 to 11 necessary excavation and connected items shall be measured and paid separately under respective items of this schedule. |
| 12 | M & L for boring of holes under roof, pavement, hardstanding by trenchless technology and necessary machine including GI pipe of 50/80/100mm dia suitable for 0.4mpa working pressure complete all as specified and directed. |
| 13 | Supply and laying GI tubing light grade 50mm dia in trenches/fixing on pole /wall/crossing in drain etc. For protection of UG cable complete all as specified and directed |
| 14 | Supply and laying GI tubing light grade 80mm dia in trenches/fixing on pole /wall/crossing in drain etc. For protection of UG cable complete all as specified and directed |
| 15 | Supply and fix cable route indicator made out of 3 mm thick MS sheet of size 30 cm x 20 cm duly painted with two coats black paint over a coat of red oxide primer and writing cable direction, capacity, size of cable with white paint, mounted on angle iron 50x50x5 mm, angle height 75 cm, (45cm below ground level) with PCC 30cmx30cmx.60cm complete all as specified and directed. |
| 16 | Supply, installation and commissioning in repair LT out door loop in loop out terminal box with sloping canopy of size 600x450x250mm made out of 3 mm thick CRCA sheet duly painted with two coarse of synthetic enamel paint over a coat of rex oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 125 Amps 4 pole ,415 Amps, 50 Hz of breaking capacity 16 KA as incomer and 03 Nos 40 Amps TPN as outgoing including taking down old terminal boxes complete all as specified and directed. |
| 17 | Supply and fix in repair bus bar box of size 450x300x500mm fabricated by 3 mm thick MS sheet outdoor type, dust/vermin proof, mounted/fixed on angle Iron frame of MS equal angle size 40x40x6mm of height 0.90 mtr, erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate and including aluminium bus bar flat of size 50x6 mm fixed as bus bar over the insulators, sleeved for three phase and neutral, Multifunctional VAF Meter , RYB Indicator -01 Set of 03, and spray painting the box with two coats of enamel paint over a coat of metal primer including necessary excavation, PCC for fixing the box complete all as specified and directed. |
| 18 | Supply, install, testing and commissioning in repair of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 300 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable complete all as specified and directed. at site removing of existing panel and comprising of the following: INCOMING:-MCCB 4 pole 200 Amps 25 kA - 01 Nos OUTGOING:-MCCB 4 pole 100 Amps 25 kA - 01 NosMCCB 4 pole 63 Amps 25 kA - 02 Nos MCCB 3Pole 40Amps 16 kA - 04 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set for each outgoing and incoming MS work incl angle iron frame and PCC workSpace for mounting of additional MCB In future.Internal wiring including copper lugs |
| 19 | Supply, install, testing and commissioning in repair of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 600 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable complete all as specified and directed at site and comprising of the following: INCOMINGMCCB 4 pole 160 Amps 25 kA - 01 Nos OUTGOINGMCCB 4 pole 100 Amps 25 kA - 01 NosMCCB 4 pole 63 Amps 16 kA - 04 Nos MCCB 3 pole 40 Amps 16 kA - 01 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set of three MS work incl angle iron frame and PCC workInternal wiring including copper lugsNote: Bottom portion of the Panels should Minium 45 cms above the ground level |
| 20 | Supply, install, testing and commissioning in repair of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 600 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable complete all as specified and directed at site and comprising of the following: INCOMINGMCCB 4 pole 125 Amps 25 kA - 01 Nos OUTGOINGMCCB 4 pole 40 Amps 16 kA - 01 NosMCCB 4 pole 63 Amps 16 kA - 01 Nos MCB DP 32 Amp 10 kA - 01 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set of three MS work incl angle iron frame and PCC workInternal wiring including copper lugsNote: Bottom portion of the Panels should Minium 45 cms above the ground level |
| 21 | Supply and jointing straight through joint outdoor type 1100 volts grade heat shrinkable type suitable for 3.5x 25 Sqmm to 3.5x 95 Sqmm LT XLPE cable and testing after jointing complete all as specified and directed. |
| 22 | Supply and jointing straight through joint outdoor type 1100 volts grade heat shrinkable type suitable for3.5x 120 Sqmm to 3.5x 240 Sqmm LT XLPE cable and testing after jointing complete all as specified and directed. |
| 23 | Supply and fix in repair CTs suitable for existing LT panel board of capacity 250 to 320 Amps complete all as specified and directed. |
| 24 | Supply and fix in repair CTs suitable for existing LT panel board of capacity 63 to 200 Amps complete all as specified and directed. |
| 25 | Supply and fix in repair LED indicator lamps (R Y B) suitable for existing panel all omplete all as pecified and directed. |
| 26 | Supply and fix in repair MCCB 200 Amps, 4 pole 36 KA adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 27 | Supply and fix in repair MCCB 125 Amps 4 pole 16KA, adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 28 | Supply and fix in repair MCCB 100 Amps 4 pole 16 KA adjustable thermal setting type and confirming to IEC 60947-II complete all as specified and directed. |
| 29 | Supply and fix in repair MCCB 63 Amps 4 pole 16KA adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 30 | Supply and fix aluminium lugs suitable for UG cable of size 6 Sqmm to 25 Sqmm complete all as specified and as directed. |
| 31 | All as per item No 30 but of size 35 Sqmm to 50 Sqmm. |
| 32 | All as per item No 30 but of size 70 to 95 Sqmm. |
| 33 | All as per item No 30 but of size 120 to 185 Sqmm. |
| 34 | All as per item No 30 but of size 240 to 300 Sqmm. |
| 35 | Material and labour for carrying out repair of existing LT panel/ loop in loop out boxes by welding to the door / hinges of any size / type and Spray painting with synthetic enamel gray paint including cleaning of surrounding of LT Panel up to 1 Sqm replacement of unsv lug complete all as specified and directed. Please Enable Macros to View BoQ information |
| 36 | Material and labour for carrying out repair of existing LT panel/ loop in loop out boxes by welding to the door / hinges of any size / type and Spray painting with synthetic enamel gray paint including cleaning of surrounding of LT Panel up to 1 Sqm replacement of unsv lug complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 09, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 30, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayNov 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender